www.blaubergventilatoren.de Twin EC Fan Speed Controller & Auto Change Over Panel
8
Power up checks
On initial power up the fault output relay will be energized into the normal “No Fault” condition.
Fan No 2 will be run for 30 seconds, to allow the controller to monitor the correct running of the fan.
If no fan fault is detected the controller will switch off No 2 fan and bring on fan No 1.
If fan No 2 is found to be faulty the fault relay output will go into fault
condition, and the LED will fast flash and fan No 1 will be turned on.
OR
If fan No 1 is found to be faulty the fault relay output will go into fault condition, and the LED will fast flash and fan
No2 will be turned on.
NOTE If the installation only has one fan, then set “Fan 1 to override” mode and wire into Fan 1 terminals. Fan 2
will be ignored and the Power Up test mode will not occur.
If both fans are to run continually then put Fan 1 & Fan 2 into override mode.
Both fans will now be monitored for correct operation. The Power Up test mode will not occur.
Fan fault monitoring
Any fan that should be running will be monitored, and if its RPM falls below the Minimum RPM speed setting the
Fault Output relay will switch to Fault.
NOTE A fault output will also be generated for lack of mains power.
To ensure that false alarm outputs are not produced the controller will monitor the fan/s for 30 seconds of
continuous fault condition before producing a fault output. This time period is used to ensure that the Fault
Output relay is stable in its operation, and will not be affected by different start up times of fans or windy days
slowing the air flow down etc.
If a fan is found to be faulty the status LED will fast flash and the fault relay remains in the fault condition until such
time as the system is turned off then back on. No automatic fault reset occurs.
Field Test mode
Field Test mode reduces the Changeover Time range to 1 to 12 minutes and the Run On Time range to 0 to 15
seconds, for quicker testing during commissioning.
Fan Speed setting
The Low, Medium & High fan speeds should be set as required for each installation.
The speed setting pots will have a basic scaling of 0, 2.5, 5, 7.5 & 10,
corresponding to 0 to 100% PWM (0 to 10V).
Changeover mode
After the initial power up checks fan No 1 will run for the pre-set time. At the end of the run period Fan No 2 will
be turned on and Fan No 1 will be turned off. If no fan faults are detected this sequence will be repeated.
If a fan fault is detected the Fault Output relay will switch to the fault condition and the status LED will start fast
flashing. The fan being run will be turned off and the other fan will be turned on until the controller is powered
down then back on to reset the unit.
If both fans develop faults then both will be turned off until the controller is powered down, then back on to reset
the unit.
OPERATING PRINCIPLE