Blaupunkt B UK256 Twin EC Fan Speed Controller and Auto Change Over Panel User manual

Type
User manual

Blaupunkt B UK256 Twin EC Fan Speed Controller and Auto Change Over Panel is a device that allows for controlling and monitoring two Blauberg TwinBox EC Motor Fans and provides an automatic changeover in case of a fan failure. The controller ensures constant monitoring of any faults with automatic fan changeover on fan failure and a number of other control options. It is rated for continuous operation. The device is equipped with a fault output relay which will be energized into the normal “No Fault” condition on initial power up.

Blaupunkt B UK256 Twin EC Fan Speed Controller and Auto Change Over Panel is a device that allows for controlling and monitoring two Blauberg TwinBox EC Motor Fans and provides an automatic changeover in case of a fan failure. The controller ensures constant monitoring of any faults with automatic fan changeover on fan failure and a number of other control options. It is rated for continuous operation. The device is equipped with a fault output relay which will be energized into the normal “No Fault” condition on initial power up.

USER’S MANUAL
EN
Twin EC Fan Speed Controller & Auto Change Over Panel
www.blaubergventilatoren.de Twin EC Fan Speed Controller & Auto Change Over Panel
2
CONTENTS
INTRODUCTION ...................................................................................................2
SAFETY REQUIREMENTS ....................................................................................2
PURPOSE ................................................................................................................4
TECHNICAL DATA ................................................................................................. 4
INPUT / OUTPUT / OPTIONS / FUNCTION SETTINGS ...................................5
OPERATING PRINCIPLE .......................................................................................7
INTRODUCTION
This users manual is a main operating document intended for technical, maintenance, and operating staff. The
manual contains information about purpose, technical details, operating principle, design, and installation of the
Blauberg Twin EC Fan Speed Controller & Auto Change Over Panel and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of automation control of
ventilation systems and should be able to work in accordance with workplace safety rules as well as construction
norms and standards applicable in the territory of the country.
Please read the user’s manual carefully prior to installing and operating the unit.
All users manual requirements as well as the provisions of all the applicable local and national construction,
electrical, and technical norms and standards must be observed when installing and operating the unit.
The warnings contained in the users manual must be considered most seriously since they contain vital
personal safety information.
Failure to follow the rules and safety precautions noted in this users manual may result in an injury or unit
damage.
After a careful reading of the manual, keep it for the entire service life of the unit.
While transferring the unit control, the users manual must be turned over to the receiving operator.
SAFETY REQUIREMENTS
www.blaubergventilatoren.de
Twin EC Fan Speed Controller & Auto Change Over Panel
3
UNIT MOUNTING AND OPERATION SAFETY PRECAUTIONS
Disconnect the unit from
power mains prior to any
installation operations.
Do not operate the unit
outside the temperature range
stated in the user's manual.
Do not operate the unit
in aggressive or explosive
environments.
Do not lay the power cable of
the unit in close proximity to
heating equipment.
While installing the unit follow
the safety regulations specific
to the use of electric tools.
Do not change the power
cable length at your own
discretion.
Do not bend the power cable.
Avoid damaging the power
cable.
Do not put any foreign objects
on the power cable.
Unpack the unit with care.
Do not use damaged
equipment or cables when
connecting the unit to power
mains.
When the unit generates
unusual sounds, odour or emits
smoke disconnect it from
power supply and contact the
Seller.
Do not touch the unit controls
with wet hands.
Do not carry out the
installation and maintenance
operations with wet hands.
Do not wash the unit with
water.
Protect the electric parts of the
unit against ingress of water.
Do not allow children to
operate the unit.
Disconnect the unit from
power mains prior to any
technical maintenance.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END
OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC
WASTE.
www.blaubergventilatoren.de Twin EC Fan Speed Controller & Auto Change Over Panel
4
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS
WITH REDUCED PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR
THOSE WITHOUT THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY
QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT
UNAUTHORISED ACCESS BY UNATTENDED CHILDREN.
PURPOSE
TECHNICAL DATA
The Blauberg Twin EC Fan Speed Controller & Auto Change Over Panel is designed to work with Blauberg TwinBox
Fans with EC Motors of domestic, public, and industrial premises.
The controller is not designed for standalone operation. It is rated for continuous operation.
The controller provides constant faults monitoring with automatic fan change over on fan failure and a number of
other control options described in this manual.
Parameter description Value
Dimensions, (mm) 299.3 x 199.55 x 89.8
Gland holes dimensions 2 x 20mm gland holes, and 2 x 16mm gland holes.
All 4 on bottom edge of case.
Supply / Fan motor nominal Voltage, (V) AC 220-240 V
Supply / Fan motor nominal Frequency, (Hz) 50 Hz
Fan motor nominal Current (each channel), (A) up to 4 A
Fan motor supply out fuse current rate, (A) 4 A
Additional supply out fuse current rate, (A) 1 A
Case protection class, (IP) IP68,
if cable glands with the same or higher level of
protection are used.
Operating Ambient Temperature range [˚C] +1 °C up to +40 °C
Humidity range [%] up to 80 % at 25 °C
NOTE If you need to control fans with 4A or higher nominal currents, then you should use external contactors
controlled by the unit.
www.blaubergventilatoren.de
Twin EC Fan Speed Controller & Auto Change Over Panel
5
INPUT / OUTPUT / OPTIONS / FUNCTION SETTINGS
Mains Supply in
3 way mains terminal block (unit will need a fused supply)
Mains supply out (Auxiliary)
3 way mains supply out terminal block, via a 1 Amp fuse.
Fan 1
3 way mains feed terminal block (L,N & E) (Live supply only switched by relay via 4A Fuse)
Speed control signal output (0 to 100% PWM)
Tacho monitoring input (RPM signal)
Fan 2
3 way mains feed terminal block (L,N & E) (Live supply only switched by relay via 4A Fuse)
Speed control signal output (0 to 100% PWM)
Tacho monitoring input (RPM signal)
PCB control setting potentiometers
Trickle fan speed (0 to 100% PWM)
Medium Boost speed (0 to 100% PWM)
High Boost speed (0 to 100% PWM)
Min RPM fan speed (for monitoring) (50 to 250 RPM)
Fan C/O (changeover) Time (1 to 12 hours)
Run On Time (for both Boost speeds) (0 to 15 mins)
Low Voltage Switch Inputs
VFC for BMS Enable (volt free contacts Closed = Run, Open = Stop)
VFCa Medium Boost Speed (volt free contacts Closed = Med, Open = Trickle)
VFCb High Boost Speed (volt free contact Closed = High speed, Open = Trickle or Medium)
240V AC Medium Boost input
Isolated 240V AC input will select Medium Boost speed (works in parallel with VFCa switch input)
0 > 10V IN
External speed control (0 to 10V DC) will control fan speed scaled from 0V = Trickle Speed to 10V = maximum
fan speed.
Outputs
Fault Output relay (voltage free contacts, Closed = no fault, Open = fault) Fail safe I.E. will go into fault condition
for no power and/or fan fault (rated at 48 V 1A).
10V Out DC supply for external user speed control pot (10k potentiometer).
Nominal 24V DC for powering external sensor unit (maximum 80 mA)
NOTE This is an unregulated supply. Output voltage level depends upon mains supply/loading etc.
www.blaubergventilatoren.de Twin EC Fan Speed Controller & Auto Change Over Panel
6
Power LED 1 [Yellow] PCB mounted
When on indicates power is present
Status LED 2 [Green] PCB mounted
Off = no power
Steady On = all OK
Flashing (Slow) = BMS enable off
Flashing (Fast) = fan fault [Fan 1 or Fan 2]
PCB Mode switches
There is the 4-way DIL PCB mounted slide switch providing the following options:-
Fan 1 Override (On = runs Fan 1 continually and disables Fan 2*).
Fan 2 Override (On = runs Fan 2 continually and disables Fan 1*).
MED/HIGH R-ON (Selects whether Run On time applies to Medium Boost only or to Medium Boost and High
Boost inputs).
Field Test Mode (see Software operation / Field test mode section below)
*If both Fan 1 Override and Fan 2 Override are on at the same time, both fans run continually (duplex mode).
See note at the end of Software operation / Power up section.
www.blaubergventilatoren.de
Twin EC Fan Speed Controller & Auto Change Over Panel
7
PCB terminals and controls location
www.blaubergventilatoren.de Twin EC Fan Speed Controller & Auto Change Over Panel
8
Power up checks
On initial power up the fault output relay will be energized into the normal “No Fault condition.
Fan No 2 will be run for 30 seconds, to allow the controller to monitor the correct running of the fan.
If no fan fault is detected the controller will switch off No 2 fan and bring on fan No 1.
If fan No 2 is found to be faulty the fault relay output will go into fault
condition, and the LED will fast flash and fan No 1 will be turned on.
OR
If fan No 1 is found to be faulty the fault relay output will go into fault condition, and the LED will fast flash and fan
No2 will be turned on.
NOTE If the installation only has one fan, then set “Fan 1 to override” mode and wire into Fan 1 terminals. Fan 2
will be ignored and the Power Up test mode will not occur.
If both fans are to run continually then put Fan 1 & Fan 2 into override mode.
Both fans will now be monitored for correct operation. The Power Up test mode will not occur.
Fan fault monitoring
Any fan that should be running will be monitored, and if its RPM falls below the Minimum RPM speed setting the
Fault Output relay will switch to Fault.
NOTE A fault output will also be generated for lack of mains power.
To ensure that false alarm outputs are not produced the controller will monitor the fan/s for 30 seconds of
continuous fault condition before producing a fault output. This time period is used to ensure that the Fault
Output relay is stable in its operation, and will not be affected by different start up times of fans or windy days
slowing the air flow down etc.
If a fan is found to be faulty the status LED will fast flash and the fault relay remains in the fault condition until such
time as the system is turned off then back on. No automatic fault reset occurs.
Field Test mode
Field Test mode reduces the Changeover Time range to 1 to 12 minutes and the Run On Time range to 0 to 15
seconds, for quicker testing during commissioning.
Fan Speed setting
The Low, Medium & High fan speeds should be set as required for each installation.
The speed setting pots will have a basic scaling of 0, 2.5, 5, 7.5 & 10,
corresponding to 0 to 100% PWM (0 to 10V).
Changeover mode
After the initial power up checks fan No 1 will run for the pre-set time. At the end of the run period Fan No 2 will
be turned on and Fan No 1 will be turned off. If no fan faults are detected this sequence will be repeated.
If a fan fault is detected the Fault Output relay will switch to the fault condition and the status LED will start fast
flashing. The fan being run will be turned off and the other fan will be turned on until the controller is powered
down then back on to reset the unit.
If both fans develop faults then both will be turned off until the controller is powered down, then back on to reset
the unit.
OPERATING PRINCIPLE
www.blaubergventilatoren.de
Twin EC Fan Speed Controller & Auto Change Over Panel
9
0 to 10V external control (User Control)
The unit will normally drive the fans at the Trickle Speed setting (when the VFCa and VFCb inputs are open and
there is no 240V Medium Boost signal). Once the 0 to 10V input goes above circa 0.5V the fan speed/s will be
increased in proportion to the input voltage.
I.E.
A) If the Trickle Speed setting is 10% PWM then the 0-10V input will control
the fan speed/s from 10% to 100% PWM.
B) If the Trickle Speed setting is 20% PWM then the 0-10V input will control
the fan speed/s from 20% to 100% PWM etc.
Boost inputs
If switch inputs VFCa (or the 240V Medium Boost input) or VFCb operate, the fan/s will run at the selected Boost
speed. Whilst any boost signal is present the 0 to 10V input will be ignored, and the fan/s will run at the boost
speed.
The fan/s will always run at the highest boost speed if Medium Boost and High Boost inputs are present at the
same time.
There will be two “Boost modes:
1) MEDIUM BOOST SPEED
Volts free contact input (referenced to units 0V/Neg) When the contacts close the Medium Boost speed will be
selected.
Isolated 240V AC input. When applied the Medium Fan speed will be selected.
NOTE If both Medium Boost inputs are active, then Medium Boost will apply until the last Medium Boost input is
removed.
RUN ON TIME
Whenever the last medium boost signal is removed the Fan/s will continue to run for the period set by the “Run
ON Time control.
NOTE If a boost signal has been removed and the fans are still being driven at the boost speed then during the Run
On Time, “any” new boost signals will be ignored until the Run On Time has expired.
2) HIGH BOOST SPEED
Volts free contact input VFCb (referenced to 0V/Neg). When the contacts close the High Boost speed will be
selected.
NOTE The High Boost can also trigger the Run In Timer if selected by the appropriate mode switch
PRIORITY OF BOOST SIGNALS
Medium Boost will override the Trickle fan speed setting and the 0 to 10V input.
High Boost will override Medium Boost, the Trickle fan speed and the 0 to10V input.
A boost signal will take control of the fan speed whether the boost speed is higher or lower than the fan speed it is
overriding.
BMS Enable input
The VFC BMS Enable input must be connected or linked for the controller to operate. This is for remote control by
a Building Management System or other control system.
If the Enable input is opened whilst running then the fan/s will be turned off and the Fault Output relay will switch
to the fault condition.
www.blaubergventilatoren.de Twin EC Fan Speed Controller & Auto Change Over Panel
10
www.blaubergventilatoren.de
Twin EC Fan Speed Controller & Auto Change Over Panel
11
www.blaubergventilatoren.de
B_UK256-1EN-01
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Blaupunkt B UK256 Twin EC Fan Speed Controller and Auto Change Over Panel User manual

Type
User manual

Blaupunkt B UK256 Twin EC Fan Speed Controller and Auto Change Over Panel is a device that allows for controlling and monitoring two Blauberg TwinBox EC Motor Fans and provides an automatic changeover in case of a fan failure. The controller ensures constant monitoring of any faults with automatic fan changeover on fan failure and a number of other control options. It is rated for continuous operation. The device is equipped with a fault output relay which will be energized into the normal “No Fault” condition on initial power up.