PP2184/2004/Issue 1 PP2184/2004/Issue 1
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
PP2184/2004/Issue 1
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
PP2184/2004/Issue 1
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe (IS) systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
! !
! !
Barrier
Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS confi guration
Barrier
Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS confi guration
Barrier
Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS confi guration
Barrier
Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS confi guration
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fi re.co.uk Website:www.apollo-fi re.co.uk
©Apollo Fire Detectors Ltd 2004
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS confi guration for 29600-239
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
+
+
+
123
456
78 9
1110 12
Galvanic
Barrier
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS confi guration for 29600-240
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS confi guration for 29600-239
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo- re.co.uk Website:www.apollo- re.co.uk
©Apollo Fire Detectors Ltd 2004
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fi re.co.uk Website:www.apollo-fi re.co.uk
©Apollo Fire Detectors Ltd 2004
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
+
+
+
123
456
78 9
1110 12
Galvanic
Barrier
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS confi guration for 29600-240
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo- re.co.uk Website:www.apollo- re.co.uk
©Apollo Fire Detectors Ltd 2004
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS confi guration for 29600-239
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
+
+
+
123
456
78 9
1110 12
Galvanic
Barrier
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS confi guration for 29600-240
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS confi guration for 29600-239
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
+
+
+
123
456
78 9
1110 12
Galvanic
Barrier
+
+
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS confi guration for 29600-240
/