Comelit 41ECN000 Installation guide

Category
Fire protection
Type
Installation guide

Comelit 41ECN000 is a LAN communication module designed to operate via serial communication with the ATENA EASY fire alarm panel. It transmits incoming events to ATENA MANAGER monitoring software through a LAN network. The module's primary function is to send messages for events to a monitoring center or end-user. It can be programmed using ATENA PROG programming software.

The module features six programmable In/Out (I/O) ports, which can be configured as inputs or outputs using ATENA PROG. These I/Os can be used to monitor external devices or control external equipment based on events received from the fire alarm panel.

Comelit 41ECN000 is a LAN communication module designed to operate via serial communication with the ATENA EASY fire alarm panel. It transmits incoming events to ATENA MANAGER monitoring software through a LAN network. The module's primary function is to send messages for events to a monitoring center or end-user. It can be programmed using ATENA PROG programming software.

The module features six programmable In/Out (I/O) ports, which can be configured as inputs or outputs using ATENA PROG. These I/Os can be used to monitor external devices or control external equipment based on events received from the fire alarm panel.

Initial power-up
1. Update the Atena Easy firmware to 3.8.3 or higher;
2. Switch off the power supply of the Atena Easy Panel;
3. Connect the LAN Module to the panel: use the serial flat interface cable to connect to ATENA EASY
Panel;
4. Turn on the power supply;
5. Load the LAN module in the System tree of Atena Prog. Connect to the Module with micro USB
and read the parameters (PC ID “1234” from default);
6. After reading, in General Settings put for Control Panel Type – “Fire Panel” and Enable the Modbus
Server;
7. In Network Settings set Manual settings, then type the desired IP address, NetMask and Gateway;
8. Write the parameters to the panel (PC ID “1234”, User Code “0000”);
9. Connect the Ethernet cable to the LAN module connector;
10. Set manually the IP parameters on Atena Easy panel;
11. Wait until the 41ECN000 module enters into normal operation mode - the Status LED
is blinking green and the Net State LED lights on in green. The time for initial power-up is
up to 90 sec.;
12. After, connecting with Atena Manager, set manually IP parameters and uploading the TDF file
programming of the panel.
41ECN000 - Installation Instruction
General Information
41ECN000 is LAN communication module, designed for operation via serial communication with ATENA EASY fire alarm panel. The module
transmits the incoming events to ATENA MANAGER monitoring software through LAN network. The general application of the module is to send
messages for events to monitoring center or end-user. The module is mounted into the ATENA EASY metal box. The programming of 41ECN000
is via ATENA PROG programming software.
Elements Description
B - Mounting holes.
C - Terminal row:
± V - Power supply 9-30VDC - not used!
Attention: The power supply is from the panel via the serial interface cable!
I/O1-6 - Programmable input/output (via ATENA PROG);
Com - Common Ground;
AC - Not used.
E - Jumper to restore of the factory settings*.
F - LED Indication**:
Status - LED for status of the connection with ATENA EASY panel;
Tx - LED for indication of transmitting events to ATENA MANAGER;
Net State - LED for the state of the connection with ATENA EASY panel.
G - LAN network connector:
Ѓ - LED LAN Action (green);
‚ - LED LAN Link (yellow).
H - Serial interface for connection to ATENA EASY.
1
* Put a jumper to reset the module parameters by default.
** The detailed description of the LED indication is shown on page 2.
18020976, Rev. A, 10/2018
Internal structure of a
programmable output
RL = 120W
10K
1K
I/O 1-6
41ECN000
9 ё 30V
+V
Status
Micro USB
V- V+
I/O1
Jumper
Tx
Net
State
I/O2
I/O3
I/O4
I/O5
I/O6
Com
AC
Comelit Group S.p.A.
Via Don Arrigoni 5 - 24020 Rovetta
S. Lorenzo BG Italy
tel. +39 0346 750 011
fax +39 0346 71436
Technical Specifications
Main power supply: 9-30VDC;
Reversed polarity protection;
Current consumption:
- Normal operation mode (standby): 80mA
- Maximal consumption: 150mA
6 Programmable In/Out: OC type
Micro USB input for programming
Operating temperature: 0°C ÷ +60°C
Restoring of the factory defaults
Dimensions: 50x90mm
• Parameters of the inputs:
- Permissible input voltage: 0 - 20V
- Signal filtering period: 300ms
- Threshold of operation: 1.3V
- Hysteresis: ±0.4V
ATTENTION: Carefully read through this manual prior to installing
the device! This manual is subject to change without notice!
Ajax
LED2LED1
BATT
NET
BATT
(PTC), 7A
Restore Defaults
Jumper
ATENA EASY
41ECN000
LAN
ATENA
MANAGER
ATENA EASY
Control Panel
41ECN000
Serial
interface
Programming
Software
ModBus
protocol
ATENA
PROG
Monitoring
Software
The serial connection between the 41ECN000 module and control panel
ATENA EASY is done with a flexible flat cable included in the spare parts
kit - 300mm long. Connect the cable to the 6-pin interface terminal (Ajax)
on the control panel ATENA EASY. The module is powered on from the
control panel via the serial interface cable.
Ajax
ATENA EASY (main PCB)
41ECN000
Module
Connection diagram
Functinal diagram
LED Indication
Mounting
LED
Status
(green/red)
Indication Description
No connection with ATENA EASY panel.
Successful connection with ATENA EASY panel.
Blinking
Red
Green
Tx
(yellow)
Net State
(green/red)
RJ-45
(LAN
connector
indication)
Transmitting of an event to ATENA MANAGER
monitoring software.
Red
Green
Green
Yellow
Short
blinks
No connection between 41ECN000 and
ATENA MANAGER monitoring software.
Successful connection between 41ECN000 and
ATENA MANAGER monitoring software.
Transmitting of an event to ATENA MANAGER
monitoring software.
(The LED is blinking successively from red to green;
the Tx LED is also blinking).
Lights
ON
Blinking
Red/
Green
LED LAN Action. The LED is blinking when there is
activity on the link; otherwise, the LED is off.
LED LAN Link. The LED is on when there is
a link connection; otherwise, the LED is off.
5
3
Backup side of the interface connector.
4
2
  • Page 1 1
  • Page 2 2

Comelit 41ECN000 Installation guide

Category
Fire protection
Type
Installation guide

Comelit 41ECN000 is a LAN communication module designed to operate via serial communication with the ATENA EASY fire alarm panel. It transmits incoming events to ATENA MANAGER monitoring software through a LAN network. The module's primary function is to send messages for events to a monitoring center or end-user. It can be programmed using ATENA PROG programming software.

The module features six programmable In/Out (I/O) ports, which can be configured as inputs or outputs using ATENA PROG. These I/Os can be used to monitor external devices or control external equipment based on events received from the fire alarm panel.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI