TECHNICAL GUIDE
SINGLE PIECE VARIABLE SPEED
AIR HANDLERS
FOR USE WITH SPLIT-SYSTEM
COOLING & HEAT PUMPS
MODELS: AVY24 THRU 60 AND SVY48 THRU 60
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com
Additional rating information can be found at
www.ahridirectory.org.
ISO 9001
Certified Quality
Management System
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
256819-YTG-J-1208
DESCRIPTION
The Affinity Air Handler line offers the ultimate in comfort, sound
and application flexibility. The Affinity models utilize a whisper
quiet variable speed motor that provides humidity control and
the lowest operating cost in the industry. The AVY air handler is
shipped ready to be installed in all positions, upflow, downflow,
horizontal left or right, with minor adjustments. The SVY 48 &
60 models are upflow only models designed into a shorter cabi-
net, for those special applications where reduced height is
required. No special kits are required to install this deluxe prod-
uct in any position.
All JCI Unitary Products air handlers and coils use a TXV to pro-
vide our customers with the optimum performance and refriger-
ant control required for 13 + Seer systems. Air handlers can be
ordered with either a R-22 or R-410A TXV factory installed. Air
handlers are also available with “Flex-coils” without a factory
installed metering device, where for added flexibility, a R-22 or
R-410A TXV can be field installed to meet your refrigerant
choice.
FEATURE
Thermal Expansion Valve - Provides the ultimate refrigerant
control required for today’s high efficient product. The UPG bolt-
on TXV provides easy installation to convert the air handler to
the required refrigerant, which is a true bolt-on design that does
not require brazing to replace or install.
MicroBlue
TM
Coated Fins - All air handler coils are treated
with the MicroBlue
TM
hydrophilic coating to enhance the
removal of condensate during the refrigeration cycle and
reduce the possibility of water blow-off. The MicroBlue
TM
coat-
ing also reduces the growth of germ causing microbes for a
healthier home environment.
Insulated Cabinet - All air handler cabinets are thermally insu-
lated with 1” foil faced insulation (R-4.2) to prevent sweating.
For applications in extreme humidity conditions an optional,
field installed, external insulating wrap kit is also available.
Factory - Sealed to achieve 2% or less leakage rate with or with-
out field installed filter at 1.0” water gauge external static pres-
sure.
Durable Finish Inside and Out - Air handler casings are made
of pre-painted galvanized steel which provides a better paint to
steel bond that resists corrosion and rust creep. All internal coil
sheet metal parts are made of G90 galvanized.
New 4 HK Heat Kit - Installation friendly, easy service, more
robust, unique to new design.
ECM Variable Speed Motor - Designed for efficient, quiet oper-
ation with added indoor comfort control. With the use of a humi-
distat, the motor will monitor the humidity in the home and
automatically keep the desired humidity level in both winter and
summer seasons. The ECM motor utilizes only 24% of the
energy used by standard blower motors to reduce your overall
heating and cooling costs.
ClimaTrak Comfort Settings - Installers can set an operating
cycle for the ECM motor that works best in a particular climate.
Homeowners benefit from an operating cycle that maximizes
their indoor comfort level regardless of whether they live in a
dry, temperate, or humid climate.
2 Johnson Controls Unitary Products
256819-YTG-J-1208
DIMENSIONS
10-3/8”
F
CIRCUIT
BREAKER
PANEL
BOTTOM INLET
DIMENSIONS
DRAIN PAN CONNECTIONS
FOR HORIZONTAL APPLICATIONS
BLOWER
COMPARTMENT
REFRIGERANT
CONNECTIONS
DRAIN CONNECTIONS
FOR UPFLOW AND
DOWNFLOW APPLICATIONS
7-11/32”
D
B
A
C
1-1/2”
E
TOP OUTLET
DIMENSIONS
FILTER
ACCESS
18-9/32”
J
K
DIMENSIONS
Models
Dimensions (Inches)
Wiring Knockouts
1
Refrigerant
Connections
Line Size
AB C
DEF
JK
Height Width Depth Power Control Liquid Vapor
AVY24B**H21 46 17.5
21.5
(w/o cladding)
22.5
(with cladding)
12-3/8 13-29/32 14-19/32
7/8” (1/2”)
1 3/8” (1”)
1 23/32” (1 1/4”)
7/8” (1/2”) 3/8”
3/4”
AVY36C**H21 52 21 17-1/8 17-13/32 18-3/32 7/8”
AVY48D**H21 57 24.5 22-1/8 20-29/32 21-19/32 7/8”
SVY48D**N21 52 24.5 17-1/8 20-29/32 21-19/32 7/8
AVY60D**H21 57 24.5 22-1/8 20-29/32 21-19/32 7/8’
SVY60D**N21 52 24.5 17-1/8 20-29/32 21-19/32 7/8
1. Actual size (Conduit size).
** Thermal expansion device indicators - “2_” indicates R-22 TXV is factory installed, “3X” indicates unit is a “Flex Coil” models with a field installed
R-22 or R-410A TXV, and “4_” indicates R-410A TXV is factory installed. Letter indicates TXV size as required, see outdoor unit technical infor-
mation for proper matches and requirements.
Johnson Controls Unitary Products 3
256819-YTG-J-1208
COIL TECHNICAL DATA
Models Application
Refrig.
Conn. Types
Face Area
(Sq. Ft.)
Rows
Deep
Fin
Per In.
Coil Size
Tube
Geometry
Tube
Dia.
Fin
Type
TXV
AVY24B3XH21
Cooling /
Heat Pump
Sweat 3.89 2 14 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
None
AVY24B2AH21 2A
AVY24B4EH21 4E
AVY24B4FH21 4F
AVY24B4KH21 4K
AVY36C3XH21
Cooling /
Heat Pump
Sweat 4.86 3 12 (2) 20 x 17.5 1 x 0.866 3/8 Enhanced
None
AVY36C2AH21 2A
AVY36C4EH21 4E
AVY36C4FH21 4F
AVY36C4GH21 4G
AVY36C4HH21 4H
AVY36C4KH21 4K
AVY36C4MH21 4M
AVY48D3XH21
Cooling /
Heat Pump
Sweat 5.83 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
None
AVY48D2CH21
2C
AVY48D4FH21
4F
AVY48D4HH21
4H
AVY48D4JH21
4J
AVY48D4KH21
4K
SVY48D3XN21 None
SVY48D2CN21 2C
AVY60D3XH21
Cooling /
Heat Pump
Sweat 5.83 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
None
AVY60D2CH2
2C
AVY60D4HH21
4H
AVY60D4JH21
4J
AVY60D4KH21
4K
SVY60D3XN21 None
SVY60D2CN21 2C
Note: H models are available with a factory installed horizontal drain pan.
COOLING CAPACITY
Models Rated CFM
Entering Air °F
(Dry / Wet Bulb)
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG
35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0
FULL-CASED “A” TYPE MULTI-POSITION
AVY24B**H21 800
85/72 35.0 31.8 28.4 24.7
80/67 32.2 29.1 25.7 22.3
75/62 26.4 23.4 21.0 17.1
70/57 21.4 18.6 20.2 12.1
AVY36C**H21 1200
85/72 51.3 46.7 41.7 36.8
80/67 41.1 36.3 31.8 27.1
75/62 32.1 27.0 29.4 21.9
70/57 27.6 25.4 23.5 18.3
AVY48D**H21
SVY48D**N21
1600
85/72 100.5 86.4 72.0 56.8
80/67 80.4 67.5 55.0 42.1
75/62 62.7 49.9 40.7 34.0
70/57 53.9 47.2 36.81 28.71
AVY60D**H21
SVY60D**N21
1850
85/72 119.9 101.0 82.0 62.2
80/67 96.0 79.2 62.6 45.8
75/62 74.8 58.6 46.2 37.0
70/57 64.3 55.4 43.2 33.7
4 Johnson Controls Unitary Products
256819-YTG-J-1208
Air Handler Air Flow Data
HIGH / LOW SPEED COOLING AND HEAT PUMP AIRFLOW
CFM
JUMPER SETTINGS
24B 36C
High Low High Low COOL Tap ADJ Tap
1088 707 1387 905 A B
830 542 1151 753 B B
948 617 1201 783 A A
716 465 1009 657 B A
854 556 1086 703 A C
612 462 953 622 C B
637 460 901 588 B C
531 460 754 493 D B
542 462 831 540 C A
462 462 657 460 D A
474 460 751 494 C C
461 464 588 461 D C
48D 60D JUMPER SETTINGS
High Low High Low COOL Tap ADJ Tap
2138 1442 2364 1545 A B
1759 1162 1962 1271 B B
2009 1311 2123 1374 A A
1612 1052 1763 1146 B A
1773 1166 1905 1237 A C
1530 989 1777 1158 C B
1459 947 1580 1021 B C
1359 886 1596 1030 D B
1388 904 1583 1019 C A
1221 806 1413 929 D A
1244 808 1412 926 C C
1118 715 1277 841 D C
HIGH / LOW SPEED ELECTRIC HEAT AIRFLOW
CFM
JUMPER SETTINGS
24B 36C
High Low High Low HEAT Tap ADJ Tap
1088 828 1387 908 A N / A
954 714 1228 804 B N / A
829 614 1151 756 C N / A
678 523 923 609 D N / A
48D 60D JUMPER SETTINGS
High Low High Low HEAT Tap ADJ Tap
2111 1417 2363 1488 A N / A
1858 1252 2174 1252 B N / A
1480 985 1868 1061 C N / A
1250 840 1387 823 D N / A
1. Airflow at nominal voltage, bottom return at 0.5 external static pressure, tested without filter installed, dry coil conditions.
2. These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure.
3. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static.
4. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
5. Both the COOL and the ADJUST tap must be set to obtain the cooling airflow desired (CFM).
6. The ADJ tap does not affect the HEAT tap setting.
7. Fan only airflow (CFM) = 63% of jumper selected COOL tap and ADJUST tap.
8. Low speed cooling used only with two stage outdoor units. (Speed is preset to 65% of high speed).
9. Dehumidification speed is 85% of jumper selected COOL tap and ADJUST tap.
10. When operating in both heat pump and electric heat modes, the airflow (CFM) will be per HEAT Tap CFM values only.
11. At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain
models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.
12. Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (i.e.: 12 Flashes is 1200 CFM) – blinks are approximate +/- 10%.
Johnson Controls Unitary Products 5
256819-YTG-J-1208
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow
80% 90% Rated CFM 110% 120%
Capacity Factor
0.96 0.98 1.00 1.02 1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
AVY24B**H21 AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Blower - Diameter x Width 10 x 7 10 x 7 10 x 10 10 x 10
Motor
HP 1/3 1/2 3/4 1
Nominal RPM 1200 1200 1200 1200
Voltage 230
Amps Full Load (230) 2.8 4.3 5.5 7.0
Filter
1
Type DISPOSABLE OR PERMANENT
Size 16 x 20 x1 20 x 20 x1 22 x 20 x1 22 x 20 x1
Permanent Type Kit 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK
Shipping / Operating Weight (lbs.) 140/134 170/164
AV - 196/185
SV - 194/181
AV - 199/188
SV - 195/184
1.Field supplied.
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
Total Motor Amps Minimum Circuit Ampacity
Max. O.C.P.
Amps/Type
1
Minimum Wire
Size A.W.G.
60 Hertz 60 Hertz
208V 230V 208V 230V
AVY24B**H21 3.2 2.8 4.0 3.5 15 14
AVY36C**H21 4.7 4.3 5.9 5.4 15 14
AVY48D**H21 6.1 5.0 7.6 6.9 15 14
SVY48D**N21 6.1 5.0 7.6 6.9 15 14
AVY60D**H21 7.8 7.0 9.7 8.8 15 14
SVY60D**N21 7.8 7.0 9.7 8.8 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
6 Johnson Controls Unitary Products
256819-YTG-J-1208
* May be 0 (no breaker) or 1 (with breaker).
ELECTRICAL DATA - 208/230-1-60
Models Heat Kits*
Max.
Static
Min.
Speed Tap
Total Heat
1
kW Staging
KW MBH W1 Only W2 Only W1 & W2
208v 230v 208v 230v 208v 230v 208v 230v 208v 230v
AVY24B**H21
4HK*6500206 0.5 Heat-D 1.9 2.5 6.4 8.5 1.9 2.5 1.9 2.5 1.9 2.5
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-B 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
4HK165N1506 0.5 Heat-A 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4
AVY36C**H21
4HK*6500506 0.5 Heat-C 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4
4HK16501806 0.5 Heat-A 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6
AVY48D**H21
SVY48D**N21
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4
4HK16501806 0.5 Heat-B 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6
4HK16502006 0.5 Heat-B 14.4 19.2 49.2 65.5 3.6 4.8 7.2 9.6 14.4 19.2
4HK16502506 0.5 Heat-B 18.0 24.0 61.5 81.9 3.6 4.8 10.8 14.4 18.0 24
AVY60D**H21
SVY60D**N21
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
4HK*6500806 0.5 Heat-D 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4
4HK16501806 0.5 Heat-C 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6
4HK16502006 0.5 Heat-C 14.4 19.2 49.2 65.5 3.6 4.8 7.2 9.6 14.4 19.2
4HK16502506 0.5 Heat-C 18.0 24.0 61.5 81.9 3.6 4.8 10.8 14.4 18.0 24
1. See conversion Table 10.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V 240V .918
220V 240V .840
COMFORT SETTINGS SELECTION
Delay Tap Comfort Setting
ANormal
BHumid
CDry
D Temperate
Johnson Controls Unitary Products 7
256819-YTG-J-1208
* May be 0 (no breaker) or 1 (with breaker).
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60
Models
Heat Kit -
Single Phase*
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
Amps/Type
1
75°C Wire Size - AWG
208V 230V 208V 230V 208V 230V
AVY24B**H21
4HK*6500206 10.4 15.28 16.53 20 20 12 12
4HK*6500506 20.0 25.67 28.50 30 30 10 10
4HK*6500806 31.3 37.85 42.63 45 45 8 8
4HK*6501006 40.0 47.33 53.50 50 60 8 6
4HK165N1506 60.0 69.00 78.50 70 90 4 3
AVY36C**H21
4HK*6500506 20.0 27.54 30.38 30 35 10 10
4HK*6500806 31.3 39.73 44.50 45 45 8 8
4HK*6501006 40.0 49.21 55.38 50 60 8 6
4HK16501506 60.0 70.88 80.38 70 90 4 3
4HK16501806 73.3 85.32 97.00 90 100 4 3
AVY48D**H21
SVY48D**N21
4HK*6500506 20.0 29.29 31.88 35 35 8 8
4HK*6500806 31.3 41.48 46.00 45 50 8 8
4HK*6501006 40.0 50.96 56.88 60 60 6 6
4HK16501506 60.0 72.63 81.88 90 90 3 3
4HK16501806 73.3 87.07 98.50 90 100 3 2
4HK16502006 80.0 94.29 106.88 100 125 3 1
4HK16502506 100.0 115.96 131.88 125 150 1 1/0
AVY60D**H21
SVY60D**N21
4HK*6500506 20.0 31.42 33.75 35 35 8 8
4HK*6500806 31.3 43.60 47.88 45 50 8 8
4HK*6501006 40.0 53.08 58.75 60 60 6 6
4HK16501506 60.0 74.75 83.75 90 90 3 3
4HK16501806 73.3 89.19 100.38 90 110 3 2
4HK16502006 80.0 96.42 108.75 100 125 3 1
4HK16502506 100.0 118.08 133.75 125 150 1 1/0
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60
Models
Heater
Model
Min. Circuit Ampacity
Max. O.C.P.
Amps/Type
1
75°C Wire Size - AWG
Circuit Circuit Circuit
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
AVY24B**H21 4HK165N1506 47.5 / 53.5 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10
AVY36C**H21
4HK16501506 48.5 / 55.4 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10
4HK16501806 44.9 / 51.2 39.8 / 45.8 45 / 60 40 / 50 8 / 8 8 / 8
AVY48D**H21
SVY48D**N21
4HK16501506 51.0 / 56.9 21.7 / 25.0 60 / 60 25 / 25 6 / 6 10 / 10
4HK16501806 47.4 / 52.7 39.8 / 45.8 50 / 60 40 / 60 6 / 6 8 / 6
4HK16502006 51.0 / 56.9 43.4 / 50.0 60 / 60 45 / 50 6 / 6 8 / 8
4HK16502506 51.0 / 56.9 43.4 / 50.0 21.7 / 25.0 60 / 60 45 / 50 25 / 25 6 / 6 8 / 8 10 / 10
AVY60D**H21
SVY60D**N21
4HK16501506 53.1 / 58.8 21.7 / 25.0 60 / 60 25 / 25 6 / 6 10 / 10
4HK16501806 49.5 / 54.6 39.8 / 45.8 50 / 60 40 / 60 6 / 6 8 / 6
4HK16502006 53.1 / 58.8 43.4 / 50.0 60 / 60 45 / 50 6 / 6 8 / 8
4HK16502506 53.1 / 58.8 43.4 / 50.0 21.7 / 25.0 60 / 60 45 / 50 25 / 25 6 / 6 8 / 8 10 / 10
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
8 Johnson Controls Unitary Products
256819-YTG-J-1208
ELECTRICAL DATA - 208/230-3-60
Models
Heat Kit -
Three Phase
Max.
Static
Min.
Speed
Tap
Total Heat
1
KW Staging
KW MBH W1 Only W2 Only W1 + W2
208V 230V 208V 230V 208V 230V 208V 230V 208V 230V
AVY24B**H21 4HK06501025 0.5 Heat-B 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6
AVY36C**H21
4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6
4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4
AVY48D**H21
SVY48D**N21
4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6
4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4
4HK06501825 0.5 Heat-B 12.9 17.2 44.7 58.7 12.9 17.2 12.9 17.2 12.9 17.2
AVY60D**H21
SVY60D**N21
4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6
4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4
4HK16502525 0.5 Heat-C 18.0 24.0 61.4 81.4 9.0 12.0 18.0 24.0 18.0 24.0
1. See conversion table on Page 5.
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
Heat Kit -
Three Phase
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
208V 230V 208V 230V 208V 230V
AVY24B**H21 4HK06501025 23.1 28.5 32.4 30 35 10 8
AVY36C**H21
4HK06501025 23.1 30.4 34.3 30 35 10 8
4HK06501525 34.7 42.9 48.8 45 50 8 8
AVY48D**H21
SVY48D**N21
4HK06501025 23.1 31.3 35.1 35 35 8 8
4HK06501525 34.7 43.8 49.6 45 50 8 8
4HK06501825 41.4 51.0 58.0 60 60 6 6
AVY60D**H21
SVY60D**N21
4HK06501025 23.1 33.8 37.6 35 40 8 8
4HK06501525 34.7 46.3 52.1 50 60 8 6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
Heater
Model
Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
Circuit
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
AVY60D**H21
SVY60D**N21
4HK16502525 41.0 / 44.9 31.3 / 36.1 - / - 45 / 45 35 / 40 - / - 8 / 8 8 / 8 - / -
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Johnson Controls Unitary Products 9
256819-YTG-J-1208
ACCESSORIES
Refer to Price Manual for specific model numbers where not
shown.
TXV Kits - TXV kits are available for “Flex-coil” applications and
converting R-22 to R-410A or as a service replacement. All kits
are bolt-on and require no brazing to install.
Electric Heaters - 4HK models shown under electrical data
include sequential operation and temperature dual limit
switches for safe, efficient operation. Circuit breakers are pro-
vided where shown.
External Insulating Wrap Kit - Provides a vinyl covered ther-
mal insulation wrap, providing additional thermal insulation pro-
tection to prevent sweating in applications where extreme high
humidity is present. Air Handler cover (or wrap) has Velcro
edges for easy installation and access.
S1-1JV0117
S1-1JV0121
S1-1JV0124
S1-1JV0224 (SV* models only)
Humidstat - S1-2HU16700124
Control when used with ECM variable speed models will moni-
tor humidity level in both winter and summer seasons. Adjusts
blower speed and airflow provided to maintain desired humidity
levels.
LIMITATIONS
These units must be wired and installed in accordance with all
national and local safety codes.
Voltage limits are as follows:
Airflow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units.
COOLING MODELS WITH ELECTRIC HEAT WIRING
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for
SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
Air Handler Voltage Voltage code
1
Normal Operating
Voltage Range
1.Rated in accordance with ARI Standard 110, utilization range
“A”.
208/230-1-60 06 187-253
Entering Air Temperature Limits
Wet Bulb Temp.°F Dry Bulb Temp. °F
Min. Max. Min. Max.
57 72 65 95
Air Handler Control Wiring
Typical A/C - Cooling only Applications
THERMOSTAT
AIR HANDLER
BOARD
1-STAGE
AIR CONDITIONING
RR
G
Y
W1
W2
C
G
W1
W2
Y
C
Y/Y2
Y1
O
HUM
X/L
COM
HUMIDISTAT
*
THERMOSTAT
AIR HANDLER
BOARD
1-STAGE
AIR CONDITIONING
RR
G
Y
W1
W2
C
G
W1
W2
Y
C
Y/Y2
Y1
O
HUM
X/L
COM
HUMIDISTAT
*
Air Handler Control Wiring
Typical A/C with Electric Heat Applications
Subject to change without notice. Printed in U.S.A. 256819-YTG-J-1208
Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 256819-YTG-I-0808
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
TWO-STAGE COOLING WIRING
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER
enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
TYPICAL APPLICATIONS
CONTROL WIRING - Air Handler & New UPG HP Systems
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”
Conventional Application - Not Hot Heat Pump
THERMOSTAT
AIR HANDLER
BOARD
2 - STAGE SCROLL
HEAT PUMP
RR R
GG
Y2
E
W
W
O O
O
X/L X/L X/L
C
C
Y/Y2
Y1
Y1
Y2 OUT
Y2
W2 OUT
W1 OUT
BS
W2
W1
HUM
COM
HUMIDISTAT
*
Y1
UPFLOW DOWNFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

York AVY24 THRU 60 User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI