17
Table 3 – Electrical Data -- Units With Optional Powered Convenience Outlet
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts-Ph-Hz
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
IFM
FLA
ELECTRIC HEAT POWER SUPPLY
DISCONNECT
SIZE
Min Max RLA LRA FLA
Nominal
kW*
MCA MOCP† FLA LRA
03
208/230-1-60 187 253 12.8 60 1.0
—
Low
4.9
— — 26.7/26.7 30/30 27/27 79/79
10.8/12.5 2.3/ 3.0 26.7/27.8 30/30 27/27 79/79
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 79/79
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 79/79
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 79/79
High
— — 26.7/26.7 30/30 27/27 79/79
10.8/12.5 2.3/ 3.0 26.7/27.8 30/30 27/27 79/79
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 79/79
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 79/79
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 79/79
1.4
Low
— — 28.1/28.1 30/30 29/29 81/81
10.8/12.5 2.3/ 3.0 28.1/29.5 30/30 29/29 81/81
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 81/81
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 81/81
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 81/81
High
— — 28.1/28.1 30/30 29/29 81/81
10.8/12.5 2.3/ 3.0 28.1/29.5 30/30 29/29 81/81
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 81/81
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 81/81
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 81/81
04
208/230-1-60 187 253 15.4 83 1.0
—
Low
4.9
— — 30.0/30.0 30/30 30/30 102/102
10.8/12.5 2.3/ 3.0 30.0/30.0 30/30 30/30 102/102
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 102/102
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 102/102
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 102/102
52.0/60.0 11.3/15.0 77.1/87.1 80/90 71/80 102/102
High
— — 30.0/30.0 30/30 30/30 102/102
10.8/12.5 2.3/ 3.0 30.0/30.0 30/30 30/30 102/102
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 102/102
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 102/102
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 102/102
52.0/60.0 11.3/15.0 77.1/87.1 80/90 71/80 102/102
1.4
Low
— — 31.4/31.4 35/35 32/32 104/104
10.8/12.5 2.3/ 3.0 31.4/31.4 35/35 32/32 104/104
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 104/104
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 104/104
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 104/104
52.0/60.0 11.3/15.0 78.9/88.9 80/90 73/82 104/104
High
— — 31.4/31.4 35/35 32/32 104/104
10.8/12.5 2.3/ 3.0 31.4/31.4 35/35 32/32 104/104
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 104/104
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 104/104
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 104/104
52.0/60.0 11.3/15.0 78.9/88.9 80/90 73/82 104/104
208/230-3-60 187 253 11.5 77 1.0 —
Low
4.9
— — 25.1/25.1 30/30 26/26 96/96
6.3/ 7.2 2.3/ 3.0 25.1/25.1 30/30 26/26 96/96
10.0/11.5 3.8/ 5.0 25.1/26.5 30/30 26/26 96/96
15.0/17.3 5.6/ 7.5 30.9/33.8 35/35 28/31 96/96
20.0/23.1 7.5/10.0 37.1/41.0 40/45 34/38 96/96
30.0/34.6 11.3/15.0 49.6/55.4 50/60 46/51 96/96
High
— — 25.1/25.1 30/30 26/26 96/96
6.3/ 7.2 2.3/ 3.0 25.1/25.1 30/30 26/26 96/96
10.0/11.5 3.8/ 5.0 25.1/26.5 30/30 26/26 96/96
15.0/17.3 5.6/ 7.5 30.9/33.8 35/35 28/31 96/96
20.0/23.1 7.5/10.0 37.1/41.0 40/45 34/38 96/96
30.0/34.6 11.3/15.0 49.6/55.4 50/60 46/51 96/96
LEGEND
FLA --- F u l l L o a d A m p s
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- RatedLoadAmps
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{ Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.Use
the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
E x a m p l e : S up p l y vo l t a g e i s 2 3 0 --- 3 --- 6 0
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
50PG03--07