Contec DIO-0404LY-WQ-US Owner's manual

Type
Owner's manual
Setu
p
Guid
e
Isolated Digital I/O
Terminal for Sub-GHz Wireless US
DIO-0404LY-WQ-US
Thank you for purchasing this product. The product you have purchased consists of the
following items.
Check, with the following list, that your package is complete.
If you find any item either missing or damaged, please contact the sales representative you
purchased the product from.
Before actual use, read the Reference Manual which can be viewed on the Contec website
to use this product correctly.
The following manuals and driver software come with this product. The following manuals
and driver software come with this product. Visit the Contec website and download them
before using the product.
The name of the documents Contents How to
g
et
Setup Guide (This document) The outline of the product. Included in the
package (Printed
matter)
Manual Product settings and operation checking
are described.
Download(PDF)
The name of the documents Contents How to
g
et
Highly functional driver
API-DIO(WDM)
Driver software of digital input and out-
put
Download
(Sel
f
-extraction)
Download
https://www.contec.com/
1. About the Product
This product is a digital I/O terminal that sends I/O digital signals wirelessly in the Sub-GHz
band. Data is sent to Ethernet gateway (Master) of the Wireless I/O series.
With strength against obstacles, capability of long-distance communications, and mesh
support, it is suitable to control or monitor devices that are spread in the wide area.
The product supports I/O of 12-24VDC digital signals, contains opto-coupler isolated input
(current sink output support) 4-channel and opto-coupler isolated open-collector output
(current sink type) 4-channel.
* This product should always be used along with the Wireless I/O series gateway (Master).
2. Product Configuration
This product consists of the items listed below.
Check, with the following list, that your package is complete. If you discover damaged or
missing items, contact your retailer.
Product...1 Setup Guide...1 Warrant
y
Certificate...1 Serial Number Label...1
3-pin Connecto
r
..1 14-pin Connecto
r
...1 Antenna...1
3. Safety Precautions
Understand the following definitions and precautions to use the product safely.
Safety Information
This document provides safety information using the following symbols to prevent acci-
dents resulting in injury or death and the destruction of equipment and resources. Under-
stand the meanings of these labels to operate the equipment safely.
DANGER
DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious in-
jury.
CAUTION
CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate in-
jury or in property damage.
Handling Precautions
DANGER
Do not use the product in locations exposed to a flammable or corrosive gas. It may
cause explosion, fire, electrical shock, or malfunction.
CAUTION
This product contains precision electronic elements and must not be used in locations
subject to physical shock or strong vibration. Otherwise, the product may malfunction,
overheat, or cause a failure.
Do not use or store this product in high temperature or low temperature surroundings,
or do not expose it to extreme temperature changes. Otherwise, the product may mal-
function, overheat, or cause a failure.
Do not use or store this device where it is exposed to direct sunlight or near stoves or
other sources of heat. Otherwise, the product may malfunction, overheat, or cause a fail-
ure.
Do not use the product in the vicinity of devices that generate strong magnetic force or
noise. Otherwise, the product may malfunction, overheat, or cause a failure.
Do not turn on the power without first connecting the antenna. Otherwise, the product
may malfunction, overheat, or cause a failure. Before turning the power on, be sure to
check whether the antenna is securely connected.
The specifications of the product are subject to change without notice for enhancement
and quality improvement. Even when using the product continuously, be sure to read the
manual in the CONTEC's website and understand the contents. Do not modify the prod-
uct. CONTEC will bear no responsibility for any problems, etc., resulting from modifying
the product.
Do not modify the product. CONTEC will bear no responsibility for any problems, etc.,
resulting from modifying the product.
The product must always be associated with the instruction manual.
When the product is used in a place that is affected by overcurrent or overvoltage (light-
ning surge), select appropriate surge protection device for all of the route (Power line,
earth, etc.). Consult with the specialist regarding selecting, purchasing, and setting the
surge protection device.
Bringing this product too close to a metal/concrete wall (including steel frames) may
cause the communication quality to deteriorate.
If a wireless device that uses the same channel (wireless frequency) as this product exists
in the area where communication is possible, a drop in the transmission speed or com-
munication quality may occur in certain situations, which may make it impossible to per-
form normal communication.
Modifications to the built-in wireless equipment are prohibited by law.
In some medical institutions and laboratories, radio-sensitive precision instruments are
used and it may be prohibited to use radio equipment.
The use of antennas other than that included with the product is prohibited by law.
The radio waves used by this product pass through obstacles (such as walls) and reach
all locations within a given area. If the security settings are not configured, communica-
tion may be intercepted by a third party.
This product is equipped with a security function, so be sure to configure the security
settings prior to use in order to reduce security problems.
This product may not perform normal wireless communication due to factors such as the
installation environment, the setup, and the communication load of the network.
Perform a verification in advance in an environment that matches your usage application
to check that there are no problems.
For the introduction and installation of this product, hire a system integrator or other
specialist who is well-versed in the construction of network systems.
When you are switching to this product from another model, it may be necessary to
reconstruct the network system due to differences in areas such as the product specifi-
cations and functions.
When disposing of the product, follow the disposal procedures stipulated under the rel-
evant laws and municipal ordinances.
Regardless of the foregoing statements, CONTEC is not liable for any damages whatso-
ever (Including damages for loss of business profits) arising out of the use or inability to
use this CONTEC product or the information contained herein.
About listed transfer rate
Data transfer speed listed in this guide or Utility is a theoretical maximum value and does
not indicate the actual data speed.
Usage limitation
This product has not been developed or manufactured to be used in systems including the
equipment which is directly related to human lives *1 or the equipment which involves hu-
man safety and may significantly affect the maintenance of public functions *2. Therefore,
do not use the product for such purposes. Use outside The U.S. may conflict with radio laws
and regulations of the country concerned. Please do not use outside The U.S.
*1 Medical devices such as life-support equipment and devices used in an operating the-
ater.
*2 Main control systems at nuclear power stations, safety maintenance systems at nuclear
facilities, other important safety-related systems, operation control systems within
group transport systems, air-traffic control systems, etc.
4. Option
AC-DC Power Adaptor (12VDC, 1A) : POA201-10-2 *1
Bracket for Wireless I/O Products : BRK-WQ-Y
14 pin Terminal connector(screw type) 6/set : CN6-Y14
*1 The ambient temperature is 0 - 40°C. The support voltage of AC cable is 125 VAC 7 A.
*Visit the CONTEC website to check the details.
5. Product Nomenclature and
Function
Nomenclature of Product Components
Number Description
1 Power connecto
r
2 mini-B USB connecto
r
3 INIT button
4 Antenna connecto
5 WLINK LED
6 Interface connecto
r
7 DIP switch (for maintenance) *1
8 Rotar
y
switch
*1 Do not touch DIP switch since this is not used for usual operations.
*There is a cover for the switch on the back side of the product.
Power connector
Use the power connector, included in the package, to supply power (use the power cable
described below or equivalent one).
Attached connector: European type terminal 3.5 pitch 3-pin jack connector
Supplied connector: European type terminal 3.5 pitch 3-pin plug connector
Compatible cable: AWG28-16(Cable length should satisfy the power specification including
the cable volta
g
e drop)
Signal Name Description
V+ Power supply (12 - 24VDC±5%)
V- Power supply (GND)
FG Frame ground
When making the power cable, be sure to make the wiring correctly.
Especially, if the wrong housing pin number is used, it may cause malfunction or acci-
dents.
Input voltage range: 12 - 24VDC±5%
Use the power supply that rises within the input voltage range of 11.4 VDC or higher
and within 10 ms. Otherwise, the product may be damaged or cause a failure.
INIT button
Name Operation / function
INIT
This is used to initialize (restore the factory settings) the product. If this but-
ton is pressed for three seconds or longer, LED of WLINK starts flashing in
orange. If the button is released before the flashing stops, all the settings of
the product are restored to the factor
y
settin
g
s after rebootin
g
the product.
*When initializing the product with INIT button, flashing continues for a while. This indi-
cates that files in the built-in memory are being removed. If you turn off the power be-
fore flashing stops, the files in the built-in memory are damaged and this might prevent
the product from booting properly. Always reboot the product after flashing stops.
WLINK LED
LED name LED color Status Description
WLINK
Green ON It indicates that the device is operatin
g
.
Green Flashing It indicates that the device is being
started (from power-on up to operation)
--- OFF It indicates that the device is power off.
Orange ON It indicates that the device is operating.
(wireless connection)
Oran
g
e Flashin
g
Write file
Red Flashin
g
S
y
stem erro
r
Interface connector
Attached connector: European type terminal 3.5 pitch 14-pin jack connector
Supplied connector: European type terminal 3.5 pitch 14-pin plug connector
Compatible cable: AWG28-16(Cable length should satisfy the power specification including
the cable volta
g
e drop)
Pin number Si
g
nal name Description
14
O-PC
(Plus common for output)
This connects to the plus side of external
power, and shares with 4 channels of out-
put si
g
nal.
13 O-03
These are four channels of output signals.
Each connects to the input signal of exter-
nal device.
12 O-02
11 O-01
10 O-00
9
O-NC
(Minus common for output)
This connects to the minus side of external
power and shares with 4 channels of out-
put si
g
nal.
8 N.C. This is left unconnected.
7 N.C. This is left unconnected.
6
I-PC
(Plus common for input)
This connects to the plus side of external
power and shares with 4 channels of input
si
g
nal.
5 I-03
These are four channels of input signals.
Each connects to the output signal of ex-
ternal device.
4 I-02
3 I-01
2 I-00
1 N.C. This is left unconnected.
DIP switch
This is a DIP switch for maintenance. Do not use this.
Pin No. Description
1 Alwa
y
s OFF
2 Alwa
y
s OFF
Rotary switch
Set device ID with Rotary switch. Open the switch cover on the back of the product and the
rotary switch can be seen.
The rotary switch is used to identify devices and IDs can be set with 0 to E.
If you intend to set the device ID with F or more, connect the PC to this product via USB
cable, then set ID.
See the table below for device IDs.
Device ID Description
0 - E
Values of the rotary switch are used as device IDs.
0: Factory default setting
F Values set in Contec device utilit
y
are used as device IDs. (0 -7F)
Front Back
Bottom
①②
Top
Isolated Digital I/O
Vi+ Vi- FG
12-24VD
C
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1O
N
2
CONTEC CO.
,
LTD.
3-9-31
,
Himesato
,
Nishi
y
odo
g
awa-ku
,
Osaka 555-0025
,
Ja
p
an
https://www.contec.com
/
No part o
f
this document may be copied or reproduced in any form by any means
without prior written consent of CONTEC CO., LTD.
NA06218 (LYWA792) 07272018_rev2 [07062018] July 2018 Edition
Installing and Connecting
Read and understood the cautions below to install the product.
- If there is metal around antenna, it affects antenna characteristics.
Do not place metal near the antenna if possible.
- This product can be mounted on DIN rail with a DIN rail installing bracket of the
optional. Refer to the bundled manual of DIN rail installing bracket for details.
Connecting an antenna
The steps below describe how to connect the supplied antenna to the product.
(1) With the antenna in straight condition, set it to the connector.
(2) Decide the bending direction and turn the product to fasten. Hold the root of the
antenna to prevent it from turning around.
(3) Be certain that the antenna is not loosely set, bend it in the desired direction.
Input circuit
*Input terminal is I-xx.
Input circuit of interface is listed above.
Signal input is opto-coupler isolated input (current sink output support), therefore, external
power supply is required to drive input in this board. The power requirement is about
5.1mA per input channel at 24VDC. (about 2.6mA at 12VDC)
Output circuit
*Output terminal is O-xx.
Output circuit of interface is listed above. Signal output is opto-coupler isolated open-col-
lector output (current sink type), therefore, external power supply is required to drive output.
The rated output current per channel is 100mA at maximum.
As low saturated transistor is used for output, connecting to TTL level input is possible.
When the output is ON, the residual voltage (LOW level voltage) between the collector and
emitter is 0.5 V or less at an output current within 50 mA, and 1.0 V or less at an output
current of 100 mA.
To protect against surge voltage, a Zener diode is connected to the output transistor.
Also, an overcurrent protection circuit is attached to four output transistor channels.
6. Setup
Have the followings ready for setting up the product.
- Host computer
- USB cable (mini USB Type-B) [a commercially available USB cable is required]
- AC Power Adaptor [commercially available adapter is required]
- Highly functional driver API-DIO(WDM)
*Host computer and USB are not provided.
*API-DIO(WDM) can be downloaded from the CONTEC website.(https://www.contec.com/)
Search by the model of this product or API-DIO(WDM) and download it.
Follow the steps below to set up.
1. Software installation
2. Hardware setup (setting is required for this product and the master respectively)
3. Hardware installation
4. Operation check
1. Software installation
STEP1: Extract the downloaded file. (self-extraction)
STEP2: After the extraction, execute Setup.exe in the INF folder to install.
2. Hardware setup
STEP1: Connect AC adapter to the product and turn the power on.
STEP2: Connect the product and the host computer with a USB cable.
STEP3: Boot the Contec Device Utility.
STEP4: In Settingmode of Contec Device Utility, this product is displayed.
(if not, check USB cable or power cable)
STEP5: Select this product to set the network and digital functions.
Set the network in accordance with the users environment.
STEP6: Shut down the Contec Device Utility, then remove this product from the host
computer.
3. Hardware installation
STEP1: Boot the Device manager.
STEP2: Select the "Action "-"Add Legacy hardware".
STEP3: Select the "Install the hardware that manually select from a list (advanced)".
STEP4: Add "NET DIO-NET-TYPE1" in "CONTEC Devices".
4. Operation check
STEP1: Power on Master and connect the host computer with a LAN cable.
STEP2: Power on this product.
STEP3: Check the change of WLINK between the master and this product.
STEP4: Boot the Contec Device Utility. The master and this product are displayed on
NET tree.
(if not, check LAN cable, power cable, or settings of this product and the master)
STEP5: Select this product and confirm Device Name, then execute Save.
SETP6: Check the operation with Diagnostic Program.
(If the product does not operate, check the settings of computer network and
the master)
Above completes the settings.
Refer to Help regarding API function or sample programs.
((Download file API-DIO(WDM)) \Help\DIOWDM\ENG\APITOOL.chm)
7. Specifications
Item Specifications
Wireless
Modulation system
GFSK
Speed *1
10kbps (Low data rate) / 110kbps (Middle data rate) /
250kbps (Hi
g
h data rate)
Output 13dBm
Used frequency
902 - 928MHz
Digital input
Input type
Opto-coupler isolated input
(current sink output support) (ne
g
ative lo
g
ic)
Input resistance
4.7k
Input ON current
2.0mA or more
Input OFF current
0.16mA or less
Response time
Within 200µsec *2
Number of input
si
g
nal channels
4
Digital output
Output type
Opto-coupler isolated open-collector output (current sink
t
y
pe) (ne
g
ative lo
g
ic)
Rated output volt-
a
g
e
35VDC
Rated output cur-
rent
Up to100mA
Response time
Within 200µsec *2
Residual Voltage
with Output ON
0.5V or less(Output current 50mA),
1.0V or less(Output current 100mA)
Number of output
si
g
nal channels
4
Protection circuit 42.3V(Min.) Zener diode protection (each channel)
1 time fuse
Digital input
Digital output
common
Interface con-
nector
14-pin terminal connector(screw type)
External power
volta
g
e
12 - 24VDC (±10%)
Voltage resistance 1000Vrms
Applicable wire AWG28 - 16
USB Bus specification USB Specification 2.0/1.1-compliant
Data transmission
speed
12Mbps (Full speed), 480Mbps (High speed)
Function USB device
Connecto
r
mini-B USB connecto
r
Antenna
Non-directional dipole antenna (2.0±0.7dBi)
Power
supply
Input voltage
ran
g
e
12 - 24VDC±5%
Current
consumption
80mA (at 12VDC input) (Max.),
40mA (at 24VDC input) (Max.)
Power connector
*3
Eu
r
opean type terminal 3.5 pitch 3-pin jack connecto
r
Physical dimensions (mm) 62.0(W) x 64.0(D) x 24.0(H) (No projection included)
Weight 100g (Body),
150g (With bundled antenna, power connector, interface
connector)
*1 It is a theoretical maximum value on wireless communication and does not indicate the
actual data speed.
*2 Response time is given when input resistance 4.7k and 12 - 24VDC (±10%)
*3 This product cannot be used with USB bus power. Make sure to use the external power
that supplies 12VDC or 24VDC voltage.
Item Specifications
Operating ambient temperature -20 - +60°C *4
Operating ambient humidity 10 - 90%RH (No condensation)
Floating dust particles Not to be excessive
Corrosive gases None
Line-noise
resistance *5
Line noise AC Line/±2k
V
, Signal Line /±1kV
(IEC61000-4-4 Level 3, EN61000-4-4 Level 3)
Static electricity
resistance
Touch /±4kV(IEC61000-4-2 Level 2, EN61000-4-2 Level 2)
Air /±8kV(IEC61000-4-2 Level 3, EN61000-4-2 Level 3)
Vibration
resistance
Sweep resistance 10 - 57Hz /semi-amplitude vibration 0.15mm,
57 - 150Hz/2.0G
40minutes each in X, Y, and Z directions
(JIS C60068-2-6-compliant, IEC60068-2-6-compliant)
Shock resistance 147m/s
2
(15G)/11ms/half-sine shock
(JIS C 60068-2-27 -compliant, IEC 60068-2-27 -compliant)
Standard FCC Class A, RoHS Directive
*4 The ambient temperature is 0 - 40°C. The support voltage of AC cable is 125 VAC 7 A.
*5 When using an optional AC adapter POA201-10-2
8. Physical Dimensions
9. Antenna Directivity
H-Plane (925MHz)
E-Plane (925MHz)
Vcc
Vcc
Product
Optocoupler
Switch
Switch
Optocoupler
Input pin
Input pin
Plus
common
External device
External
power supply
12 - 24VDC
Vcc
Overcurrent protection
Optocoupler
Optocoupler
Load
Product
Minus
common
External device
Plus
common
External
power supply
12 - 24VDC
Output pin
Output pin
Load
Zener
diode
Zener
diode
(62)
(24)
(64) (9)
(24)
[mm]
(176)
(48)
(8.9)
[mm]
φ3.8
φ9.0
φ10
  • Page 1 1
  • Page 2 2

Contec DIO-0404LY-WQ-US Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI