Tripp Lite SNMPWEBCARD User manual

Category
Remote power controllers
Type
User manual

This manual is also suitable for

Tripp Lite SNMPWEBCARD is a versatile network card that can be installed in compatible Tripp Lite UPS systems or PDUs to enable remote monitoring, control, and reporting. With this device, you can manage your UPS system or PDU from a web browser, telnet, or SNMP Network Management Station. The SNMPWEBCARD allows you to reboot the device, control outlets, shed nonessential loads, monitor load levels, and receive SNMP traps or email alerts for events like power failures.

Tripp Lite SNMPWEBCARD is a versatile network card that can be installed in compatible Tripp Lite UPS systems or PDUs to enable remote monitoring, control, and reporting. With this device, you can manage your UPS system or PDU from a web browser, telnet, or SNMP Network Management Station. The SNMPWEBCARD allows you to reboot the device, control outlets, shed nonessential loads, monitor load levels, and receive SNMP traps or email alerts for events like power failures.

User’s Guide
SNMPWEBCARD
Firmware Version 12.04.0048 / 12.04.0049 / 12.04.0051
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
Copyright © 2010 Tripp Lite. All trademarks are the sole property of their respective owners.
1. Introduction 2
1.1 System Requirements 2
2. Installation and Configuration 2
2.1 Default UPS System Shutdown Setting 2
2.2 Other Default Settings 3
2.3 SNMP Configuration 3
3. Web Console 3
3.1 Opening the Web Console 3
3.2 Web Console Interface 4
3.3 Status 4
3.4 Actions > Control 6
3.4.1 Actions > Control > Economy Mode 6
3.5 Actions > Loads 7
3.6 Settings > Device 8
3.7 Settings > Events 8
3.8 Settings > Contacts 9
3.9 Settings > Network 10
3.10 Settings > System 13
3.11 Logs > Events 14
3.12 Logs > Data 15
3.13 Help 15
4. Telnet/SSH Console 16
5. Load Ramping and Shedding 17
6. Troubleshooting 18
7. Technical Support 18
Documentation Notice: This Users Guide is a supplement to the printed manual that came with your SNMPWEBCARD or network-enabled PDU. Refer to the printed manual
for instructions on hardware installation and basic conguration, including IP address assignment. If you have misplaced your printed manual, refer to the electronic version
included on the bundled CD-ROM or download it at www.tripplite.com/support/manuals/.
WARRANTY
REGISTRATION:
register online today for a
chance to win a FREE Tripp Lite
product—www.tripplite.com/warranty
A
D
E
F
G
H
B
C
2
1. Introduction
2. Installation and Configuration
1.1 System Requirements
2.1 Default UPS System Shutdown Settings
SNMPWEBCARD is an optional network card that you can install in the accessory slot of a compatible UPS systems or PDU*. SNMPWEBCARD
connects your UPS system or PDU to your Ethernet network as a manageable device that supports remote monitoring, remote control and remote
condition reporting. You can manage the device from PowerAlert Network Management System, an SNMP Network Management Station, a Web
browser or telnet, allowing you to reboot, control outlets, shed nonessential loads, monitor load levels and more. The SNMPWEBCARD can also send
SNMP traps or e-mail messages to the addresses you specify, alerting you automatically to events such as power failures.
* SNMPWEBCARD is preinstalled in Tripp Lite Monitored and Switched PDUs, which can be identied by the presence of “MN” or “NET” in the model name.
For instructions on hardware installation and basic conguration, refer to the printed manual that came with your SNMPWEBCARD or PDU. The
manual can also be found on the bundled CD-ROM or downloaded from www.tripplite.com/support/manuals/.
During a power failure, SNMPWEBCARD is pre-congured to shut
down the UPS system two minutes after receiving a low battery signal.
This allows the UPS system to provide the maximum available runtime
to connected equipment. If you want to change the default setting,
follow these instructions and refer to Figure 2-1:
Use a Web browser to open the PowerAlert console window for 1.
your SNMPWEBCARD (see 3.1 Opening the Web Console for
instructions).
Click the “Settings” button2.
A
at the top of the window.
Click the “Events” button3.
B
at the left side of the window.
4. Conrm that the “Battery Low
C
in the “Shutdown”
D
column is
checked.
5. Click the Details Tab
E
or double-click on the icon to access
settings.
6. From the Details page
F
, choose your preferred settings from the
Settings drop down menu
G
and click the “Save Changes” button
H
.
Figure 2-1: UPS System Shutdown Settings
Tripp Lite UPS system or PDU with compatible accessory slot
Ethernet network that supports the TCP/IP protocol
One of the following options for remote monitoring and control:
PowerAlert Network Management System
SNMP-based Network Management Station (such as HP
®
OpenView
®
)
Web browser that supports frames, forms and Java™ (such as Microsoft
®
Internet Explorer
®
7.0 or later)
Standard telnet program
For “Terminal Mode” conguration only:
Terminal emulation software program (such as HyperTerminal)
Computer with available DB9 serial port
Warning: Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to signicantly affect its safety or effectiveness
is not recommended. Do not use this equipment in the presence of a ammable anesthetic mixture with air, oxygen or nitrous oxide.
3
3. Web Console
2.2 Other Default Settings
2.3 SNMP Configuration
3.1 Opening the Web Console
SNMPWEBCARD allows a compatible UPS system or PDU to function as an SNMP-managed device on your network, using the SNMP agent and
Management Information Base (MIB). The SNMP agent resides in the SNMPWEBCARD rmware and responds to standard SNMP commands
(Get, Get Next and Set). It can also generate SNMP traps (messages). The MIB determines which parameters can be monitored and controlled. Two
MIB lesTripplite.mib and RFC1628.mib—must be loaded on each Network Management Station that will monitor the managed device. (The les
are provided on the CD-ROM included with the SNMPWEBCARD or network-enabled PDU. Consult your Network Management Station software
documentation for instructions on how to import MIB les.)
The Web console is the primary graphical user interface for the SNMPWEBCARD.
Open a Web browser that supports frames, forms and Java. 1.
Type the IP address assigned to the SNMPWEBCARD or PDU into 2.
the address eld and press the enter key. (Refer to the printed manual
for IP address assignment instructions.)
You should be prompted for a user name and password (Figure 3.
3-1). The default administrator user name is admin and the default
password is admin.
After you enter the user name and password, the status page (Figure 4.
3-3) will appear in the browser window.
Note: Pages update automatically every 30 seconds. Reload/refresh
a page manually to update sooner.
Figure 3-1: Web Console Login
Setting Default Value Additional Information
IP Address Obtain via DHCP
3.9 Settings > Network
User Name and Password
User Name: admin Password: admin (For Version 12.04.0030 and Above)
User Name: guest Password: guest
User Name: admin Password: [blank] (For Versions 12.03.0024 and 12.04.0019)
3.10 Settings > System
Telnet Access Enabled (SSH Access: Enabled)
3.9 Settings > Network
Web Access Enabled (SSL Access: Disabled)
3.9 Settings > Network
SNMP Access Enabled for Version 12.04.0040 and above
Disabled for Previous Versions
Default SNMP Access for 12.04.0040 and above
Community Access Type Network Access SNMP Version
tripplite read/write all v2c
public read only all v1
3.9 Settings > Network
Temperature High &
Battery Low Event
Shut Down UPS System 2 Minutes After Event
3.7 Settings > Events
E-mail Notification Not Configured
3.7 Settings > Events
SNMP Traps Not Configured
3.9 Settings > Network
Time Use Onboard Clock (Set Manually)
3.10 Settings > System
Event Logging Enabled
3.11 Logs > Events
Data Logging Disabled
3.12 Logs > Data
Ramp/Shed Remain off / Remain on (not configured)
5.0 Load Ramping and Shedding
SYSLOG Disabled
3.9 Settings > Network
Figure 2-2: Default SNMPWEBCARD Settings
B
D
E
F
A
C
4
3.2 Web Console Interface
3.3 Status
Clicking the Tripp Lite logo
A
in the header opens Tripp Lites Web
site in a new browser window. The header also contains the menu
buttons
B
, which are the main navigational icons of the console.
Clicking a menu button reveals submenu buttons
C
on the left side
of the console that are applicable to the selected menu button. When
you click a menu or submenu button, the text changes from white to
green.
Each submenu has an information section
D
that appears when the
submenu is selected. The information section contains data, settings
and/or controls. Several of the information sections are further
divided into tabs
E
.
The alarm section
F
appears at the bottom of the console window
regardless of which submenu is selected. If an alarm or other
notication condition occurs, the alarm section will show the
severity of the condition, the cause of the condition (such as “UPS on
Battery”) and the automatic response or recommended user response
(such as “Prepare system for shutdown”).
Click the “Status” menu button to display the status page (Figure
3-3), which displays device information, device summary and
alarm status. Four additional buttons within the window allow
you to select information categories: input information, output
information, battery information and miscellaneous information such
as additional device information and system information. When you
activate an information category, the button for that category changes
from white to blue. The status of each information item is indicated
by the icon next to the item.
Figure 3-2: Console Interface Overview
Figure 3-3: Status Page
A
5
3.3 Status ( Co ntinued )
RSS Feed
The RSS Feed feature was implemented to allow users to subscribe
to the SNMPWEBCARD to view current alarm status, as well as
event logs in the form of .XML, .TXT and .CSV les. This allows
a user to quickly view status on the SNMPWEBCARD without
requiring a login to each individual device.
1. Click on the RSS symbol
A
.
2. Add the URL http://x.x.x.x:8080/digest.xml to the RSS reader or
aggregator. Note: If the SNMPWEBCARD is congured to SSL mode,
enter HTTPS instead of HTTP.
This is an example of the status screen viewed via the RSS reader:
Dynamic Generation of Status Report
The SNMPWEBCARDs Web interface makes it possible to retrieve current alarm status through XML, text (TXT), or comma-delimited CVS le
extensions. This feature can be used to integrate status information into proprietary management systems. To retrieve the le, enter the following URL:
http://x.x.x.x/status.leextension. Note: If the SNMPWEBCARD is congured to SSL mode, enter HTTPS instead of HTTP.
Figure 3-4: RSS Feed Screen
Figure 3-5: RSS Subscription
Figure 3-6: Status Screen
6
3.4 Actions > Control
3.4.1 Actions > Control > Economy Mode
Click the “Actions” menu button and the “Control” submenu button to
display the Actions > Control page. Click the “Controls” tab (Figure
3-7) to see commands that you can execute immediately or schedule for
automatic execution. To execute a command immediately, select it from the
drop-down menu and click the “Execute” button. To schedule a command,
select it from the drop-down menu, set the desired time and frequency
parameters and click the “Schedule” button.
If the command you select from the drop-down menu has operational
parameters that you can modify, they will be shown in the “Parameters”
area. You can click the editable variables and type new values to change
the settings for the command. If you plan to change the command
parameters, you should change them before you execute the command or
add it to the command schedule.
Available commands include “Reboot UPS,” “Initiate Self-Test,” “Cycle
All Loads,” “Cycle Load,” “Turn Load Off,” “Turn Load On,” “Turn All
Loads Off,” and “Turn All Loads On”. For a complete list of commands
available for your device, refer to the drop-down menu.
Click the “Schedules” tab (Figure 3-8) to see a list of scheduled commands.
To remove a scheduled command, check the box next to the command and
click the “Delete Selections” button.
Figure 3-7: Actions > Control > “Controls” Tab
Figure 3-8: Actions > Control > “Schedules” Tab
Figure 3-9: Actions > Control > “Controls” Tab > Set Economy Mode
Economy Mode
When a SmartOnline UPS System operates in on-line mode, it continuously
converts AC input power to DC (battery) power and converts DC power to
regulated AC output power. Continuous double conversion produces ideal
output, but does not provide maximum efciency.
In Economy Mode (available on select models), the UPS system increases
efciency by implementing dynamic double conversion, which means it
suspends or resumes double conversion automatically as the quality of input
power changes. As long as input power quality is satisfactory, the UPS system
suspends double conversion and operates with maximum efciency. If input
power quality deviates from the designated safe operating range, the UPS
system resumes double conversion until input power quality improves.
You can turn Economy Mode on or off at any time, from any location. You can
also schedule Economy Mode, allowing the UPS system to provide maximum
protection during peak hours and maximum efciency during off-peak hours.
Enabling Economy Mode:
To put a Tripp Lite SmartOnline UPS System into Economy Mode, go to the
Actions” menu button and the “Control” submenu button. Select either “Enable
Economy Mode” or “Set Economy Mode”, depending on the UPS. If the UPS
has “Set Economy Mode”, enter a “1” in the “Parameters-Value” eld and then
click the “Execute Command” button. On the front panel of the UPS system, the
“LINE” and “LOAD” LEDs will illuminate green and the “BYPASS” LED will
illuminate a solid yellow when the UPS system is in Economy Mode. Models
with LCD display will indicate Economy Mode status in the LCD screen.
7
3.4.1 Actions > Control > Economy Mode (Continue d)
3.5 Actions > Loads
Click the “Actions” menu button and the “Loads” submenu button
to display the Actions > Loads page (Figure 3-10). You can control
the outlets of the managed device by selecting the load and then
clicking the appropriate “On,” “Off” or “Cycle” button. The load
of connected equipment is displayed as a percentage of maximum
capacity, allowing you to see whether additional equipment can be
added safely. (Load uctuates with the power demands of connected
equipment. It is prudent to limit the load to approximately 80% of
maximum capacity in order to accommodate higher startup power
demands and other increased power needs.)
If your device has controllable load banks, additional buttons allow
you to control each load bank. (Each load bank consists of one or
more outlets.) You can use the “Description” eld to label the banks
for easy reference. The main control buttons affect all outlets at
once. Note: If the control buttons remain grayed out when a load is
selected, this condition indicates the outlet is non-controllable.
Warning: The load controls start or stop the ow of electricity
to your device’s outlets. Make sure you know which equipment
is connected to each load bank before attempting to use these
controls. Check the outlet labels and/or test the load banks
by plugging a circuit tester or small light into each outlet and
observing the effects of the controls.
Note: On select PDUs and UPS systems it is possible to dene
logical outlet groups (groups of individual outlets) that can be
controlled through a single command to turn ON/OFF or Cycle (see
Figure 3-10a). This feature is only available on models that support
Ramping and Shedding. See Section 5Load Ramping and Shedding
for more information. For select PDUs, support is available for
individual outlet current and power information. If the PDU supports
individual current and power information, additional columns (for
Current and Power) will be displayed on the Loads page (see Figure
3-10b).
Figure 3-10: Actions > Loads Page
Figure 3-10a: Actions > Loads > Load Groups
Figure 3-10b: Actions > Loads > Load Current/Power
Disabling Economy Mode:
To put a Tripp Lite SmartOnline UPS System out of Economy Mode, go to the “Actions” menu button and the “Control” submenu button. Select either
“Disable Economy Mode” or “Set Economy Mode”, depending on the UPS. If the UPS has “Set Economy Mode”, enter a “0” in the “Parameters-Value” eld
and then click the “Execute Command” button. On the front panel of the UPS system, the “LINE”, “ONLINE”, and“LOAD” LEDs will illuminate green.
8
3.7 Settings > Events
Click the “Settings” menu button and the “Events” submenu button to
access the Settings > Events page (Figure 3-12). The Settings > Events
page allows you to congure responses to changes in operating and
environmental conditions.
Events are divided into four categories: Critical, Warning,
Information and Ofine. Each event category has an icon associated
with it. The icon will be displayed in the alarm status section of the
console window (with other event information) when an event of that
category occurs.
You can congure settings for several event types, including “On
Battery” and “Battery Low.” (Events vary by device.) See Figure 3-13
Settings > Events > Details Tab. You can congure several settings
categories that specify actions to be executed when the selected event
takes place:
Shutdown” Turns the device off after a specied period of time.
“Contact Notication” Sends an e-mail to an e-mail address(es)
in your contact list. (Requires an e-mail contact to be set. See
Figure 3-14 Settings > Contacts.)
“SNMP Trap Notication” Sends an SNMP trap to a specied IP
address(es) in your SNMP list. (Requires an SNMP contact to be
set. See Figure 3-15 Settings > Contacts.)
“Logging”– Enables logging for the selected event. Note: The Log
can be accessed via Logs Menu.
“SNMP Set Notication” –Allows the device to perform an SNMP
set on another SNMP-enabled device or application on the network,
allowing the device or application to be notied when the event
occurs. (Requires an SNMP contact to be set. See Figure 3-15 >
Contacts.)
Check the “Status” box next to the event category to enable the
option.
Figure 3-12: Settings > Events > Summary Tab
Figure 3-13: Settings > Events > Details Tab
3.6 Settings > Device
Click the “Settings” menu button and the “Device” submenu button
to display the Settings > Device page (Figure 3-11). You can edit the
device variables for the UPS system.
Note: Some UPS systems have fewer device variables; some
have more. Some UPS systems will ll the “Serial Number” eld
automatically. The “Low Battery Warning” eld is tied to the
“Battery Capacity Below Warning” event.
See Section 5 – Load Ramping and Shedding for information about
the “Ramping” and “Shedding” tabs. The tabs will only be accessible
if the device supports these features.
Figure 3-11: Settings > Device > Variables Tab
9
3.8 Settings > Contacts
Click the “Settings” menu button and the “Contacts” submenu
button to display the Settings > Contact Settings page.
The “Email” tab (Figure 3-14) shows a table of e-mail contacts.
Before your SNMPWEBCARD can send e-mail notications, you
must enter e-mail server information and add at least one e-mail
contact. Click the “SMTP Settings” button to enter the settings for
your mail server. If you do not know the correct settings, contact
your network administrator. Add a new email contact by clicking
the “New” button and entering the information requested, and
save. Test your settings by highlighting/selecting an email contact,
then click the “Send Test Email” button.
Additional requirements for E-mail settings:
Enter a valid IP address or DNS name for the SMTP mail 1.
server. (Using a DNS name requires valid DNS server settings.
You will have the option to enter two: “Preferred DNS Server”
and “Alternate DNS Server”. See Section 3.9 Settings >
Network.)
If SMTP authentication is required, obtain the authentication 2.
information from your network Administrator (see Figure
3-14a).
The mail server must be set up to relay e-mail from the subnet 3.
or IP address of the SNMPWEBCARD if SMTP Authentication
is not being used.
The “To” and “From” addresses must be valid.4.
The “SNMP” tab (Figure 3-15) shows a table of SNMP contacts.
Before your SNMPWEBCARD can send an SNMP trap or SNMP
set to an IP address, you must add at least one SNMP contact.
Add a new contact by clicking the “New” button and entering the
information requested, and save. If you do not know the correct
settings, contact your network administrator. (The standard port
for SNMP set destinations is port 161. The standard port for
SNMP trap recipients is port 162.)
Note: If adding an SNMP contact to be used with a SNMP Set
Notication, use port 161 or the port number that the remote
SNMP device can be accessed on. After adding Email and SNMP
contacts, the user must set contacts for trap sending during events
via Settings>Events (see 3.7 Settings>Events).
Note: You also need to congure and enable each event setting
through the Settings>Events window before notications can be
sent to your contacts.
Figure 3-14: Settings > Contacts > Email Tab
Figure 3-14a: Settings > Contacts > Email Tab > SMTP Server Settings
Figure 3-15: Settings > Contacts > SNMP Tab
10
3.9 Settings > Network
Click the “Settings” menu button and the “Network” submenu
button to display the Settings > Network page.
Note: Any changes in the “TCP/IP” tab, “Telnet/SSH” tab or Web
tab require the card to be rebooted.
The “TCP/IP” tab (Figure 3-16) contains several network settings:
“MAC Address” is the unique physical address of the
SNMPWEBCARD and cannot be changed. The address is also
printed on a label on the surface of the card. An extra label may
be included.
“Host Name” is the unique name by which the
SNMPWEBCARD is identied on the network. Host name is
used to identify a particular host in various forms of electronic
communication such as Web or email and is translated into
an IP address via the Domain Name System (DNS) resolver
for communication between devices over the network. Note:
It is necessary to specify a DNS IP Address in the Settings >
Network > TCP/IP Tab page and include these descriptions in
the conguration of all pertinent Router/Switch networks.
“Domain Name” denes the local subnetwork.
“Boot Mode” denes whether the card has a static IP address
(assigned manually) or a DHCP address (assigned automatically
by a DHCP server on your network). DHCP is the default
setting. (For instructions on assigning a static IP address via
terminal mode, refer to the printed manual that came with your
SNMPWEBCARD or PDU.)
“IP Address,” “Network Mask” and “Default Gateway” are IP
network settings that will either be assigned automatically or
must be entered manually, depending on whether the card is
set to use a static IP or DHCP. If you don’t know the correct
settings, contact your network administrator.
“Preferred DNS Server” and “Alternate DNS Server” are
required only if you want to use domain names (such as
mailserver.xyz.com) in addition to numeric addresses (such as
192.168.0.123).
“Ethernet Port Speed” denes the communication speed of the
SNMPWEBCARD Ethernet port. By default, it will auto-
negotiate in order to use the fastest speed thats compatible with
your network equipment.
The “Telnet/SSH” tab (Figure 3-17) determines whether Telnet/
SSH access is enabled or disabled. You can also set the Telnet/SSH
port. (Default Settings: Telnet port is 23, SSH port is 22.) Note:
Telnet/SSH access requires a user name and an admin password.
Guest users do not have Telnet/SSH access. See Section 4.0 –
Telnet/SSH Console for additional information about Telnet/SSH
access. SSH is enabled by default.
(continued)
Figure 3-16: Settings > Network > TCP/IP Tab
Figure 3-17: Settings > Network > Telnet/SSH Tab
11
3.9 Settings > Network (continue d)
The “Web” tab (Figure 3-18) allows you to enable or disable Web
browser access, choose the HTTP and/or HTTPS protocol and set
the HTTP port.
HTTP (default setting) is the standard protocol used by Web
browsers. HTTPS is a secure protocol that encrypts and decrypts
data passed between the user and the SNMPWEBCARD. If HTTPS
is selected, users can access the SNMPWEBCARD securely with
HTTPS (https://x.x.x.x). If HTTP/HTTPS is selected, users can
access the SNMPWEBCARD with either protocol. Note: HTTP and
HTTPS can be globally or individually enabled/disabled.
Port 80 is the default HTTP port. The port can be changed in HTTP
mode, but cannot be changed in HTTP/HTTPS mode. Port 443 is
the HTTPS port and cannot be changed.
Note: Enabling HTTPS requires the card to reboot. This process
may take several minutes. The default community name for
SNMPWEBCARD rmware 12.04.0040 and above is tripplite (read/
write).
Access to the SNMPWEBCARD via SNMP can be congured to
allow SNMP access (via a dened community string) to everyone, a
range or a single IP by dening the appropriate subnet mask.
Figure 3-18: Settings > Network > Web Tab
Figure 3-19: Settings > Network > SNMP > SNMP Mode
Figure 3-20: Settings > Network > SNMP > V1/V2c Users Figure 3-21: Settings > Network > SNMP > V3 Users
SNMPv1 and SNMPv2
IP Address Subnet Community Access
192.168.1.1 (single) 255.255.255.255 User-Defined User-Defined
192.168.1.0 (range) 255.255.255.0 User-Defined User-Defined
192.168.0.0 255.255.0.0 User-Defined User-Defined
192.0.0.0 255.0.0.0 User-Defined User-Defined
* (everyone) 0.0.0.0 User-Defined User-Defined
12
3.9 Settings > Network (continue d)
SYSLOG
SYSLOG is a protocol that allows a machine to send event
notication messages across IP networks to event message
collectors – also known as SYSLOG servers. Up to 4 SYSLOG
servers may be dened by either IP address or hostname (Figure
3-22). Hostnames require that a DNS (Domain Name System)
server be congured on the TCP/IP tab. Once congured, any
event, setting change or action will trigger a message to be sent to
the SYSLOG server for logging.
Fig. 3-22: SYSLOG
As of Firmware version 12.04.0051, Tripp Lites SNMPWEBCARD supports SNMPv3 Gets and Sets. SNMPv3 Traps are not supported. The
SNMPWEBCARD SNMP Tab displays an additional three tabs to congure SNMP access:
A. SNMP Mode allows the user to congure what SNMP access is enabled or disabled. Note: Disabling SNMPv2 access will cause the
SNMPWEBCARD not to function with Tripp Lites PowerAlert Network Shutdown Agent or PowerAlert Network Management System.
B. V1/V2c Users Tab allows conguration of up to four community IDs.
C. V3 Users Tab allows conguration of up to four users. Tripp Lite’s SNMPv3 implementation requires that Authentication and Privacy Passwords
be congured.
User Name
The identifier of the user profile. SNMP version 3 maps Gets, Sets and Traps to a user profile by matching the user name
of the profile to the user name in the data packet being transmitted. A user name can have up to 32 ASCII characters.
Authentication Passphrase
A phrase of 8 to 32 ASCII characters that verifies that the Network Management System (NMS) communicating with this
device through SNMPv3 is the NMS it claims to be, that the message has not been changed during transmission, and that
the message was communicated in a timely manner, indicating that it was not delayed and that it was not copied and sent
again later at an inappropriate time.
Privacy Passphrase
A phrase of 8 to 32 ASCII characters that ensures the privacy of the data (by means of encryption) that a Network
Management System (NMS) is sending to this device or receiving from this device through SNMPv3.
Authentication Protocol The Tripp Lite implementation of SNMPv3 supports only MD5 authentication.
Privacy Protocol The Tripp Lite implementation of SNMPv3 supports only DES as the protocol for encrypting and decrypting data.
Public Value
A field provided to enter a username/password hint for SNMPv3 Admin users. This SNMPv3 value is part of the SNMPv3
UsmUserTable.
IP Address A field provided to enter the information found in the Address” column in the table on p. 11.
Mask A field provided to enter the information found in the “Subnet” column in the table on p. 11.
IMPORTANT NOTE: There are a total of four unique SNMP access IDs across all SNMP versions. Therefore, if you have two SNMPv1/2
communities, you can then have two SNMPv3 users.
A
13
3.10 Settings > System
Click the “Settings” menu button and the “System” submenu
button to display the Settings > System page.
The SNMPWEBCARD has a real-time clock with a backup
battery that keeps the clock running when the card is powered
off. The “CongFile” and three “Time” tabs (Figures 3-23
through 3-26) allow you to set the date and time manually or to
dene a Network Time Protocol server for periodic network time
synchronization. The time zone can also be specied. If you don’t
know the correct Network Time Protocol server settings, contact
your network administrator.
The “Security” tab (Figure 3-27) allows you to dene usernames
and set passwords for three user levels: guest, manager and
administrator (admin). Guest users have read-only access and
do not have telnet access. Manager users have similar rights to
Admin users, however, they are not allowed to change security
settings. Admin users have read/write access, which means that
they can control the SNMPWEBCARD and change its settings.
Tripp Lite recommends dening passwords for both user levels.
Note: For rmware version 12.04.0019 and 12.03.0024, the default
admin password is blank. For rmware version 12.04.0030 and
above, the default admin password is admin.
Write Conguration/View Conguration
The SNMPWEBCARD can maintain a copy of its current
conguration as a backup in the event of system problems or to
congure other SNMPWEBCARDs via FTP.
To generate a conguration le (pacong.ini), select the “Write
Cong” button at the bottom of the page. This le can also be
viewed and saved to your computer
A
by clicking the “view”
button. You will be prompted with a login screen, at which time
you may enter Administrator username and password.
To distribute the conguration le to other SNMPWEBCARDs
(12.04.0040 or above), FTP to the SNMPWEBCARD’s IP address.
In binary mode, “PUT” the conguration le (pacong.ini) to
the SNMPWEBCARD, then close the FTP session. When the
SNMPWEBCARD reboots, it will operate according to the new
conguration le. Note: The admin password will be required to
view or download the conguration le.
Fig. 3-23: Settings > System > CongFile
Fig. 3-24: Settings > System > Time > TimeSource
Fig. 3-25: Settings > System > Time > NTP
Fig. 3-26: Settings > System > Time > RTC Figure 3-27: Settings > System > Security Tab
14
3.11 Logs > Events
Click the “Logs” menu button and the “Events” submenu button
to display the Logs > Events page (Figure 3-29). All events are
logged here with a date, time and description. Each event also
displays an icon that identies its status: normal, critical, warning,
information or ofine.
Figure 3-29: Logs > Events Page
3.10 Settings > System (continued )
Watchdog Tab
The Watchdog tab provides the user the ability to set up timers
that will reboot the card automatically if the Watchdog trigger
is reached. This provides a mechanism to maximize the uptime/
accessibility of the SNMPWEBCARD. The Watchdog tab allows
enabling/disabling of either the Ping probe or NTP probe.
Primary Ping Target: IPv4 address/hostname (requires DNS
settings to be congured).
Secondary Ping Target: IPv4 address/hostname (requires
DNS settings to be congured) (optional).
Ping Probe Interval: Time in minutes before retry.
Probe Tries Before Fail: The number of attempts to
ping the primary and secondary IP addresses before the
SNMPWEBCARD assumes there is a problem and reboots
itself.
The SNMPWEBCARD will continue to reboot until it is
successfully able to ping the primary or secondary IP address.
Primary NTP Target: IPv4 address (requires DNS settings
to be congured).
Secondary NTP Target: IPv4 address/hostname (requires
DNS settings to be congured) (optional).
NTP Probe Interval: Time in minutes before retry.
Probe Tries Before Fail: The number of attempts to get time
from the primary and secondary NTP addresses before the
SNMPWEBCARD assumes there is a problem and reboots
itself.
The SNMPWEBCARD will continue to reboot until it is
successfully able to get time from either the primary or secondary
IP address.
Note: The Watchdog tab is applicable for Firmware version
12.04.0051 and above.
Fig. 3-28: Settings > System > Watchdog
15
3.12 Logs > Data
3.13 Help
Click the “Logs” menu button and the “Data” submenu button
to display the Logs > Data page (Figure 3-30). Data logging
is disabled by default. You can enable data logging and save
changes by entering a logging interval between 1 and 60. When
data logging is enabled, all data elds and their current value are
logged. You can export the data log to a .CSV le by right-clicking
the “Export Data Log” link and choosing “Save Target As…” or
“Save Link As…” from the pop-up menu. Note: Only 250 data
entries at a time will be stored. The option to clear the Data Log is
also available. Simply click the “Clear Data Log” button.
Click the “Help” menu button to open a PDF that contains the most recent version of the SNMPWEBCARD User’s Guide.
Figure 3-30: Logs > Data Page
16
4. Telnet/SSH Console
Most of the monitoring and control features available in the Web
console (see Section 3 – Web Console) are also available in the telnet
and/or SSH console. Accessing the SNMPWEBCARD through the
telnet console is ideal for mobile or resource-limited platforms.
Accessing the Telnet Console
Open a telnet client and connect to the IP number of the
SNMPWEBCARD. At the login prompt, enter the admin user name
and password. (Telnet access must be enabled and an admin password
must be dened. Guest users do not have telnet access.) After a
successful login, you’ll see the telnet consoles main menu (Figure 4-1).
The Telnet Console Interface
The telnet console uses a menu-driven, text-based interface. It has
most of the same menus and submenus as the Web console, but they are
arranged differently. Several submenus that were previously grouped
below “Settings” now appear at the top level, and instead of appearing
at the top level, the “Status,” “Actions,” “Settings” and “Logs” menus
are accessible under the “Devices” menu. You’ll see those menu
choices after selecting your device, along with information about the
device (Figure 4-2). Note: You can also select an ENVIROSENSE
temperature/humidity and alarm monitoring device if one is present.
The functional menu hierarchy of the telnet console interface is shown
in Figure 4-3.
Figure 4-1: Telnet Console Main Menu
Figure 4-2: Telnet Console Device Submenu
Figure 4-3: Telnet Console Menu Hierarchy
17
5. Load Ramping and Shedding
Click the “Settings” menu button and the “Device” submenu button
to display the Settings > Device page. If your device supports load
ramping and shedding, the “Ramping” tab and/or “Shedding” tab
(Figure 5-1) will be available.
The “Ramping” and “Shedding” tabs each contain a table of the
load segments available for your device. Each load segment has
a “Description” eld, an “Action” eld and a “Delay” eld. The
“Description” eld allows you to enter a note about the equipment
connected to the load segment. The “Action” eld allows you to
congure the load ramping or shedding behavior by choosing from
the possible actions listed in the drop-down menu. The “Delay” eld
allows you to enter the delay (in seconds) before the specied action is
performed. After entering the desired values, click the “Save Changes”
button to make the values active. Ramping sequences are applied when
AC input power is switched on. Shedding sequences are applied when
AC input power is lost, increasing the battery backup runtime available
for supported equipment. You can disable load shedding by setting all
actions to “Remain On.” You can disable load ramping by setting all
actions to “Remain Off.
Load ramping and load shedding require a Tripp Lite UPS system or
PDU with switchable load banks (banks of one or more outlets that
can be switched on and off remotely, independent of other outlets).
A device that has switchable load banks can be classied as an
autonomous device or a non-autonomous device, which determines its
load ramping and load shedding characteristics (Figure 5-2).
An autonomous device can execute stored load shedding and load
ramping congurations independent of an SNMPWEBCARD
or PowerAlert. Conguration of an autonomous UPS system
requires PowerAlert or an SNMPWEBCARD (disconnect the
SNMPWEBCARD network cable before attempting to use an
autonomous UPS systems RS-232 serial port). Conguration of an
autonomous PDU requires an SNMPWEBCARD (the card is pre-
installed in “NET” models). Figure 5-3 lists autonomous devices that
are currently available.
Non-autonomous devices require an SNMPWEBCARD for
conguration and execution of a custom load shedding sequence. Non-
autonomous devices do not support custom load ramping. UPS systems
that have switchable load banks are non-autonomous devices unless
they are listed in Figure 5-3.
Note: Load ramping and shedding can also be congured through
the telnet console. (Select the rst menu option “1- Devices” from the
Main Menu, then select the rst device from the Device List menu, then
select the third menu option “3- Settings. From the Settings menu,
select the second menu option “1- Device”. From the Device Settings
menu, select the second menu option “2- Shedding” for shedding
conguration or the third menu option “3- Ramping” for ramping
conguration.)
Figure 5-1: Settings > Device > Shedding & Ramping Tabs
Custom Load Ramping Custom Load Shedding
Configuration Execution Configuration Execution
Autonomous Device
Requires SNMPWEBCARD
or PowerAlert.
Functions without
SNMPWEBCARD or
PowerAlert.
Requires SNMPWEBCARD
or PowerAlert.
Functions without
SNMPWEBCARD or
PowerAlert.
Non-Autonomous Device
Not supported. Not supported. Requires SNMPWEBCARD. Requires SNMPWEBCARD.
Figure 5-2: Autonomous and Non-Autonomous Device Characteristics
Part Number Series Number
SMART1500CRMXL All
SM2200RMDVTAA All
SM2200RMXL2UP All
SM2200RMXL2UTAA All
SMART2200CRMXL All
SMART2200RM2U AGSM7501
SMART2200RMXL2U AGSM6803, AGSM7109
SMART2600RM2U AGSM6907
SM3000RMNAFTA AGSM7090
SM3000RMXL2UTAA All
SMART3000CRMXL All
SMART3000RM2U AGSM6908, AGSM6909
SMART3000RMOD2U All
SMART3000RMXL2U All
SMX2200RT2UTAA All
SMX2200XLRT2U AGSM7145
SMX3000RT2UTAA All
SMX3000XLRT2U AGSM7144
SU3000RTXL2U All
SUINT3000RTXL2U All
Switched PDU models All with “NET” suffix
Switched PDU models All with “PDU3VS” prefix
Figure 5-3: Autonomous Devices
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
Tripp Lite has a policy of continuous improvement. Specications are subject to change without notice.
201005222 • 932946-EN
6. Troubleshooting
7. Technical Support
Conrm that the SNMPWEBCARD is turned on.
Check all connections and conrm that they are secure.
Refer to the following list of problems and implement any recommended
solutions.
If the problem persists after trying the recommended steps, contact
Tripp Lite Technical Support.
Problem Possible Solution
The IP address of the
SNMPWEBCARD is unknown.
If your network’s DHCP server assigned an IP address to the SNMPWEBCARD, contact your network
administrator to discover the IP address assigned to the card or view it during terminal session at boot-
up. You'll need to know the MAC address of the SNMPWEBCARD. If your network does not use DHCP,
or if you need to assign a static IP address for another reason, follow the instructions for assigning
a static IP address via terminal mode configuration. Refer to the printed manual that came with your
SNMPWEBCARD or PDU for more information.
Unable to perform SNMP get
operations.
Check the SNMP settings of the SNMPWEBCARD (see 3.9 Settings > Network). The IP address and
community name of the device or application trying to perform the SNMP get operation must be entered
in “NMS Access Settings” with “Read Only” or “Read/Write” permission.
Unable to perform SNMP set
operations.
Check the SNMP settings of the SNMPWEBCARD (see 3.9 Settings > Network). The IP address and
community name of the device or application trying to perform the SNMP set operation must be entered
in “NMS Access Settings” with “Read/Write” permission.
Unable to receive traps at your
management station.
Check the SNMP settings of the SNMPWEBCARD (see 3.9 Settings > Network). The IP address and
community name of the management station must be entered in “NMS Access Settings” with “Read Only”
or “Read/Write” permission. Also check trap recipient settings in Contacts menu and Events menu.
Unable to use autodiscovery
to find the agent from your
management station.
Check the SNMP settings of the SNMPWEBCARD (see 3.9 Settings > Network). The IP address and
community name of the management station must be entered in “NMS Access Settings” with “Read/
Write” permission. Versions below 12.04.0040 are not supported.
The HTTP interface displays an
error message: Action Fail.
If the previous command is not yet finished, another command cannot be executed. You must wait until
the previous command has finished.
SNMPWEBCARD e-mail
notifications are not working.
Before your SNMPWEBCARD can send e-mail notifications, you must enter e-mail server information
and add at least one e-mail contact in the Settings > Contacts > Email Tab (Figure 3-14). Click the
“SMTP Settings” button to enter the settings for your local mail server. If you do not know the correct
settings, contact your network administrator. Add a new e-mail contact by clicking the “New” button and
entering the information requested in the pop-up window. Test your settings by clicking the “Send Test
Email” button.
Additional requirements for E-mail settings:
Enter a valid IP address or DNS name for the SMTP mail server. (Using a DNS name requires valid DNS
server settings. See 3.9 Settings > Network.)
The mail server must not require authentication.1.
The mail server must be set up to relay e-mail from the subnet or IP address of the 2.
SNMPWEBCARD.
The “To” and “From” addresses must be valid.3.
A DNS IP must be specified in the Settings > Network > TCP/IP tab page.4.
Note: You also need to configure and enable each event setting through the Settings > Events
page before notifications can be sent to your contacts.
If you encounter a problem:
Before contacting Tripp Lite Technical Support, refer to Section 6 – Troubleshooting for possible solutions. If you are still unable to resolve the problem,
you can reach Tripp Lite Technical Support here:
www.tripplite.com/support
E-mail: techsupport@tripplite.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Tripp Lite SNMPWEBCARD User manual

Category
Remote power controllers
Type
User manual
This manual is also suitable for

Tripp Lite SNMPWEBCARD is a versatile network card that can be installed in compatible Tripp Lite UPS systems or PDUs to enable remote monitoring, control, and reporting. With this device, you can manage your UPS system or PDU from a web browser, telnet, or SNMP Network Management Station. The SNMPWEBCARD allows you to reboot the device, control outlets, shed nonessential loads, monitor load levels, and receive SNMP traps or email alerts for events like power failures.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI