LST Conventional Zone Module M512ME, M512ME User manual

  • Hello! I am an AI chatbot trained to assist you with the LST Conventional Zone Module M512ME User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
M512ME_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Conventional Zone Module
M512ME
Description
The addressable Conventional Zone Module M512ME
serves for the integration of conventional detectors,
detectors for intrinsically safe areas and special detec-
tors into an ADM loop with System Sensor/200 proto-
col. The conventional zone module provides an output
for resetting special detectors.
The address of the module is easily selected by means
of two integrated decadic rotary switches. The Surface
Mounting Box SMB500 is required for mounting the
module.
The module must be powered by an external supply.
ADM loop technology with
System Sensor/200 protocol
Integration of conventional and
special detectors into the ADM loop
Output for resetting of detectors
Setting of module address via
decadic rotary switches
Specifi cations
Operating voltage 18 – 32VDC
Current consumption from loop 300µA (quiescent)
Ambient temperature -10°C to +60°C
Dimensions L × W × H (without mounting plate) 70 × 70 × 32 (mm)
Weight 142g
Approval VdS G297009
Order number 249045
Order name Conventional Zone Module/Anal./500/SS M512ME
Surface Mounting Box
Dimensions W × H × D 125 × 124 × 55 (mm)
Colour cream
Weight 155g
Order number 249004
Order name Surface Mounting Box for M500/SS SMB500
/