Buhler TF Series Installation And Operation Instructions Manual

Type
Installation And Operation Instructions Manual
Fluidcontrol
Installation and Operation Instructions
Original instructions
Temperature sensor/switch
TF, TS, Thermolog
BE140006
11/2019
Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen
Tel. +49 (0) 21 02 / 49 89-0, Fax: +49 (0) 21 02 / 49 89-20
Internet: www.buehler-technologies.com
Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen
Tel. +49 (0) 21 02 / 49 89-0, Fax: +49 (0) 21 02 / 49 89-20
Internet: www.buehler-technologies.com
Read this instruction carefully prior to installation and/or use. Pay at-
tention particularly to all advises and safety instructions to prevent in-
juries. Bühler Technologies can not be held responsible for misusing
the product or unreliable function due to unauthorised modifications.
All rights reserved. Bühler Technologies GmbH 2020
Document information
Document No..........................................................BE140006
Version...........................................................................11/2019
TF, TS, Thermolog
Contents
1 Introduction..................................................................................................................................................................................................................... 2
1.1 Intended Use.........................................................................................................................................................................................................2
1.2 Model key............................................................................................................................................................................................................... 2
2 Safety instructions.........................................................................................................................................................................................................4
2.1 Important advice.................................................................................................................................................................................................4
2.2 General hazard warnings ................................................................................................................................................................................. 5
3 Transport and storage ..................................................................................................................................................................................................6
4 Setup and Connection .................................................................................................................................................................................................. 7
5 Operation and control ..................................................................................................................................................................................................8
5.1 TF-M-Pt100/TF-E-Pt100/TF-M-Pt100-VAL Temperature Sensor.............................................................................................................8
5.2 TSM/TSK/TSA Bi-Metal Temperature Switch..............................................................................................................................................8
5.3 Thermolog MK2/EK2 Temperature Sensor with 4-20mA Output.........................................................................................................8
6 Maintenance and repair ..............................................................................................................................................................................................9
7 Service and repair......................................................................................................................................................................................................... 10
8 Disposal............................................................................................................................................................................................................................ 11
9 Appendix..........................................................................................................................................................................................................................12
9.1 Technical data .................................................................................................................................................................................................... 12
9.1.1 TF and Thermolog Temperature Sensor ...................................................................................................................................... 12
9.1.2 TSA, TSK and TSM Temperature Switch .......................................................................................................................................12
9.2 Pin Assignment...................................................................................................................................................................................................13
9.2.1 TF-M-Pt100/TF-E-Pf100/TF-M-Pt100-VAL Temperature Sensor ............................................................................................ 13
9.2.2 Thermolog MK2/EK2 Temperature Sensor with 4-20 mA Output ....................................................................................... 13
9.2.3 TSA/TÖA Bi-Metal Temperature Switch....................................................................................................................................... 13
9.2.4 TSM/TSK Bi-Metal Temperature Switch ......................................................................................................................................14
10 Attached documents....................................................................................................................................................................................................15
iBühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
1 Introduction
1.1 Intended Use
Temperature sensors can be used to monitor the temperature of a fluid within a tank.
These operating instructions describe several temperature switches / sensors types in one, as many descriptions identical or
similar.
Please refer to the type plate to identify your model. In addition to the job number it also contains the item number and model
designation.
If a model has special features, these are described separately in the operating instructions.
WARNING
All device models are solely intended for industrial applications. They are
not safety com-
ponents
. The devices must not be used if failure or malfunction thereof jeopardises the
safety and health of persons.
Use in explosive areas is
prohibited
.
DANGER Explosion hazard when used in explosive areas
Use in explosive areas is prohibited.
1.2 Model key
Model key for TF temperature probe
Version
MS
VA
(max. 1000 mm)
Length
TF-M
TF-E
Brass
Stainless steel
Switching type
TF-M for version MS
------------
------------
------------
------------
2 lead
2L =
TF-E for version with VA
Plug connection
M3
M12
GS4
for 4 lead only
3L =
4L =
3 lead
4 lead
Model key for temperature sensor MK 2/EK 2
Version
MS
VA
(max. 1000 mm)
Length
MK
EK
Brass
Stainless steel
Plug connection
M12
MK2 for version with MS
------------
------------
------------
M3
EK2 for version with VA
2 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
Typenschlüssel für Temperaturfühler TSM/TSE
Number of temperature contacts
1 or 2
(max. 1000 mm)
Length
TSM
TSE
TSM for version MS
------------
------------
------------
------------
------------
------------
TSE for version with VA
Version
MS
VA
T1 (1st temperature contact)
NO contact
NC contact
50 °C
60 °C
70 °C
80 °C
TM50NC
TM60NC
TM70NC
TM80NC
TM50NO =
TM60NO =
TM70NO =
TM80NO =
Brass
Stainless steel
Plug connection
M3
M12
T2 (2nd temperature contact)
NO contact
NC contact
50 °C
60 °C
70 °C
80 °C
TM50NC
TM60NC
TM70NC
TM80NC
TM50NO =
TM60NO =
TM70NO =
TM80NO =
Model key for temperature sensor TSK
Number of temperature contacts
1 or 2
(max. 1000 mm)
Length
TSK
------------
------------
------------
------------
------------
------------
Version
MS
VA
T1 (1st temperature contact)
NO contact
NC contact
40 °C
50 °C
60 °C
70 °C
80 °C
TM40NC
TM50NC
TM60NC
TM70NC
TM80NC
TM40NO =
TM50NO =
TM60NO =
TM70NO =
TM80NO =
Brass
Stainless steel
Plug connection
M3
M12
T2 (2nd temperature contact)
NO contact
NC contact
40 °C
50 °C
60 °C
70 °C
80 °C
TM40NC
TM50NC
TM60NC
TM70NC
TM80NC
TM40NO =
TM50NO =
TM60NO =
TM70NO =
TM80NO =
3Bühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
2 Safety instructions
2.1 Important advice
Operation of the device is only valid if:
the product is used under the conditions described in the installation- and operation instruction, the intended application
according to the type plate and the intended use. In case of unauthorized modifications done by the user Bühler Technolo-
gies GmbH can not be held responsible for any damage,
when complying with the specifications and markings on the nameplates.
the performance limits given in the datasheets and in the installation- and operation instruction are obeyed,
monitoring devices and safety devices are installed properly,
service and repair is carried out by Bühler Technologies GmbH,
only original spare parts are used.
This manual is part of the equipment. The manufacturer keeps the right to modify specifications without advanced notice. Keep
this manual for later use.
Signal words for warnings
DANGER
Signal word for an imminent danger with high risk, resulting in severe injuries or death if not avoided.
WARNING
Signal word for a hazardous situation with medium risk, possibly resulting in severe injuries or death if not
avoided.
CAUTION
Signal word for a hazardous situation with low risk, resulting in damaged to the device or the property or
minor or medium injuries if not avoided.
NOTICE
Signal word for important information to the product.
Warning signs
These instructions use the following warning signs:
Warns of a general hazard Unplug from mains
Voltage warning Wear respiratory equipment
Warns not to inhale toxic gasses Wear a safety mask
Warns of corrosive liquids Wear gloves
General information
4 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
2.2 General hazard warnings
The equipment must be installed by a professional familiar with the safety requirements and risks.
Be sure to observe the safety regulations and generally applicable rules of technology relevant for the installation site. Prevent
malfunctions and avoid personal injuries and property damage.
The operator of the system must ensure:
Safety notices and operating instructions are available and observed,
The respective national accident prevention regulations are observed,
The permissible data and operational conditions are maintained,
Safety guards are used and mandatory maintenance is performed,
Legal regulations are observed during disposal,
compliance with national installation regulations.
Maintenance, Repair
Please note during maintenance and repairs:
Repairs to the unit must be performed by Bühler authorised personnel.
Only perform conversion-, maintenance or installation work described in these operating and installation instructions.
Always use genuine spare parts.
Do not install damaged or defective spare part. If necessary, visually inspect prior to installation to determine any obvious
damage to the spare parts.
Always observe the applicable safety and operating regulations in the respective country of use when performing any type of
maintenance.
5Bühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
3 Transport and storage
Only transport the product inside the original packaging or a suitable alternative.
The equipment must be protected from moisture and heat when not in use. It must be stored in a covered, dry, dust-free room
at room temperature.
6 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
4 Setup and Connection
DANGER Toxic, corrosive gasses
The sample gas can be harmful to the health if inhaled or on contact.
a) Ensure harmful gases are discharged safely.
b) Switch off the gas supply before performing maintenance and repairs, and flush the
gas lines with air. Secure the gas supply from accidentally being opened.
c) Protect yourself from toxic / corrosive gasses when performing maintenance. Wear
suitable protective equipment.
The temperature switch / sensor come complete and can be screwed onto the container with the thread. The maximum torque
of the screw-in thread is 25Nm.
When installing, be sure the sealing face is clean and even. Only screw the temperature switch / sensor into the fitted thread.
Sealed with an elastic sealing ring. No other sealants required.
7Bühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
5 Operation and control
DANGER Electric voltage
Risk of electric shock
a) Disconnect the unit from the mains when performing any maintenance.
b) Secure the equipment from accidental restarting.
c) The unit may only be maintained and opened by instructed, competent personnel.
The pin assignment for the respective models are listed in chapter Pin Assignment [> page13].
5.1 TF-M-Pt100/TF-E-Pt100/TF-M-Pt100-VAL Temperature Sensor
Type TF temperature sensors use a Pt100 temperature sensor per DIN/IEC751 class B to generate a temperature-dependent res-
istance signal. The Pt100 sensor is installed at the lowest point of the sensor tube to always ensure sufficient contact with the
medium being measured.
The temperature sensor TF-M-Pt100-VAL was designed for measuring storage temperatures and has a spring-loaded sensor
tube to allow installation free of play with a constant contact pressure at the measuring point.
5.2 TSM/TSK/TSA Bi-Metal Temperature Switch
The TS temperature sensors have a bi-metal temperature switch to signal a set temperature value. Unlike the TSM standard ver-
sion, the TSK and TSA versions with bi-metal switches have a lower hysteresis.
The TSA version is further specifically designed for installation in tube systems and cooling matrices.
The bi-metal switch is installed at the lowest point of the sensor tube to always ensure sufficient contact with the medium be-
ing measured.
5.3 Thermolog MK2/EK2 Temperature Sensor with 4-20mA Output
Type MK2 and EK2 temperature sensors use a Pt100 temperature sensor per DINEN/IEC60751 Class B to generate a temperat-
ure-dependent resistance signal.
The built-in electronics convert this resistance signal into a standard 4-20 mA two-lead signal.
The Pt100 sensor is installed at the lowest point of the sensor tube to always ensure sufficient contact with the medium being
measured.
8 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
6 Maintenance and repair
NOTICE
Always observe the applicable safety and operating regulations when performing any
type of maintenance.
If the devices are mounted according to the instructions, a maintenance is not necessary.
9Bühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
7 Service and repair
This chapter contains information on troubleshooting and correction should an error occur during operation.
Repairs to the unit must be performed by Bühler authorised personnel.
Please contact our Service Department with any questions:
Tel.: +49-(0)2102-498955
or your agent
If the equipment is not functioning properly after correcting any malfunctions and switching on the power, it must be inspected
by the manufacturer. Please send the equipment inside suitable packaging to:
Bühler Technologies GmbH
- Reparatur/Service -
Harkortstraße 29
40880 Ratingen
Germany
Please also attach the completed and signed RMA decontamination statement to the packaging. We will otherwise be unable to
process your repair order.
You will find the form in the appendix of these instructions, or simply request it by e-mail:
.
10 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
8 Disposal
Dispose of parts so as not to endanger the health or environment. Follow the laws in the country of use for disposing of elec-
tronic components and devices during disposal.
11Bühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
9 Appendix
9.1 Technical data
9.1.1 TF and Thermolog Temperature Sensor
TF-M-PT100 TF-E-PT100 THERMOLOG MK2 THERMOLOG EK2 TF-M-PT100-VAL
Screw-in thread: G ½ G ½ G ½ G ½ G ½
Max. pressure 5 bar 10 bar 5 bar 10 bar 1 bar
Operating temperature -40…+100 °C -40…+100 °C -20…+100 °C -20…+100 °C -40…+100 °C
Max. operating voltage
with M3 plug
- - 10-30 V DC 10-30 V DC -
Max. operating voltage
with M12 plug
- - 10-30 V DC 10-30 V DC -
Max. measuring current
Pt100
1 mA 1 mA - - 1 mA
Measuring range -40…+100 °C -40…+100 °C 0…+100 °C = 4-20 mA 0…+100 °C = 4-20 mA -40…+100 °C
Max. load R - - R= (UB-7.5 V)/ 0.02 A R= (UB-7.5 V)/ 0.02 A -
9.1.2 TSA, TSK and TSM Temperature Switch
TSA TSK TSM
Screw-in thread: G ½ G ¾ G ½
Max. pressure 15 bars 1 bar 5 bar
Operating temperature -40..+80 °C -40..+80 °C -40..+80 °C
Max. operating voltage
with M3 plug
230 VAC 230 VAC 230 VAC
Max. operating voltage
with M12 plug
24 V AC/DC 24 V AC/DC 24 V AC/DC
Max. Switching current 2 A 2.5 A 2.5 A
Max. Contact load 100 VA 100 VA 100 VA
Switching tolerance ± 5 K ± 5 K ± 5 K
Switch-back difference 15 K ± 3 K 15 K ± 3 K 18 K ± 5 K (TMÖ50-TMÖ80)
35 K ± 5 K (TMS60)
40 K ± 5 K (TMS70)
Switching function of
temperature contacts
TSA = NO*
TÖA = NC*
TKS = NO*
TKÖ = NC*
TMS = NO*
TMÖ = NC*
*NO = normally open contact / NC = normally closed contact
12 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
9.2 Pin Assignment
9.2.1 TF-M-Pt100/TF-E-Pf100/TF-M-Pt100-VAL Temperature Sensor
With M3 plug per DIN
EN 175301-803
With GS4 plug With M12 plug
2 lead
3 lead
4 lead
9.2.2 Thermolog MK2/EK2 Temperature Sensor with 4-20 mA Output
With M3 plug per DIN EN 175301-803 With M12 plug
9.2.3 TSA/TÖA Bi-Metal Temperature Switch
With M3 plug per DIN EN 175301-803 With M12 plug
13Bühler Technologies GmbHBE140006 ◦ 11/2019
TF, TS, Thermolog
9.2.4 TSM/TSK Bi-Metal Temperature Switch
NOTICE
The designation T1 indicates the temperature contact with the low switching temperat-
ure.
The designation T2 indicates the temperature contact with the higher switching temper-
ature.
With M3 plug per DIN EN 175301-803 With M12 plug
14 Bühler Technologies GmbH BE140006 ◦ 11/2019
TF, TS, Thermolog
10 Attached documents
Declarations of conformity: KX140002, KX110021
RMA decontamination statement
15Bühler Technologies GmbHBE140006 ◦ 11/2019
RMA-Nr./ RMA-No.
Die RMA-Nummer bekommen Sie von Ihrem Ansprechpartner im Vertrieb oder Service./ You may obtain the RMA
number from your sales or service representative.
Firma/ Company
Firma/ Company
Straße/ Street
PLZ, Ort/ Zip, City
Land/ Country
Zu diesem Rücksendeschein gehört eine Dekontaminierungserklärung. Die gesetzlichen Vorschriften schreiben vor,
dass Sie uns diese Dekontaminierungserklärung ausgefüllt und unterschrieben zurücksenden müssen. Bitte füllen Sie
auch diese im Sinne der Gesundheit unserer Mitarbeiter vollständig aus./ This return form includes a decontamination
statement. The law requires you to submit this completed and signed decontamination statement to us. Please com-
plete the entire form, also in the interest of our employee health.
Ansprechpartner/ Person in charge
Name/ Name
Abt./ Dept.
Tel./ Phone
E-Mail
Gerät/ Device
Anzahl/ Quantity
Auftragsnr./ Order No.
Serien-Nr./ Serial No.
Artikel-Nr./ Item No.
Grund der Rücksendung/ Reason for return
Kalibrierung/ Calibration Modifikation/ Modification
Reklamation/ Claim Reparatur/ Repair
andere/ other
bitte spezifizieren/ please specify
Ist das Gerät möglicherweise kontaminiert?/ Could the equipment be contaminated?
Nein, da das Gerät nicht mit gesundheitsgefährdenden Stoffen betrieben wurde./ No, because the device was not operated with
hazardous substances.
Nein, da das Gerät ordnungsgemäß gereinigt und dekontaminiert wurde./ No, because the device has been properly cleaned and
decontaminated.
Ja, kontaminiert mit:/ Yes, contaminated with:
explosiv/
explosive
entzündlich/
flammable
brandfördernd/
oxidizing
komprimierte
Gase/
compressed
gases
ätzend/
caustic
giftig,
Lebensgefahr/
poisonous, risk
of death
gesundheitsge-
fährdend/
harmful to
health
gesund-
heitsschädlich/
health hazard
umweltge-
fährdend/
environmental
hazard
Bitte Sicherheitsdatenblatt beilegen!/ Please enclose safety data sheet!
Das Gerät wurde gespült mit:/ The equipment was purged with:
Diese Erklärung wurde korrekt und vollständig ausgefüllt und von einer
dazu befugten Person unterschrieben. Der Versand der (dekontaminier-
ten) Geräte und Komponenten erfolgt gemäß den gesetzlichen Bestim-
mungen.
This declaration has been filled out correctly and completely, and signed by
an authorized person. The dispatch of the (decontaminated) devices and
components takes place according to the legal regulations.
Datum/ Date
rechtsverbindliche Unterschrift/ Legally binding signature
Falls die Ware nicht gereinigt, also kontaminiert bei uns eintrifft, muss die
Firma Bühler sich vorbehalten, diese durch einen externen Dienstleister
reinigen zu lassen und Ihnen dies in Rechnung zu stellen.
Should the goods not arrive clean, but contaminated, Bühler reserves the
right, to comission an external service provider to clean the goods and in-
voice it to your account.
Firmenstempel/ Company Sign
DE000011
01/2019
RMA-Formular und Erklärung über Dekontaminierung
RMA-Form and explanation for decontamination
Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen
Tel. +49 (0) 21 02 / 49 89-0, Fax: +49 (0) 21 02 / 49 89-20
Internet: www.buehler-technologies.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21

Buhler TF Series Installation And Operation Instructions Manual

Type
Installation And Operation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages