INSTALLATION INSTRUCTIONS
Connect X300
Description
Connect X300 is a physical device that is the gateway connection between a Cloud service and a
controlled/monitored system. This system in a building can include fire alarm control panels, devices,
sensors, detectors, etc.
X61
X60 X63
X30 X31
X1 P1 X2 P1
X70
ON/OFF
X80
L+
M
EARTH
SCREW
X62
NOT
USED
NOT
USED NOT
USED
NOT
USED
POWER
SUPPLY
FIRE PANEL
CONNECTION
INTERNET
ACCESS
Figure 1
Connect X300 Gateway
Connections and Indicators
X1P1: Connection to Desigo Fire Safety Modular/Cerberus PRO Modular via FCM2041-U2/-
U3 Operator Interface.
Connection to Desigo FC2025/FC2050 and Cerberus PRO FC922/FC924 via
FCM2018/2019/2035-U2/-U3 Operating Units.
Connection to Desigo FV2025/2050 and Cerberus PRO FV922/924 via VCA2002-A1 Card
Cage.
X2P1: Connection to internet network
Features
Two Ethernet ports for WAN and LAN
Remote firmware and configuration data update over the IP Interface
LED indication of activities and state
Operating voltage DC 24V
Max current load: 515mA DC
Plug-in screw terminal block for supply
Mounting on wall using enclosures
Depending on firmware, the following functions are supported (examples):
Multi-site management
Remote monitoring
firealarmresources.com
A6V11649121_enUS_b
2
Application
The device integrates Desigo Fire Safety Modular, Cerberus PRO Modular, Desigo
FC2025/FC2050/FV2025/FV2050, and Cerberus PRO FC922/FC924/FV922/FV924 fire panels over IP. It
transmits data to the cloud over IP networks or over mobile networks (3G/4G/LTE).
Functions
The Connect X300 provides two integration levels to connect fire alarm control panels to the cloud: System
integration (between the Connect X300 and the fire panels) and cloud integration (between the Connect
X300 and the cloud). The Connect X300 supports Ethernet and 3G/4G/LTE for cloud connectivity.
Mounting and Wiring
The Connect X300 can be mounted inside the ENCL-01, P/N S54465-C63-A1, or PAB-ENCL Siemens
enclosures using adaptor plates. Adaptor plate CGAP, P/N S54811-B101-A1, is used with the ENCL-
01 enclosure while adaptor plate CGAP2, P/N S54811-B102-A1, is used for the PAB-ENCL enclosure.
Refer to Figures 2 through 6.
Wiring the Connect X300 Gateway inside PAB-ENCL Enclosures
To connect the ethernet cable, see Figure 3. Use knockouts from the right side; wires are considered
Power Limited. To connect the power to the Connect X300 Gateway, see Figure 2.
Option: The FP2011-U1 Power Supply can be used with the cable provided to connect the power from
the FP2011-U1 Power Supply to the Connect X300 Gateway. Use knockout close to the location of the
Power Supply to enter the box. Wires are considered Non-Power Limited.
firealarmresources.com
A6V11649121_enUS_b
3
E
{
ENCL-01
Enclosure
S54465-C63-A1
CGAP
Adapter Plate
S54811-B101-A1
Connect X300
Gateway
S55842-Z121-A100
Insert wires
into to 2-POS
Power Plug
(Black Wire to
POS “L+”) PSC-12 Power
Supply (Located
in the Desigo Fire
Safety
Modular/Cerberus
PRO Modular
Enclosure)
12-22 AWG
Red
TB3
(24VDC @ 4A)
+
-
DETAIL E
SCALE 2 : 5
Power
Plug
12-22 AWG Black
Wires are Power Limited
For UL applications: wiring limited to
20 ft in conduit located in the same room.
For ULC applications: wiring in
metallic conduit located in the same room
not exceeding 18 m.
NOTE: All high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼”
separation must be maintained with high voltage and non-power limited wiring running in separate conduit
openings from power wiring. Wiring within the cabinet should be routed around the perimeter of the cabinet.
Figure 2
Desigo Fire Safety Modular/Cerberus PRO Modular System Power Connection to Connect X300
firealarmresources.com
A6V11649121_enUS_b
4
J11
Ethernet
Plug
Rear View of
FCM2041-U2/-U3
Operator Interface
(Located in the
Desigo Fire Safety
Modular/Cerberus
PRO Modular
Enclosure
X1P1
Plug
S55842-Z121-A100
Connect X300
Gateway
(Can be mounted
inside the enclosures
P/Ns S54465-C63-A1,
S54339-A8-A1, &
S54339-A9-A1
Ethernet Cable 6 ft. long (User Provided)
Wires are Power Limited
For UL applications: wiring limited to
20 ft. in conduit located in the same room.
For ULC applications: wiring in
metallic conduit located in the same room
not exceeding 18 m.
X2P1 Plug
to Internet
Connection
NOTE: All high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼”
separation must be maintained with high voltage and non-power limited wiring running in separate conduit
openings from power wiring. Wiring within the cabinet should be routed around the perimeter of the cabinet.
Figure 3
Desigo Fire Safety Modular/Cerberus PRO Modular System Ethernet Connection to Gateway
firealarmresources.com
A6V11649121_enUS_b
5
E
{
ENCL-01
Enclosure
S54465-C63-A1
CGAP
Adapter Plate
S54811-B101-A1
Connect X300
Gateway
S55842-Z121-A100
Insert wires
into to 2-POS
Power Plug
(Black Wire to
POS “L+”)
12-22 AWG Red
DETAIL E
SCALE 2 : 5
Power
Plug
12-22 AWG Black
Wires are Power Limited
For UL applications: wiring limited to
20 ft in conduit located in the same room.
For ULC applications: wiring in
metallic conduit located in the same room
not exceeding 18 m.
FCI2016-U1 OR
FCI2017-U1
1
X1001
Figure 4
Desigo and Cerberus PRO Power Connection to Connect X300 Gateway
firealarmresources.com
A6V11649121_enUS_b
6
FCM2018-U2/-U3,
FCM2019-U2/-U3, OR
FCM2035-U2/-U3
X1P1
Plug
S55842-Z121-A100
Connect X300
Gateway
(Can be mounted
inside the enclosures
P/Ns S54465-C63-A1,
S54339-A8-A1, &
S54339-A9-A1
Ethernet Cable 6 ft. long (User Provided)
Wires are Power Limited
For UL applications: wiring limited to
20 ft. in conduit located in the same room.
For ULC applications: wiring in
metallic conduit located in the same room
not exceeding 18 m.
X2P1 Plug
to Internet
Connection
Restricted to
same room with
UL Listed
Switch/Hub.
X5
Figure 5
Desigo and Cerberus PRO Fire Only Panel Ethernet Connection to Connect X300 Gateway
firealarmresources.com
A6V11649121_enUS_b
7
X1P1
Plug
S55842-Z121-A100
Connect X300
Gateway
(Can be mounted
inside the enclosures
P/Ns S54465-C63-A1,
S54339-A8-A1, &
S54339-A9-A1
Ethernet Cable 6 ft. long (User Provided)
Wires are Power Limited
Can be connected to either X301 or X302
on VCA2002-A1 Card Cage.
For UL applications: wiring limited to
20 ft. in conduit located in the same room.
For ULC applications: wiring in
metallic conduit located in the same room
not exceeding 18 m.
X2P1 Plug
to Internet
Connection
Restricted to
same room with
UL Listed
Switch/Hub.
2
X301 X302
3
X201 X202
BACKUP VAC
1:3 1:1
VAC104
VAC103
VAC102
VAC101
VCC-I/0
VCC CPU
X102
LOCAL CAN
MODULE
X303X304 X501 X101
+24 VDC
POWER
4 5 6
7 8 9
1 1 1 1 -
+ -
+
1
VCC LOCAL MONET
1 -
+ -
+1 -
+ -
+
X604 X603 X602 X601
X611X612X613X614
Figure 6
Desigo and Cerberus PRO Fire Voice Panel Ethernet Connection to Connect X300 Gateway
firealarmresources.com
A6V11649121_enUS_b
8
Configuring for the Cerberus PRO FC922/FC924/FV922/FV924 and Desigo
FC2025/FC2050/FV2025/FV2050
Refer to FG2004 Commissioning Guide, Document ID A6V11382550.
Configuring for the Desigo Fire Safety Modular/Cerberus PRO Modular using Zeus
1. Insert a Custom Enclosure.
2. Under this, insert the X300 Gateway.
a. To enable supervision of this gateway, check the property for Connection Supervision.
i. When checked, a Not responding trouble will be reported each time the connection
between the Operator Interface and Connect X300 is lost.
ii. By default, this property is unchecked.
b. To add the gateway to the battery calculations, check the Cloud Battery Backup option.
i. By default, the value is checked.
firealarmresources.com
A6V11649121_enUS_b
9
Cyber security disclaimer
Siemens provides a portfolio of products, solutions, systems and services that
includes security functions that support the secure operation of plants, systems,
machines and networks. In the field of Building Technologies, this includes building
automation and control, fire safety, security management as well as physical
security systems.
In order to protect plants, systems, machines and networks against cyber threats, it
is necessary to implement and continuously maintain a holistic, state-of-the-art
security concept. Siemens’ portfolio only forms one element of such a concept.
You are responsible for preventing unauthorized access to your plants, systems,
machines and networks which should only be connected to an enterprise network
or the internet if and to the extent such a connection is necessary and only when
appropriate security measures (e.g. firewalls and/or network segmentation) are in
place. Additionally, Siemens’ guidance on appropriate security measures should be
taken into account. For additional information, please contact your Siemens sales
representative or visit https://www.siemens.com/global/en/home/company/topicareas/
future-of-manufacturing/industrial-security.html.
Siemens’ portfolio undergoes continuous development to make it more secure.
Siemens strongly recommends that updates are applied as soon as they are
available and that the latest versions are used. Use of versions that are no longer
supported, and failure to apply the latest updates may increase your exposure to
cyber threats. Siemens strongly recommends to comply with security advisories on
the latest security threats, patches and other related measures, published, among
others, under https://www.siemens.com/cert/en/cert-security-advisories.htm.
firealarmresources.com
Document ID A6V11649121_enUS_b P/N A5W00096128
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Siemens Connect X300 4G Dongle Installation guide

Category
Fire protection
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI