BLAUBERG ALB User manual

Category
Split-system air conditioners
Type
User manual

BLAUBERG ALB is a powerful and efficient air heating (cooling) unit designed for a variety of indoor applications, including manufacturing sites, car repair shops, car washes, garages, car showrooms, warehouses, shopping centers, super- and hypermarkets, shops, sport halls, conference halls, poultry and cattle farms, greenhouses and other similar premises.

ALB units are equipped with a high-efficient electric heater and a powerful fan, enabling quick air heating (cooling) in large premises or local heating (cooling) of a working space in hangars or industrial facilities.

The unit is designed for application with the ambient temperature ranging from +1 °C up to +50 °C. The maximum allowable water temperature is 100 °C, the maximum pressure at 100 °C is 1.6 MPa (16 bar).

BLAUBERG ALB is a powerful and efficient air heating (cooling) unit designed for a variety of indoor applications, including manufacturing sites, car repair shops, car washes, garages, car showrooms, warehouses, shopping centers, super- and hypermarkets, shops, sport halls, conference halls, poultry and cattle farms, greenhouses and other similar premises.

ALB units are equipped with a high-efficient electric heater and a powerful fan, enabling quick air heating (cooling) in large premises or local heating (cooling) of a working space in hangars or industrial facilities.

The unit is designed for application with the ambient temperature ranging from +1 °C up to +50 °C. The maximum allowable water temperature is 100 °C, the maximum pressure at 100 °C is 1.6 MPa (16 bar).

AIR HEATING (COOLING) UNIT
EN USER'S MANUAL
ALB-Serie
2
www.blaubergventilatoren.de ALB
CONTENTS
Safety requirements ..................................................................................................................................................................... 3
Purpose ................................................................................................................................................................................................ 5
Delivery set ........................................................................................................................................................................................ 6
Designation key .............................................................................................................................................................................. 6
Technical data .................................................................................................................................................................................. 7
Design and operating principle ........................................................................................................................................... 9
Mounting and set-up .................................................................................................................................................................. 10
Connection to power mains .................................................................................................................................................. 12
Control ................................................................................................................................................................................................. 12
Technical maintenance .............................................................................................................................................................. 13
Troubleshooting ............................................................................................................................................................................. 13
Storage and transportation regulations .......................................................................................................................... 14
Manufacturers warranty ........................................................................................................................................................... 15
Certificate of acceptance .......................................................................................................................................................... 19
Seller information .......................................................................................................................................................................... 19
Installation certificate .................................................................................................................................................................. 19
Warranty card ................................................................................................................................................................................... 19
This users manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the ALB unit and all its
modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to
work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
www.blaubergventilatoren.de
ALB
3
All operations described in this manual must be performed by qualified personnel only, properly
trained and qualified to install, make electrical connections and maintain ventilation units.
Do not attempt to install the product, connect it to the mains, or perform maintenance yourself.
This is unsafe and impossible without special knowledge.
Disconnect the power supply prior to any operations with the unit.
All users manual requirements as well as the provisions of all the applicable local and national
construction, electrical, and technical norms and standards must be observed when installing
and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and
repair operations.
Connection of the unit to power mains is allowed by a qualified electrician with a work permit
for the electric units up to 1000 V after careful reading of the present users manual.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting
installation. The casing internals must be free of any foreign objects that can damage the
impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing may result
in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous
materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline,
insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efficient air flow.
Do not sit on the unit and do not put objects on it.
SAFETY REQUIREMENTS
4
www.blaubergventilatoren.de ALB
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE
The information in this users manual was correct at the time of the documents preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration
of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.
www.blaubergventilatoren.de
ALB
5
PURPOSE
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED
PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE
TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED
PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORISED
ACCESS BY UNATTENDED CHILDREN.
The air heating (cooling) units with a water-to-air heat exchanger are designed for indoor air heating (cooling) and uniform air distribution
with a fan and louvre shutters.
An integrated high-efficient electric heater and a powerful fan enable quick air heating (cooling) in large premises or local heating
(cooling) of a working space in hangars or industrial facilities.
Designed for heating (cooling) of large premises: manufacturing sites, car repair shops, car washes, garages, car showrooms, warehouses,
shopping centers, super- and hypermarkets, shops, sport halls, conference halls, poultry and cattle farms, greenhouses and other similar
premises. The unit design enables quick and easy mounting and reduces total investment costs for heating (cooling) systems.
6
www.blaubergventilatoren.de ALB
DELIVERY SET
DESIGNATION KEY
Name Number
ALB unit 1 pc.
Users manual 1 pc.
Packing box 1 pc.
Drain pipe 1 pc. (ALB 25, ALB 30, ALB 45)
ALB 1 z 9
Heater power [kW]
Material of the casing and component parts
_: painted metal
z: galvanized steel
Modication
_: unit model for heating and cooling
1: unit model for heating only
Unit type
ALB Air heating (cooling) unit
www.blaubergventilatoren.de
ALB
7
TECHNICAL DATA
The unit is designed for application with the ambient temperature ranging from +1 °C up to +50 °C.
The maximum allowable water temperature is 100 °C, the maximum pressure at 100 °C is 1.6 MPa (16 bar).
The unit is designed for operation in cold and moderate climate zones.
A double-pipe system is used to supply water to the heat exchanger.
In summer season cold water is supplied to the heat exchanger, and during the heating period - hot water.
The unit design is regularly improved, so some models may slightly differ from those ones described herein.
Parameters ALB 25, ALB1 25,
ALB1z 25
ALB 30, ALB1 30,
ALB1z 30
ALB 45, ALB1 45,
ALB1z 45
Unit supply voltage, 50 Hz [V] 230 230 230
Fan power [W] 136 191 255
Fan current [A] 0.6 0.85 1.12
RPM [min-1] 1350 1440 1360
Sound pressure level at 3 m distance [dBA] 53 55 58
Maximum heat medium temperature 100 100 100
Ingress protection rating IP44 IP44 IP44
Insulation class F B F
Air blowing range [m] 9 12 16
Technical data for heating mode:
Model
Air ow [m3/h]
Inlet air temperature
[°C]
Temperature dierence
90/70 °C
Temperature dierence
80/60 °C
Temperature dierence
70/50 °C
Temperature dierence
60/40 °C
Power [kW]
Output
temperature [°C]
Water ow [m3/h]
Water pressure
loss [kPa]
Power [kW]
Output
temperature [°C]
Water ow [m3/h]
Water pressure
loss [kPa]
Power [kW]
Output
temperature [°C]
Water ow [m3/h]
Water pressure
loss [kPa]
Power [kW]
Output
temperature [°C]
Water ow [m3/h]
Water pressure
loss [kPa]
ALB 25,
ALB1 25,
ALB1z 25
2200
-15 34.5 26.0 1.51 7.5 30.4 21.2 1.30 6.0 26.0 16.0 1.19 4.6 22.0 11.0 1.01 3.4
-10 32.0 29.0 1.40 6.6 28.3 24.3 1.22 5.3 24.0 19.2 1.12 4.0 20.0 14.0 0.90 2.8
-5 30.0 32.0 1.30 5.8 26.2 27.4 1.19 4.6 22.0 22.0 1.01 3.4 18.0 17.0 0.79 2.3
0 28.0 35.0 1.19 5.2 24.1 30.4 1.12 4.0 20.0 25.0 0.90 2.8 16.0 20.0 0.68 1.8
5 26.2 38.0 1.19 4.5 22.1 33.3 1.01 3.3 18.0 28.0 0.79 2.3 14.0 22.0 0.61 1.4
10 24.2 41.4 1.12 3.9 20.1 36.1 0.94 2.8 15.9 30.6 0.68 1.9 12.0 25.0 0.50 1.0
15 22.1 44.2 1.01 3.3 18.1 38.8 0.90 2.3 13.8 33.0 0.61 1.4 9.0 27.0 0.40 0.7
ALB 30,
ALB1 30,
ALB1z 30
3000
-15 48.4 27.2 2.09 7.4 42.0 22.0 1.91 6.0 36.6 17.0 1.58 4.7 31.0 11.7 1.30 3.5
-10 45.4 30.3 2.02 6.6 39.0 25.2 1.69 5.3 33.7 20.0 1.51 4.0 27.6 14.6 1.19 2.9
-5 42.4 33.4 1.91 5.9 36.7 28.2 1.58 4.6 30.0 22.9 1.40 3.4 24.0 17.4 1.12 2.4
0 39.5 36.4 1.69 5.2 33.8 31.1 1.51 3.9 28.0 25.7 1.19 2.9 21.0 20.0 1.01 1.9
5 36.7 39.4 1.58 4.5 30.9 34.0 1.40 3.4 25.0 28.5 1.12 2.4 19.0 22.7 0.79 1.5
10 33.8 42.1 1.51 3.9 28.1 36.7 1.19 2.8 22.0 31.1 1.01 1.9 16.0 25.2 0.68 1.1
15 31.0 44.9 1.40 3.3 25.3 40.0 1.12 2.3 19.4 33.7 0.90 1.5 13.0 27.5 0.61 0.7
ALB 45,
ALB1 45,
ALB1z 45
3850
-15 63.0 28.4 2.81 11.9 55.6 23.3 2.41 9.7 48.1 18.1 2.09 7.6 40.4 12.8 1.80 5.7
-10 59.2 31.5 2.59 10.6 51.8 26.4 2.30 8.5 44.3 21.1 1.91 6.6 36.7 15.7 1.58 4.8
-5 55.4 34.6 2.41 9.4 48.0 29.3 2.09 7.4 40.6 23.9 1.80 5.6 32.9 18.5 1.40 3.9
0 51.6 37.5 2.30 8.3 44.3 32.2 2.02 6.4 36.9 26.8 1.58 4.7 29.2 21.3 1.30 3.2
5 47.9 40.4 2.09 7.3 40.6 35.0 1.80 5.5 33.2 29.5 1.51 3.9 25.6 23.9 1.12 2.5
10 44.3 43.2 2.02 6.3 37.0 37.8 1.58 4.6 29.6 32.2 1.30 3.2 21.9 26.4 1.01 1.9
15 40.6 45.9 1.80 5.4 33.4 40.4 1.51 3.8 26.0 34.8 1.12 2.5 18.1 28.8 0.79 1.3
8
www.blaubergventilatoren.de ALB
Technical data for cooling mode:
Model Air ow [m3/h]
Intake air
temperature
[°]
Temperature dierence 90/70 °C
Power [kW] Output temperature
[°C] Water ow [m3/h] Water pressure loss
[kPa]
ALB 25 2200
35 9.1 26.0 1.6 7.5
30 5.8 22.5 1.0 6.1
25 3.2 21.0 0.6 2.1
20 2.0 18.0 0.3 0.9
ALB 30 3000
35 11.4 27.0 2.0 11.2
30 7.3 22.9 1.3 5.0
25 3.9 21.1 0.7 1.6
20 2.4 17.7 0.4 0.7
ALB 45 3850
35 18.0 24.9 3.1 31.8
30 10.8 21.7 1.9 12.9
25 7.3 19.0 1.3 6.3
20 3.2 17.4 0.5 1.4
Note: The ALB1 and ALB1z unit models are not designed for cooling as they are not equipped with elements necessary for condensate
removal.
1 – heat exchanger
2 – axial fan with a protecting grille
3 – casing
4 - louvre shutters
5 – terminal box
6 – heat exchanger spigots
ALB
H
4
1
B
5
2
L 1
L
36
К
43
H1
B1
Overall dimensions:
Model Dimensions [mm] Number of pipe rows Weight
[kg]
BB1 HH1 LL1 K
ALB 25 680 785 605 468 360 286 G 3/4" 2 37.0
ALB 30 680 785 655 518 360 286 G 3/4" 2 40.0
ALB 45 780 885 710 570 380 300 G 3/4" 2 50.0
www.blaubergventilatoren.de
ALB
9
ALB 1
2
L1
L
36
К
H1
B1
5
H
4 1
B
Overall dimensions:
Model Dimensions [mm] Number of pipe rows Weight
[kg]
BB1 HH1 LL1 K
ALB1 25, ALB1z 25 630 690 555 468 320 262 G 3/4" 2 28.0
ALB1 30, ALB1z 30 630 690 605 518 355 262 G 3/4" 2 31.0
ALB1 45, ALB1z 45 730 790 655 570 380 285 G 3/4" 2 41.0
DESIGN AND OPERATING PRINCIPLE
The ALB unit consists of four basic components: a water-to-air heat exchanger (1), an axial fan with a protecting grille (2), a polymer
coated steel casing (3), louvre shutters (4).
The water-to-air heat exchanger is made of copper tubing ribbed with aluminium.
The water-to-air heat exchanger is equipped with internally threaded (3/4) copper tubes.
The axial fan located at the unit inlet generates air flow in the water-to-air heat exchanger.
The protecting grille of the fan prevents ingress of foreign objects inside the unit.
The adjustable louvre shutters are located at the unit outlet. Each louvre vane is manually adjustable which makes it easy to create a
required air stream direction. The curved profile of the louvre vanes prevents air flow turbulence and its rising toward upper part of the
room thus keeping warm air within the heated area. The unit operation is based on heat/cool conduction from the hot or cold water to
surface of the copper tubes filled with circulating water. The copper tubes have aluminium fins for extra large heat exchange surface.
The copper tubes transfer heat energy to the aluminium fins and the fins transfer it further to the air flow generated by the fan.
The heated (cooled) air flow is supplied to the premises and directed locally by means of the louvre shutters.
The ALB model is a single-room air heating/cooling system and the ALB1 model is a single-room air heating system.
The unit is suitable both for vertical and horizontal installation.
During unit operation in the cooling mode some condensate may form on the heat exchanging surface and get accumulated in the
unit drain pan.
The ALB 25, ALB 30 and ALB 45 units must be equipped with a drain pipe. Fix the drain pipe to the unit bottom with rivets.
The drain pipe and the rivets are supplied with the unit.
Apply some sealant on the mating surfaces of the pipe and
drain pan mating surfaces. Fix the pipe with fasteners.
The drain pipe opening is
plugged. Remove the plug.
The unit is designed for indoor installation in compliance with applicable hygienic norms and standards.
10
www.blaubergventilatoren.de ALB
MOUNTING AND SETUP
READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.
FAILURE TO PROVIDE MINIMUM DISTANCE TO WALLS OR CEILING WILL IMPAIR THE
UNIT AERODYNAMIC AND THERMAL CHARACTERISTICS AS WELL AS SERVICE LIFE OF
THE UNIT.
Provide free air access to the fan intake vent while installing the unit.
The minimum distance between the wall or ceiling and the ALB unit is 300 mm.
While mounting the unit provide enough access for maintenance or repair work.
The unit is designed for mounting on walls or any other vertical surface as well for ceiling mounting using the fixing brackets.
While connecting the water-to-air heat exchanger to the water mains, disable any loads that can damage the unit or tight connections.
Layout of the heat medium piping must ensure quick detachment for easy servicing and repair operations.
Install a mud filter at the heat medium inlet to the heat exchanger.
Mounting accessories:
Model Mounting angles Bracket Multi-angle bracket
ALB 25 UMP ALB UM ALB 25 UMU ALB 25
ALB 30 UMP ALB UM ALB 30 UMU ALB 30
ALB 45 UMP ALB UM ALB 45 UMU ALB 45
ALB1 25, ALB1z 25 UMP ALB UM ALB1 25 UMU ALB1 25
ALB1 30, ALB1z 30 UMP ALB UM ALB 25* UMU ALB 25
ALB1 45, ALB1z 45 UMP ALB UM ALB 30* UMU ALB 30
*The cross pieces between the UM ALB mounting brackets are not applicable in case of mounting to the ALB1 and ALB1z units.
INSTALLATION OF THE UNIT WITH AN MKAOW MOUNTING SET
The UM ALB mounting bracket is used for ceiling or wall mounting of the unit. Not included in the delivery set, available as a special
accessory.
CEILING MOUNTING WITH UM ALB
min 300 mm
min 300 mm
WALL MOUNTING WITH UM ALB
ALB ALB1, ALB1z
www.blaubergventilatoren.de
ALB
11
INSTALLATION OF THE UNIT WITH AN MKPAOW MOUNTING SET
The UMP ALB mounting set (not included in the delivery set) is used for ceiling mounting of the unit by means of the mounting studs
or chains.
INSTALLATION OF THE UNIT WITH UMP ALB
min 300 mm
Mounting stud
INSTALLATION OF THE UNIT WITH AN UMU ALB MULTIANGLE BRACKET
The UMU ALB mounting multi-angle bracket (not included in the delivery set) is used for ceiling or wall mounting of the unit.
The UMU ALB bracket design enables wall or ceiling installation of the unit at the angle of 30° and 45°.
RIGHT ANGLE MOUNTING WITH
UMU ALB
30° MOUNTING WITH
UMU ALB
45° MOUNTING WITH
UMU ALB
30°
45°
UNIT REACH DISTANCE
Failure to provide the minimum distance of 0.3 mm to walls or ceiling will impair the unit aerodynamic and thermal characteristics as
well as service life of the unit.
Wall mounting
Minimum distance to the wall is 0.3 m.
Mounting height is from 3 to 8 m.
Maximum air blowing range is 16 m.
Ceiling mounting
Minimum distance to the ceiling is 0.3 m.
Mounting height is from 4 to 14 m.
16 m
3-8 m
4-14 m
16 m
12
www.blaubergventilatoren.de ALB
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.
CONTROL
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
AND WILL VOID THE WARRANTY.
The unit is rated for connection to single-phase AC 220-230 V/50 Hz power mains.
The unit must be connected to power mains using durable, insulated and heat-resistant conductors (cables and wires) with minimum
cross section not less than 0.5 mm2.
The given wire cross sections are for reference only.
The cross section selection must account for the maximum permissible wire heating which depends on the wire type, its insulation,
length and installation method (i.e. overhead, in pipes or inside walls).
The unit connections shall be made on the terminal block mounted inside the terminal box in strict accordance with the wiring diagram
and terminal designations.
The external lead-in must be equipped with a circuit breaker with a thermal-magnetic trip built into the stationary wiring to disconnect
all the mains phases.
The QF external circuit breaker location must ensure free access for quick shutdown of the unit.
The circuit breaker tripping is selected based on the electrical characteristics of the unit, listed in the "Technical data" section.
The unit is equipped with asynchronous motors with an external rotor, with integrated thermal protection with automatic restart.
L
N
X1
1
2
3
N
L
QF
PE
~230 V
50 Hz
4
РЕРЕРЕРЕ
WIRING DIAGRAM
Smooth or step fan speed control is performed by means of a thyristor or transformer speed controller.
Reducing the fan speed enables reducing air flow and heating or cooling heat exchange.
The air heating (cooling) unit is operated via the UWT-1E control unit (special accessory).
The control unit has three operation modes and three fan speed stages for the ALB unit.
The control unit is equipped with an on/off switch with a control lamp, cable glands for cable connections and a thermal fuse for
short circuit protection. The control unit is designed for joint operation with the TST-1-300 digital thermostats with a sensor display
(TSTD-1-300 is available with a remote control) or RTS-1-400 with an LCD display (RTSD-1-400 is available with a remote control). The
thermostats are available as special accessories. The thermostat must be installed in a premise that is heated or cooled by the ALB unit.
The thermostat is used for air temperature monitoring and operation mode control.
The thermostat installation place must not be subjected to temperature fluctuations induced by open windows, door and heating
devices. Several air heating (cooling) units installed in the same premise may share one thermostat.
www.blaubergventilatoren.de
ALB
13
TROUBLESHOOTING
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE
OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE
REMOVING THE PROTECTION
TECHNICAL MAINTENANCE
Maintenance means regular preventive measures during operations. The aluminium ribs must be cleaned of dirt and dust once a year
with a wet cloth or a vacuum cleaner. If the internal environment is clean enough, the cleaning may be performed more seldom, as
required. Disconnect the unit from power mains prior to any maintenance operations.
Possible faults and troubleshooting
Problem Possible reasons Troubleshooting
When switching on the unit the fan does
not start.
No power supply.
Make sure the power supply line
is connected correctly, otherwise
troubleshoot a connection error.
The motor is jammed, the impeller blades
are soiled.
Turn the unit off. Troubleshoot the motor
jam and the impeller clogging. Clean the
blades. Restart the unit.
Circuit breaker tripping during the unit
start-up.
High current consumption due to short
circuit in power line. Turn the unit off. Contact the Seller.
Low air flow.
Low set fan speed. Set higher speed.
Control system malfunction. Turn the unit off.
Contact the Seller.
Heater malfunction. Control system malfunction. Turn the unit off.
Contact the Seller.
Noise, vibration.
The impeller is soiled. Clean the impeller.
The fan or casing screw connection is
loose.
Tighten the screw connection of the fans
or the casing against stop.
14
www.blaubergventilatoren.de ALB
STORAGE AND TRANSPORTATION REGULATIONS
Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range
from +5 ˚С to +40 ˚С and relative humidity up to 70 %.
Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing
deformation.
Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
Follow the handling requirements applicable for the particular type of cargo.
The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. The unit must be transported only in the working position.
Avoid sharp blows, scratches, or rough handling during loading and unloading.
Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least
3-4 hours.
www.blaubergventilatoren.de
ALB
15
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby
declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European
Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking
Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance
of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation
through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the
manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults
in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means
of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
routine technical maintenance
unit installation/dismantling
unit setup
To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment
paperwork certifying the purchase. The unit model must comply with the one stated in the users manual. Contact the Seller for warranty
service.
The manufacturer’s warranty does not apply to the following cases:
Users failure to submit the unit with the entire delivery package as stated in the users manual including submission with missing
component parts previously dismounted by the user.
Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user's manual.
Users failure to ensure timely technical maintenance of the unit.
External damage to the unit casing (excluding external modifications as required for installation) and internal components caused
by the user.
Redesign or engineering changes to the unit.
Replacement and use of any assemblies, parts and components not approved by the manufacturer.
Unit misuse.
Violation of the unit installation regulations by the user.
Violation of the unit control regulations by the user.
Unit connection to power mains with a voltage different from the one stated in the user's manual.
Unit breakdown due to voltage surges in power mains.
Discretionary repair of the unit by the user.
Unit repair by any persons without the manufacturers authorization.
Expiration of the unit warranty period.
Violation of the unit transportation regulations by the user.
Violation of the unit storage regulations by the user.
Wrongful actions against the unit committed by third parties.
Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
Missing seals if provided by the users manual.
Failure to submit the users manual with the unit purchase date stamp.
Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND
TROUBLEFREE OPERATION OF THE UNIT
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION
OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE
PURCHASE DATE STAMP
16
www.blaubergventilatoren.de ALB
www.blaubergventilatoren.de
ALB
17
18
www.blaubergventilatoren.de ALB
www.blaubergventilatoren.de
ALB
19
CERTIFICATE OF ACCEPTANCE
Unit Type AIR HEATING (COOLING) UNIT
Model ALB _______
Serial Number
Manufacture Date
Quality Inspector’s
Stamp
SELLER INFORMATION
Seller
Sellers Stamp
Address
Phone Number
E-mail
Purchase Date
This is to certify acceptance of the complete unit delivery with the users manual. The warranty terms are
acknowledged and accepted.
Customer’s Signature
INSTALLATION CERTIFICATE
The ALB _______________________________ unit is installed pursuant to the requirements stated in
the present user's manual.
Installation Stamp
Company name
Address
Phone Number
Installation
Technician’s Full Name
Installation Date: Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction,
electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:
WARRANTY CARD
Unit Type AIR HEATING (COOLING) UNIT
Sellers Stamp
Model ALB _______
Serial Number
Manufacture Date
Purchase Date
Warranty Period
Seller
www.blaubergventilatoren.de
B52EN-05
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

BLAUBERG ALB User manual

Category
Split-system air conditioners
Type
User manual

BLAUBERG ALB is a powerful and efficient air heating (cooling) unit designed for a variety of indoor applications, including manufacturing sites, car repair shops, car washes, garages, car showrooms, warehouses, shopping centers, super- and hypermarkets, shops, sport halls, conference halls, poultry and cattle farms, greenhouses and other similar premises.

ALB units are equipped with a high-efficient electric heater and a powerful fan, enabling quick air heating (cooling) in large premises or local heating (cooling) of a working space in hangars or industrial facilities.

The unit is designed for application with the ambient temperature ranging from +1 °C up to +50 °C. The maximum allowable water temperature is 100 °C, the maximum pressure at 100 °C is 1.6 MPa (16 bar).