Connecting
Note! The maximum load may not exceed 50 VA.
Expansion module
The expansion module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be
installed in an external, enclosed cabinet and connected with a longer modular cable.
• Set the switches on the front of the expansion module to the Shunt position.
• Connect a modular cable between HP CRM Exp.out and HPC EM Exp.in
Connections of expansion module for shunt operation:
Temperature input, T1: Sensor, shunt temperature.
Temperature input, T2: -
Analogue output 0-10 V, AO1: Signal to shunt valve.
Relay, DO1: Signal to circulation pump (no-potential closure, maximum 6A).
Exp.in: Connection from HPC RM.
Exp.out: Connection to possible additional module.
Sensor, shunt temperature
• Connect to T1 and GND
Circulation pump
• Connect to DO1.1 to 24 VAC 2.1.
• Connect DO1.2 to the contactor coil (the relay coil) and further to 24 VAC 2.2.
Shunt valve
• Connect AO1 to the signal input of the pilot valve.
• Connect GND to pilot valve GND. If GND is missing in the pilot valve, connect GND to 24 VAC 2.2 somewhere in
the system. It is most appropriate to jumper terminals 144 and 146 in the controller cabinet.
• Connect the pilot valve terminal G to 24 VAC 2.1.
• Connect the pilot valve terminal G0 to 24 VAC 2.2.