6
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operation parameters (tab.6)
Operation temperature -10ºC...+40ºC
Storage temperature +5ºC...+40ºC
Relative humidity 30%...90%, without condensation
Vibrations during operation
Unacceptable
Impulse waves during operation
Unacceptable
Direct isolation
Unacceptable
Vibrations and impulse waves during transport According to PN-83/T-42106
2. Installation.
2.1 Requirements.
The buffer power-supply shall be mounted by the qualified installer having appropriate (required and
necessary for a given country) permissions and qualifications for connecting (operating) 230V/AC installations and
low-voltage installations. The device shall be mounted in closed rooms, according to the environment class II, of
the normal air humidity (RH=90% max. without condensation) and the temperature within the range from -10°C
to +40°C. The power-supply shall operate in a vertical position so that free and convectional air flow through
ventilating holes of the casing is guaranteed.
Before installation is started, the balance of the power-supply load shall be performed. During the normal
operation, the sum of currents collected by receivers shall not exceed I=4,0A@24Vac.
It is acceptable to
change values of fuses to other than original, if not all outputs of power supply of LB5 block are used and
S=100VA max
is not exceeded. (
Σ4,0A@24Vacmax and current of single 2A/AUX output).
As the power-supply is designed for a continuous operation and is not equipped with a power-switch,
therefore an appropriate overload protection in the power supply circuit shall be guaranteed. Moreover, the user
shall be informed about the method of isolation of the power supply from the power voltage (usually through
assignment and marking of an appropriate fuse in the fuse-box). The electrical system shall be made in accordance
with valid standards and regulations.
2.2 Installation procedure.
1. Before installation is started, the voltage in the 230V power-supply circuit shall be isolated.
2. The power-supply shall be mounted in a selected location and connection cords shall be lead.
3. The power cables (~230Vac) shall be connected to L-N terminals of the power supply. The earth conductor
shall be connected to the terminal marked by the earth symbol . The connection shall be made by means of a
three-core cable (with a yellow and green PE protection wire). The power cables shall be lead to appropriate
terminals of the connection board through bushing.
The circuit of the shock protection shall be performed with a particular care, i.e. the yellow
and green protection wire of the power cable shall be connected from one side to the
terminal marked by the symbol of in the casing of the power-supply. Operation of the
power-supply without the properly made and fully operational circuit of the shock
protection is
UNACCEPTABLE!
It can result in failure of devices and electric shock.
4. Connect the conductors of consumers to the +AU, -AUX terminals of the terminal box on the power-supply unit.
5. If necessary, connect the conductors from the equipment to the technical outputs:
- AW LB5 signalization of fuse failure (LB5 block output)
- TAMPER signalization of power-supply unit opening
6. As there are significant voltage drops at the resistance of power cables of receivers during installation, it is possible to adjust