Gossen MetraWatt SINEAX CAM Operating instructions

Type
Operating instructions
4
Universal
heavy current
measuring unit
SINEAX CAM
156 449-04 09.14
Obligatory safety instructions are marked with the following
symbols in these directions:
Read fi rst, then …
Perfect and safe operation requires that these Safe-
ty Instructions as well as the Operating Instructions
(Nr. 156 481) have been read and understood!
This device should only be handled by staff members
who are familiar with it and authorised to work on electric
facilities.
Tampering with the device voids any warranty!
Scope of supply
SINEAX CAM
1 Safety Instructions
1 Software and documentation CD
1 USB cable
Brief description
The confi gurable SINEAX CAM measuring unit is designed for AC power
distribution systems or industrial facilities. The reliable device determines
the current network condition and the degree of impurity caused by non-
linear consumers through a comprehensive harmonics analysis.
The device is also suited to the acquisition of special input signals with
variable sampling intervals (e.g. full wave controls), altered sine shapes
(e.g. phase-angle controls) or strong distortions.
Technical data
Measuring input
Voltage: 57…400V (L-N), or 100…693V (L-L)
Current: 1…5 A
Rated frequency: 50/60 Hz
Connection mode: One-phase, 3 or 4 wire systems of a
balanced or asymmetrical load, split
phase. 4-quadrant operation
Power supply
Option 1: 100…230 V AC/DC ± 15%
Option 2: 24…60 V DC ± 15%
Input power: ≤ 4…20 VA (depending on I/O inter-
face)
Green LED: Power On indication
Interfaces
Bus connection: RS-485 (Modbus protocol), via plug ter-
minals, max. length 1200 m (4000 ft)
USB connection: USB 2.0, 5-pin Mini-B
Relay
Load capacity: 250 V AC, 2 A, 500 VA or 30 V DC,
2 A, 60 W
Device may only be disposed of in a professional
manner!
I/O interface
Different groups of terminals with defi ned input/output functions are
available depending on the version. These groups are galvanically
isolated from each other.
Analog outputs
2x 0/4…20 mA per group of terminals, galvanically connected or
2x ± 20 mA per group of terminals, galvanically connected
Burden voltage 10 V max.
Burden 0…500 Ω (max. 20 mA)
Analog inputs
2x 0/4…20 mA per group of terminals, galvanically connected
Input resistance < 40 Ω
Digital inputs/outputs
3 per group of terminals, in relation to software confi gurable as passive
inputs or outputs (all the same), according to EN 61131-2
Inputs 24 V DC (Type 3)
Outputs 24 V DC, rated current 50 mA (60 mA max.)
Digital inputs 125 V DC
3 per group of terminals
Inputs 48 / 125 V DC
HV input 110 V / 230 V AC
Voltage range: 0…265 V AC (1.1 x 240 V)
Frequency: 50…60 Hz
Switching limit: 40…80 V AC
Input impedance: 20 … 30 kΩ
Mounting
The device is mounted on a top-hat rail.
Please ensure that the operating temperature limits are
not exceeded when determining the place of mounting
(place of measurement):
– 10 … 55 °C
Snap housing on the top-hat rail (EN 50 022) (see Figure 1).
Figure 1. Mounting on top-hat rail 35 x 15 or 35 x 7.5 mm.
Disassembly
Remove the housing from the mounting rail according to Figure 2.
Figure 2
Camille Bauer Metrawatt Ltd.
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax +41 56 618 21 21
www.camillebauer.com
Safety Instructions
5
Electric connections
Screw connections are used. They are designed for cross sections of
4 mm
2
for single wire leads and 2 x 2.5 mm
2
for multiwire leads.
Ensure under all circumstances that the leads are free
of potential when connecting them!
Please observe, …
… that the data on the type plate must be adhered to!
Analog outputs
R
ext
R
ext
x2 x3 x4x1
x = 4..7
C1+
I/O i:
0-20 mA
C1- C2+ C2-
i = 1..4
Analog inputs
x2 x3 x4x1
x = 4..7
C1+
I/O i: 0-20 mA
C1- C2+ C2-
i = 1..4
+
-
+
-
I I
Digital outputs
R
L1
R
L2
R
L3
x2 x3 x4x1
x = 4..7
C1
I/O i: Digital I/O
C2 C3
+out
-inp
i = 1..4
+
24 VDC
Digital inputs
x2 x3 x4x1
x = 4..7
C1
I/O i: Digital I/O
C2 C3
+out
-inp
i = 1..4
+
24 VDC
HV input 110/230 VAC
72 73 7471
~
I/O 4:
110-230 VAC
~
~
110/230 V
Digital inputs 125 V DC
72 73 7471
C1
I/O 4: Digital I/O
C2 C3
+out
-inp
+
125 VDC
Types of connections
Network /
application
Terminal assignment
Single-phase
AC mains
Connect voltage according to the following table
in case of current measurement via L2 or L3:
Three-wire
three-phase
system
balanced load
I: L1
Connect voltage according to the following table
in case of current measurement via L2 or L3:
Four-wire
three-phase
system
balanced load
I: L1
L1
N
11 31
2
L1
N
kl
KL
211 31
L1
N
v
V
u
U
kl
KL
211 31
L1
L2
L3
5
1
8
2
3
L1
L2
L3
kl
KL
5
1
8
2
3
L1
L2
L3
u
U
v
V
v
V
u
U
k
l
KL
5
1
8
2
3
Current Terminals 2 5 8
transf.
L2 1 3 L2 L3 L1
L3 1 3 L3 L1 L2
L1
N
11 31
2
L2
L3
L1
N
kl
KL
211 31
L2
L3
L1
v
V
u
U
kl
KL
211 31
N
L2
L3
Current Terminals 2 11
transf.
L2 1 3 L2 N
L3 1 3 L3 N
A marked and easily accessible switch for turning off the power
supply has to be arranged in the vicinity of the device.
In case of a supply of direct current > 125 V DC, an external fuse
has to be provided in the power supply circuit.
Otherwise, the national provisions (e.g. in Germany VDE 0100 “Con-
ditions concerning the erection of heavy current facilities with rated
voltages below 1000 V”) have to be observed in the installation and
material selection of electric lines!
21 22 23
Rel 1
31 32 33
Rel 2
When the device is
switched off, the status of
the relay contact is not
defined. Dangerous
voltages may occur.
Link
Re
2
1
3
4
2
1
3
258
11134
6
7 9 10 12
13 14
71 72
73
74
42 43 44 51 52 53 54 61 62
63
6441
USB
23 31
333221 22
+A –B
GND
+A –B
GND
V+
Modbus Subbus
USB I/O 1 I/O 2 I/O 3 I/O 4
Rel 1 Rel 2
klklkl kl
I
1
I
2
I
3
I
N
U
1
U
2
U
3
N
Power supply
Current inputs for Rogowski coils:
See operating instructions on CD
*
*
6
Network /
application
Terminal assignment
Three-wire
three-phase
system
asymmetrical
load
Three-wire
three-phase
system
asymmetrical
load
Aron
measuring
circuit
Four-wire
three-phase
system
asymmetrical
load
3 single-pole isolated voltage transformers in the
high-voltage system
3 single-pole isolated voltage transformers in the
high-voltage system
L1
L2
L3
5
8
2
1
3
4 6
7
9
L1
L2
L3
kl
KL
l
KL
kl
KL
5
8
2
1
3
4 6
7
9
L1
L2
L3
kl
KL
kl
KL
kl
KL
xxx
uuu
X
XX
UUU
5
8
2
1
3
4 6
7
9
L1
L2
L3
5
1
8
2
3
7
9
L1
L2
L3
kl
KL
kl
KL
5
1
8
2
3
7
9
L1
L2
L3
kl
KL
kl
KL
xxx
uuu
X
XX
UUU
5
1
8
2
3
7
9
L1
L2
L3
u
U
v
V
v
V
u
U
kl
KL
kl
KL
5
1
8
2
3
7
9
L1
L2
L3
N
11
1
3
4 6
7
9 10 12
L1
L2
L3
kl
KL
kl
KL
kl
KL
N
5
11
8
2
1
3
4 6
7
9 10 12
kl
KL
L1
L2
L3
kl
KL
kl
KL
kl
KL
N
xxx
uuu
X
XX
UUU
5
11
8
2
1
3
4 6
7
9
10 12
kl
KL
5
8
2
Network /
application
Terminal assignment
Four-wire
three-phase
system
asymmetrical
load
Open Y
circuit
Split phase
(“Two-phase
network”)
asymmetrical
load
2 single-pole isolated voltage transformers in
the high-voltage system
L1
L2
L3
N
11
1
3
4 6
7
9 10 12
8
2
L1
L2
L3
kl
KL
kl
KL
kl
KL
N
11
8
2
1
3
4 6
7
9 10 12
kl
KL
L1
L2
N
5
11
2
1
3
4 6
L1
L2
L3
k
l
K
L
k
l
KL
k
l
KL
xx
uu
X
U
2
4
3
1
5
6
7 8
9
10
X
U
L
N
11
12
k
l
KL
L1
L2
N
5
11
2
1
3
4 6
kl
KL
kl
KL
10 12
kl
KL
Dimensional sketch
SINEAX CAM in mounting rail housing snapped on top-hat rail
(35 x 15 mm or 35 x 7.5 mm). Terminals partly pluggable.
Link
Re
2
1
3
4
2
1
3
258
11134
6
7 9 10 12
13 14
71 72
73
74
42 43 44 51 52 53 54 61 62
63
6441
USB
23 31
333221 22
186 63
98
90
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Gossen MetraWatt SINEAX CAM Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI