The QIF-2000 Interface module comes already mounted onto a CH-559 Plate. The CH-559 mounts onto the QBC-
5000B battery charger cover located above the amplifiers in the audio cabinet of the QX-5000 Audio system. The
QBC-5000B must be removed and the QIF-2000, and its plate is mounted onto the QBC-5000B with four #4 screws
behind the QBC-5000B cover. The whole assembly is then mounted back into the audio cabinet over the battery
charger.
Figure 1: Mounting QIF-2000 Interface Module
The QIF-2000 Interface module is used for complex mapping. Inputs 1 through 16 may be programmed via fire
alarm relays to activate different zones with an alert or evacuation tone. The mapping is configured at our factory.
Figure 2: QIF-2000 Interface Wiring Diagram (if using a QIF-1000 see Figure 3)
TOP VIEW
FRONT VIEW of CH-559 PLATE
BACK OF
PLATE
FRONT OF
PLATE
12 VDC BATTERY
12 VDC BATTERY
INLINE FUSE
- BATTERY +
Orange-Yellow-Orange
(MUST BE IN CORRECT ORDER)
XFORMER
SCREW
TERMS
Black
120 VAC INPUT
LIVE / NEUTRAL / GROUND
LUG
IN OUT
SCREW
TERMS
Red
QBC-5000B
BATTERY
CHARGER
CONNECTORS FOR MULTIPLE
QMB-5000B MOTHERBOARDS
SLOT #1
CONNECTOR FOR
QIF-5000B INTERFACE
MODULE
SLOTS #2 - #8
CONNECTORS FOR
QAA- STYLE AMPLIFIERS
CONNECTOR FOR QBC-5000B
BATTERY CHARGER
QPS-5000
POWER SUPPLY
QIF-2000
J7
J8
J6
J5
V+OUT
V+IN
IN 1
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
IN 8
IN 9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
QIF-2000
L R
JP1
5-WIRE HARNESS TO
QIF-5000 J11
MD-702 CABLE
NORMALLY OPEN CONTACTS
FROM FIRE ALARM
CONFIGURABLE RELAYS ON
THE FA-1000 OR FX-2000
(MUST BE CLOSE CONDUIT)
JP2
J8 NOT USED UNLESS MULTIPLE QIF-2000 INTERFACE
MODULES ARE USED AND THEN THE MD-758 CABLE IS
CONNECTED FROM HERE TO J7 OF THE NEXT QIF-2000
PUT JUMPER JP1 ON
THE LEFT TWO PINS
TO QIF-5000B
J2-8
TO MASTER PAGING
QMP-5xxx, V+
F1 FUSE 0.5A
F2 0.65A PTC
F1 F2
6 PIN MOLEX
INPUTS
MOUNTING HOLES (4)
EN-OUT
CC -
CC +
RM-1008A
CLOSE NIPPLE CONNECTED BETWEEN QIF-2000 18AWG
AND THE FIRE ALARM PANEL