Mircom LT-869 QIF-2000 Installation guide

Type
Installation guide
QIF-2000
Emergency Voice Alarm System Interface Board
LT-869 Rev. 3
January 2010
Installation Instructions
The QIF-2000 Interface module comes already mounted onto a CH-559 Plate. The CH-559 mounts onto the QBC-
5000B battery charger cover located above the amplifiers in the audio cabinet of the QX-5000 Audio system. The
QBC-5000B must be removed and the QIF-2000, and its plate is mounted onto the QBC-5000B with four #4 screws
behind the QBC-5000B cover. The whole assembly is then mounted back into the audio cabinet over the battery
charger.
Figure 1: Mounting QIF-2000 Interface Module
The QIF-2000 Interface module is used for complex mapping. Inputs 1 through 16 may be programmed via fire
alarm relays to activate different zones with an alert or evacuation tone. The mapping is configured at our factory.
Figure 2: QIF-2000 Interface Wiring Diagram (if using a QIF-1000 see Figure 3)
TOP VIEW
FRONT VIEW of CH-559 PLATE
BACK OF
PLATE
FRONT OF
PLATE
12 VDC BATTERY
12 VDC BATTERY
INLINE FUSE
- BATTERY +
Orange-Yellow-Orange
(MUST BE IN CORRECT ORDER)
XFORMER
SCREW
TERMS
Black
120 VAC INPUT
LIVE / NEUTRAL / GROUND
LUG
IN OUT
SCREW
TERMS
Red
QBC-5000B
BATTERY
CHARGER
CONNECTORS FOR MULTIPLE
QMB-5000B MOTHERBOARDS
SLOT #1
CONNECTOR FOR
QIF-5000B INTERFACE
MODULE
SLOTS #2 - #8
CONNECTORS FOR
QAA- STYLE AMPLIFIERS
CONNECTOR FOR QBC-5000B
BATTERY CHARGER
QPS-5000
POWER SUPPLY
QIF-2000
J7
J8
J6
J5
V+OUT
V+IN
IN 1
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
IN 8
IN 9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
QIF-2000
L R
JP1
5-WIRE HARNESS TO
QIF-5000 J11
MD-702 CABLE
NORMALLY OPEN CONTACTS
FROM FIRE ALARM
CONFIGURABLE RELAYS ON
THE FA-1000 OR FX-2000
(MUST BE CLOSE CONDUIT)
JP2
J8 NOT USED UNLESS MULTIPLE QIF-2000 INTERFACE
MODULES ARE USED AND THEN THE MD-758 CABLE IS
CONNECTED FROM HERE TO J7 OF THE NEXT QIF-2000
PUT JUMPER JP1 ON
THE LEFT TWO PINS
TO QIF-5000B
J2-8
TO MASTER PAGING
QMP-5xxx, V+
F1 FUSE 0.5A
F2 0.65A PTC
F1 F2
6 PIN MOLEX
INPUTS
MOUNTING HOLES (4)
EN-OUT
CC -
CC +
RM-1008A
CLOSE NIPPLE CONNECTED BETWEEN QIF-2000 18AWG
AND THE FIRE ALARM PANEL
Figure 3: Wiring Diagram When Using A QIF-1000 And QIF-2000 With The QX-5000
Note: If the fire alarm panel is not nearby (beyond 24 ft. from the QX-5000), the fire alarm panel must be
addressable, FX-2000 and the use of an addressable relay module CR-6 must be used for the QIF-2000
Interface module.
V+
V+
AOUT+
AOUT-
AOUTS
AIN+
AIN-
AINS
AIN+
AIN-
AINS
AUDIO1
AUDIO2
SHIELD
AUDIO1
AUDIO2
SHIELD
RS-485 +
RS-485 -
SHIELD
RS-485 +
RS-485 -
SHIELD
J1
J2
J11
J11
J1-1
J1-1
J1-2
J1-2
J1-5
J1-5
J1-3
J1-3
J1-4
J1-4
J2-8
J2-8
5 wire harness
QIF-1000 V+
QIF-5000B J2-8
Mic -
Mic -
Mic +
Mic +
Shield
Shield
J1-1
J1-1
J1-2
J1-2
J1-3
J1-3
J1-4
J1-4
J1-5
J1-5
J1-5
J1-5
J2-1
J2-1
J2-2
J2-2
PTT+
PTT+
PTT-
PTT-
MD-702
MD-702
J7
J8
T
U
O-
N
E
-
C
C
+C
C
MD-702
MD-702
SEL0
Removed
JP2
OUT
OUT
+V
IN
IN+V
RM-1008A Common
From QMP-5xxx
From QMP-5xxx
From QMP-5xxx V+
#1
#1
QIF-5000B #1
QIF-1000
QIF-2000
QIF-2000 V+ OUT
AUDIO FROM LOCAL QMP
AUDIO FROM OTHER QMP
QIF-1000 #1
ID=1
DIP SW: ALL ON
(MASTER)
JW1 Installed
JW2, 3 removed
MIC OUT +
MIC OUT -
SHIELD
NOTE: When using multiple
QIF-2000s refer to Figure 4
and note that JP2 is not removed
from additional QIF-2000s
Figure 4: Multiple QIF-2000 Wiring Diagram
V
+
O
U
T
V
+
I
N
TO V+ OF THE QMP-TO V+ OF THE QMP-
5100B/5101B OR 5100B/5101B OR
QIF-1000 if used.QIF-1000 if used.
B
B
V
+
O
U
T
V
+
I
N
V
+
O
U
T
V
+
I
N
V
+
O
U
T
V
+
I
N
V
+
O
U
T
V
+
I
N
V
+
O
U
T
V
+
I
N
V
+
O
U
T
V
+
I
N
V
+
O
U
T
V
+
I
N
NOTE: MULTIPLE QIF-2000s ARE WIRED AS SHOWN HERE WITH A MAXIMUM OF EIGHT
QIF-2000s PER QX-5000 SYSTEM. FOR SUPERVISION PURPOSES THE 16th
INPUT OF THE LAST UNIT (UNIT 8) MUST BE PERMANENTLY CONNECTED TO VCC.
IF THE QIF-2000 UNIT 1 IS CONNECTED TO A QIF-1000, THEN REMOVE JUMPER JP2
ON THE QIF-2000 UNIT 1 (REFER TO FIGURE 2 FOR THE LOCATION OF JP2).
DO NOT REMOVE JP2 ON UNITS 2 TO 8.
Notes
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113
© Mircom 2010
Printed in Canada
Subject to change without prior notice
www.mircom.com
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Tel: 1-888-660-4655 Fax: 1-888-660-4113