  • Hello! I am an AI chatbot trained to assist you with the 3M Cold Shrink QT-II Outdoor Termination Kit 5649, Tape Shielding, 35 kV, 1.80-2.30 in (46-58 mm) Cable Insul. O.D., 1/kit Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Quick Term II
Silicone Rubber Termination Kit, up to 35 kV
Instruction Sheet
IEEE Std. No. 48, 1975
Class 1 Termination
35 kV Class
Kit Contents:
3 Molded silicone rubber terminations
3 Packets of silicone grease
3 Strip of Scotch Brand 70 Silicone Rubber Tape
6 Strips of Scotch Brand Vinyl Mastic
1 Illustrated Instruction Sheet
Each kit contains enough materials to complete three terminations.
Technical Information:
For use on up to 35 kV Tape or Ribbon Shielded Cables
Class 1, IEEE 48
Conductor Size Range:
15 kV: 1500 -2000 kcmil
25/28 kV: 1250 - 1750 kcmil
35 kV: 1000 - 1500 kcmil
Jacket O.D. Range:
2.10- 2.75(53,3 - 70,0 mm)
Silicone Rubber Termination Kits
for use on
Shielded Cables
35 kV Class
5649
Number of Pages: 3
Issue Date: 5/1/98
Scale: Not to Scale
Issue:
78-8124-4058-0
Terminal
Lug
Scotch70
Tape
Top Seal
Skirted
Termination
Molded
Ribs
A. Prepare Cable
1. Train cable into position. Field determine exposed conductor length for terminal lug installation.
2. Remove cable jacket, tape shield, and semi-con layer as dimensioned (Figure 1).
NOTE: If cable has a tape wrapped semi-con layer, it is recommended that two lapped layers of
Scotch13 Semi-conductive Tape be applied over the cable semi-con end to provide a straight
edge at the cable semi-con end and to hold the cable shield in place.
3. Attach a shield ground braid to the cable metallic tape shield per Utility instruction. At a point ¾from
the cable jacket end, install a 1 inch wide solder block in the ground braid (Figure 2).
4. Install black sealing mastic strip (contained in kit) around the shield ground braid at the solder block
(Figure 3). NOTE: Stretch the mastic slightly to remove the paper liner. Discard excess.
5. Band the ground braid tightly to the cable jacket with vinyl tape. Completely cover the mastic seal area
(Figure 3).
6. Remove cable insulation from end of cable for length previously determined for lug (Figure 3).
7. CLEAN CABLE USING STANDARD PRACTICE.
a. Wipe the cable insulation with an approved solvent such as that found in the ScotchA-2 Cable
Prep Kit. Do not allow solvent to touch semi-con!
b. If abrasive must be used:
1) use on insulation only. DO NOT USE ON SEMI-CON MATERIAL.
2) Use only 120 grit aluminum oxide such as in A-2 Cable Prep Kit or ScotchA-3 Electricians
Abrasive Roll.
3) be careful not to reduce the cable insulation diameter below that allowed by the kit.
Figure 1
Figure 2
Figure 3
Cable
Jacket
Tape Shield
Semi-Con Insulation Shield
Insulation
14-½
15-½
16-½
Depth of
Terminal Lug
Shield Braid
Solder Block
¾
Sealing Mastic
Conductor
Vinyl Tape
- 2 -
B. Install Lug or Connector
1. These units were designed to fit over common lugs. If lug being used will not fit through the core of the
termination, slide termination on cable before installing lug. (DO NOT REMOVE CORE AT THIS TIME).
2. Install lug or connector. Crimp according to manufacturers directions.
3. REMOVE EXCESS CONTACT AID AND SHARP CRIMP FLASH.
C. Install Termination
1. Cover the edge of the semi-conducting material with a liberal coating of silicone grease (Figure 4).
NOTE: ON THIS PRODUCT THE SILICONE GREASE DOES NOT SERVE AS A LUBRICANT. IT
MUST BE USED TO FILL THE STEP AT THE SEMI-CON CUTOFF. Spread excess silicone grease
over entire exposed primary insulation.
2. Place a marker tape 3-½back from the end of the semi-con material (Figure 4).
3. Slide the termination body onto the cable. Align the rubber base of the unit with the previously applied
marker tape.
4. Remove termination core by unwinding counter-clockwise starting with the loose core end. Make sure
the termination body is butted up to the edge of the marker tape (Figure 5).
5. Seal between the lug and insulator by over-wrapping insulator end and lug portion using gray Scotch
70 Silicone Rubber Electrical Tape (contained in kit) (See Main Illustration, page 1).
Figure 4
Figure 5
Important Notice
All statements, technical information and recommendations related to
the Sellers products are based on information believed to be reliable,
but the accuracy or completeness thereof is not guaranteed. Before
utilizing the product, the user should determine the suitability of the
product for its intended use. The user assumes all risks and liability
whatsoever in connection with such use.
Any statements or recommendations of the Seller which are not contained in
the Sellers current publications shall have no force or effect unless
contained in an agreement signed by an authorized officer of the
Seller. The statements contained herein are made in lieu of all
warranties expressed or implied, including but not limited to the
implied warranties of merchantability and fitness for a particular
purpose which warranties are hereby expressly disclaimed.
SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER
PERSON UNDER ANY LEGAL THEORY INCLUDING BUT NOT
LIMITED TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY
OR FOR ANY DIRECT OR CONSEQUENTIAL DAMAGES SUSTAINED
OR INCURRED BY REASON OF THE USE OF ANY OF THE
SELLERS PRODUCTS THAT WERE DEFECTIVE.