aci AIM1 Installation & Operation Instructions

Type
Installation & Operation Instructions

This manual is also suitable for

The aci Interface Series AIM1 is an optically isolated analog signal conditioner that converts and isolates input signals (voltage or current) to corresponding output signals. It offers a 1:1 input-to-output ratio with linear, proportional outputs. The AIM1 supports input spans of 0 to 5 VDC, 0 to 10 VDC, or 0 to 20 mA and can provide the same ranges as outputs. It features onboard isolation transformers for power and output, ensuring signal integrity and reducing electrical noise. The device requires an external 24 VAC isolation transformer with a floating secondary for power.

The aci Interface Series AIM1 is an optically isolated analog signal conditioner that converts and isolates input signals (voltage or current) to corresponding output signals. It offers a 1:1 input-to-output ratio with linear, proportional outputs. The AIM1 supports input spans of 0 to 5 VDC, 0 to 10 VDC, or 0 to 20 mA and can provide the same ranges as outputs. It features onboard isolation transformers for power and output, ensuring signal integrity and reducing electrical noise. The device requires an external 24 VAC isolation transformer with a floating secondary for power.

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
Version: 10.0
I0000468
FIGURE 1: DIMENSIONS
INTERFACE SERIES
Installation & Operation Instructions
AIM1
Phone: 1-888-967-5224
Website: workaci.com
GENERAL INFORMATION
The AIM1 optically isolates an analog (voltage or
current) input signal from its corresponding
output signal. The factory calibrated output is
linear and proportional (1:1 ratio) to the input
signal. The AIM1 will accept a 0 to 5 VDC, 0 to 10
VDC, or 0 to 20 mA input span and output any one
of those same ranges. It requires one external 24
VAC isolation transformer with oating secondary
for power and has an onboard 24 VAC isolation
transformer to supply the isolated output.
MOUNTING INSTRUCTIONS
Ground yourself to discharge static electricity
before touching any electronic equipment, as
some components are static sensitive. The
interface device can be mounted in any
position. If circuit board slides out of snap
track, a non-conductive stop” may be
required. Use only ngers to remove board
from snap track. Slide out of snap track or
push up against side of snap track and lift that
side of the circuit board to remove. Do not
ex board. Do not use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
When using a shielded cable, ground the shield only at the controller end. Grounding both ends
can cause a ground loop.
This device needs to have its own Isolated Transformer. This transformer cannot be
connected/or shared with any other device. It is recommended you use an isolated UL-listed class
2 transformer.
• All wiring must comply with all local and National Electric Codes.
FUNCTION SELECTIONS
STEP 1) INPUT TYPE
Set jumper block J1 for 0 – 5 Volts, 0 – 10 Volts, or 0 – 20 milliamps input signal. See Figure 3 (p. 2) for
details.
STEP 2) OUTPUT TYPE
Set jumper block J2 and J3 for 0 -5 Volts, 0 – 10 Volts, or 0 – 20 milliamps output signal. See Figure 3 (p.
2) for details.
3.42” (86.99mm)
3.25”
(82.55mm)
0.70”
(17.78mm)
3.25” (82.55mm)
3.88”
(98.55mm)
FIGURE 2: WIRING
FIGURE 3: JUMPER SETTINGS
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
Version: 10.0
I0000468
L2
J2
J3
J1
L1
2ND POWER
REWOP IRP
E5 10
IE
10V
5V
20mA
AIM1
Label Location
24VAC
I1
I2
I3 O1
O2
O3
T1
J1
10V
5V
20mA
J1
10V
5V
20mA
J1
10V
5V
20mA
J2
J3
E5 10
IE
J2
J3
E5 10
IE
J2
J3
E5 10
IE
0 to 5 Volts
0 to 5 Volts
0 to 10 Volts
0 to 20 mA
0 to 10 Volts
0 to 20 mA
Input Jumper Settings
Output Jumper Settings
(Source)
Factory Set -
DO NOT ADJUST
Factory Set -
DO NOT ADJUST
L1 LED Indicates
24VAC Power
to board
Analog Input Common
Source Analog
Input Signal
(+)
(-)
(-)
(+)
Analog Ouput Common
Source Analog
Ouput Signal
(-)
(+)
24VAC
I1
I2
I3
Connect I1 and I2
Loop
Powered
Sensor
(+)
(-)
(-)
(+)
24VAC
Figure C
J1
10V
5V
20mA
J1 must be in
20mA position
4-20mA
Current Input
24VDC Out
(20mA Load Max.)
Input from a 2-Wire Current Loop Powered Sensor
Move shunt J3 to "E" position
Sink output will not work
in "I" position.
Input
to
Controller
(-)
(+)
Figure D
4-20mA
(Modulates)
Excitation Voltage
Current Sink Output
L2 LED Indicates
Power Output
O1
O2
O3
J2
J3
E5 10
IE
24 VAC
Power Supply
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 10.0
I0000468
Figure A
Figure B
Calibration and Checkout
The AIM1 is factory calibrated as follows, unless otherwise specied: 0 – 5 Volts Input Signal 1:1 Input to
Output Signal Ratio, 0 -5 Volts Output Signal.
STEP 3) WIRING CONNECTIONS (for “source” input and output)
With the power OFF connect a 24 VAC power supply to the 24VAC terminals of the AIM1.
For inputs from powered current devices, and voltage input signals, connect signal common (-) to the I3
signal input terminal of the AIM1, and the signal positive (+) to the I2 signal input terminal of the AIM1.
For 2-Wire current inputs to AIM1 requiring power see Figure C on page 1 for hook-up details.
Connect the output signal common (-) terminal O3 and the output signal positive terminal O2 to their
respective terminals on the controlled device.
For current “sink” output from AIM1, see Figure D on page 1 for hook-up details.
STEP 4) POWER UP
Turn on the 24VAC power supply. Both Primary Power (PRI POWER) and Secondary Power (2ND POWER)
LED indicators on the AIM1 will light.
STEP 5) OPERATION
The AIM1 will now accept an input signal and produce an isolated and proportional output signal.
(Example, a 5.0 volt input signal will produce a 5.0 (± 0.05 volts) volt DC output signal.)
PRODUCT SPECIFICATIONS
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 10.0
I0000468
WARRANTY
The AIM1 Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S SENSORS &
TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
24 VAC (+/- 10%), 50/60 Hz
100 mA maximum
0 to 5 VDC @ 20,000, 0 to 10 VDC @ 20,000
0-20 mA @ 250
0 to 5 VDC @ 5,000, 0 to 10 VDC @ 5,000
0-20 mA (Source or Sink) @ 500 (Maximum Load Resistacne)
+/- 1%
+/- 2%
+/- 1%
+/- 1%
45° Captive screw Terminal Blocks
12 (3.31 mm) to 22 AWG (0.33 mm)
0.5 Nm (Minimum); 0.6 Nm (Maximum)
35 to 120°F (1.7 to 48.9°C)
10 to 95% non-condensing
-20 to 150°F (-28.9 to 65.5°C)
NON-SPECIFIC INFORMATION
Supply Voltage:
Supply Current:
Input Voltage Signal Range (@
Impedance):
Input Current Signal Range (@
Impedance):
Output Voltage Signal Range (@
Impedance):
Output Current Signal Range (@
Impedance):
Voltage Mode Accuracy:
Current Sink Mode Accuracy:
Current Source Mode Accuracy:
Linearity:
Connections:
Wire Size:
Terminal Block Torque Rating:
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

aci AIM1 Installation & Operation Instructions

Type
Installation & Operation Instructions
This manual is also suitable for

The aci Interface Series AIM1 is an optically isolated analog signal conditioner that converts and isolates input signals (voltage or current) to corresponding output signals. It offers a 1:1 input-to-output ratio with linear, proportional outputs. The AIM1 supports input spans of 0 to 5 VDC, 0 to 10 VDC, or 0 to 20 mA and can provide the same ranges as outputs. It features onboard isolation transformers for power and output, ensuring signal integrity and reducing electrical noise. The device requires an external 24 VAC isolation transformer with a floating secondary for power.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI