Grundfos AEF Installation And Operating Instructions Manual

Type
Installation And Operating Instructions Manual
Fire AEF - electric and diesel driven
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
English (GB)
2
English (GB) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
1.1 Warning description
Safety instructions placed directly on the fire pump set:
1. Symbols used in this document
2
1.1 Warning description
2
2. Applications
3
3. Delivery, transport, storage
3
3.1 Delivery
3
3.2 Transport
3
3.3 Storage
3
4. Product description
4
4.1 Fire pump set
4
4.2 Pump
4
4.3 Motor
4
4.4 Controller
7
4.5 Nameplate
8
5. Operating conditions
8
5.1 Minimum inlet pressure
8
5.2 Maximum inlet pressure
8
5.3 Minimum flow rate
8
5.4 Pumped liquids
8
5.5 Water temperature
8
5.6 Pump temperature
8
5.7 Pump speed
8
5.8 Maximum operating pressure
9
5.9 Ambient temperature
9
5.10 Relative air humidity
9
5.11 Effect of ambient temperature and altitude on electric
motor output
9
5.12 Effect of ambient temperature and altitude on diesel
engine output
9
6. Installation
10
6.1 Installation site
10
6.2 Foundation
10
6.3 Levelling
11
6.4 Pipework
11
6.5 Alignment
12
6.6 Air supply
18
6.7 Exhaust system
18
6.8 Separate control cabinet
18
7. Electrical connection
19
7.1 Checking the direction of rotation on electric units
19
8. Maintenance
19
8.1 Maintenance intervals
19
9. Service, spare parts and accessories
19
10. Warranty
19
11. Further documentation
19
12. Disposal
19
Warning
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
Warning
If these safety instructions are not observed,
it may result in personal injury.
Caution
If these safety instructions are not observed,
it may result in malfunction or damage to the
equipment.
Note
Notes or instructions that make the job easier
and ensure safe operation.
Warning
Hazardous voltages are present in
this enclosure. Improper use or failure
to take precautions can cause serious
injury, electric shock and (or) damage
to the equipment.
Disconnect all supply sources
(including any foreign circuits) before
working on controller, motor or pump.
Only qualified staff must work on or
around this equipment.
Warning
The mains terminals are still live when
the main switch is in position "OFF".
Warning
Phase-sensitive equipment.
Connect in ABC order.
Warning
The enclosure class and withstand
rating are applicable only if all door
locks are in closed position.
The ambient temperature must be 5 to
50 °C.
Warning
If an overload or a fault current
interruption occurs, check the circuits
to determine the cause of the
interruption. If a fault condition exists,
examine the current-carrying
components and replace them if
damaged. Replace the integrated
current sensors to reduce the risk of
fire or electric shock.
To maintain overcurrent, short-circuit
and earth-fault protection and to
reduce the risk of fire or electric
shock, follow the manufacturer's
instructions for selection of overload
and short-circuit protection.
Lifting points for the entire fire pump
set.
Hazadous voltages are present
inside this enclosure. Serious
injury, electrocution and/or
equipment damage will result of
improper application or if
precaution is not used.
Disconnect all supply sources
(including any foreign circuits)
before working om controller,
motor(s) or pump(s).
Only qualified personnel should
work on or around this
equipment.
LINE TERMINALS ALIVE
WHEN MAIN SWITCH
IS IN “OFF” POSITION
DANGER
PHASE SENSITIVE EQUIPMENT
CONNECT IN ABC ORDER
WARNING
ENCLOSURE AND WITH STAND RATING
APPLICABLE ONLY IF ALL DOORLOCKS
ARE IN A CLOSED POSITION.
CONTROLLER MUST BE INSTALLED IN
AN ENVIROMENT WHERE AMBIENT
TEMPERAURE IS BETWEEN 41°F(5° V)
AND 122°F (50°C)
WARNING
WARNING
IF AN OVERLOAD OR A FAULT CURRENT
INTERRUPTION OCCURS, CIRCUITS MUST BE
CHECKED TO DETERMINE THE CAUSE OF THE
INTERRUPTION. IF A FAULT CONDITION EXISTS,
THE CURREN-CARRYING COMPONENTS
SHOULD BE EXAMINED AND REPLACED IF
DAMAGED, AND THE INTEFRAL CURRENT
SENSORS MUST BE REPLACED TO REDUCE
THE RISK OF FIRE OR ELECTRICAL SHOCK.
TO MAINTAIN OVERCURRENT, SHORT-CIRCUIT,
AND GROUND-FAULT PROTECTION, THE
MANUFACTURER’S INSTRUCTIONS FOR THE
SELECTION OF OVERLOAD AND SHORT-
CIRCUIT PROTECTION MUST BE FOLLOWED TO
REDUCE THE RISK OF FIRE OR
ELECTRIC SHOCK.
CB FXD63A250 / CFD63A250
SPECIFICALLY SET FOR THIS INSTALLATION
L=1100
5=1900
2=1300
6=2100
3=1500
7=2300
4=1700
h=2500
English (GB)
3
2. Applications
The Peerless Fire AEF pump sets are designed for fire systems
for supplying water to hose reels, fire hydrants and sprinkler
systems.
The Peerless Fire AEF pump sets with electric motor or diesel
engine must not be used for ordinary pumping of liquids or
common pressure boosting in daily work. The pump sets must
only be used for firefighting.
The pump controller must not be used as a junction box for
supplying other equipment.
3. Delivery, transport, storage
3.1 Delivery
The fire pump set is delivered from factory in an open wooden
box or wooden and cardboard box which is specifically designed
for transport by fork-lift truck or similar device.
3.2 Transport
For lifting the entire fire pump set, use the lifting holes of the base
frame. When lifting, the lifting point must always be above the
centre of gravity of the fire pump set. See fig. 1.
Fig. 1 Correct lifting of fire pump set
3.3 Storage
To prevent water, dust, etc. from entering the pump, all openings
must be covered until all pipes are connected. Apply a suitable
antirust agent on all machined, non-coated surfaces.
The antirust agent must meet these requirements:
It must not attack rubber parts.
It must be easy to remove.
It must be applied according to the instructions of the
manufacturer.
Protect the pump against corrosion and damage if the pump is to
be stored for more than six months before startup:
1. Remove the stuffing box packing.
2. Spray the interior part of the pump housing and the stuffing
box with a water-soluble type of antirust agent.
3. If the pump has not been connected to the pipework, cover
the pump suction and discharge flanges with full natural
rubber gasket material, and blank off these openings with
metal blanking flanges. Use at least four bolts for fastening.
4. Cover the opening of the stuffing box with a non-hygroscopic
tape. The stuffing box gland may be left on the pump shaft,
but must be wired or otherwise securely fastened in position.
5. Coat all exposed painted surfaces with an antirust agent that
can be readily removed with a petroleum distillate product.
6. Make sure that all exposed painted surfaces are dry, clean
and free of grease and other contaminants.
7. Cover the pump with a weather-resistant cover of waterproof
paper or plastic material to protect it against dirt and dust.
8. Inspect the pump at regular intervals during storage.
9. Rotate the shaft by hand every four to six weeks to prevent
pitting of the bearings.
3.3.1 Engine
Engines may be stored for up to 12 months in a dry room after
delivery. We recommend that you protect the engine with an air-
permeable cover. At least once a month, check the engine for
accumulation of dirt or water. Remove any dirt or water
immediately.
If the engine is stored for more than 12 months or stopped for
more than six months, protect it against corrosion and damage:
1. Drain the engine of oil, and replace the oil filter.
2. Fill the engine housing with appropriate oil.
3. Replace the fuel filter.
4. Separate the engine from the pump by removing the coupling.
5. Turn on the engine. Let it run for one or two minutes.
6. Drain oil and cooling liquid.
7. Drain fuel. Loosen the drain screw in the tank bottom and
collect the diesel fuel in a suitable container. After draining,
tighten the drain screw in the tank bottom.
Repeat these steps every six months.
You find more information about point 1-4 and 6 in the service
instructions.
Warning
Only use the fire pump set for the applications
mentioned. Any other use is considered improper
use. Peerless cannot be held responsible for
damage caused by improper use. The liability
rests solely with the operator.
Note
Check the fire pump set carefully on delivery
against the papers and inspect for damage
incurred during transport. Immediately notify the
carrier of any damage or shortage found.
Transport and store it correctly before
installation.
Warning
Only qualified staff must lift the fire pump set.
When lifting the entire fire pump set, never use
the lifting eyes of the individual components.
Use only suitable lifting equipment in proper
condition.
During transport of the fire pump set, the cabinet
door must be closed and locked.
Do not stand or place hands under a component
in such a way that the component would fall on
the hands if dropped.
TM06 0715 0814
Caution
Put a warning label on the engine:
Engine without oil. Do not start the engine.
English (GB)
4
4. Product description
4.1 Fire pump set
The fire pump set consists of a pump, an electric motor or diesel
engine and a controller. Pump and motor are connected via a
flexible coupling or drive shaft. All components are adapted to
each other and mounted on a common base frame ready for
installation. The base frame is made of steel channel or bent
steel. The controller can also placed separately. The fire pump
set comes ready for operation.
As an example, the most important components of the fire pump
set are shown in fig. 2. It shows an AEF fire pump set with a
Peerless horizontal split-case-pump and an electric motor.
Pump and motor are connected by a flexible coupling.
The controller is installed separately.
Fig. 2 Example of fire pump set
4.2 Pump
The fire pump set comes with a Peerless AEF horizontal split-
case-pump. The pump is FM-approved and UL-listed.
The impeller diameter of both pumps can be reduced to
customise the pump performance to a certain duty point.
The actual impeller diameter may therefore deviate from the
standard diameters stated in catalogues, data sheets etc.
The actual impeller diameter is stated on the pump nameplate.
4.2.1 Split-case-pump
The Peerless AEF horizontal split-case-pump is a non-self-
priming, single-stage pump. It has in-line axial suction and
discharge ports with ANSI flanges. An adapter flange from ANSI
to DIN is available and must be ordered separately. The pumps
are equipped with a stuffing box, and with an automatic air
release valve making venting unnecessary.
4.3 Motor
4.3.1 General description for electric motor
Electric driven fire pump sets are driven by a 2- or 4-pole motor,
typically NEMA design B motors in accordance with UL 1004-s.
The motors are insulation class F and the terminal boxes are
either ODP or TEFC. A service factor of 1.15 is also typically
furnished.
4.3.2 General description for diesel engine
The pump is driven by a stationary 4-stroke diesel engine. It has
been especially adapted to meet the requirements of fire pumps.
The diesel engine is FM-approved and UL-listed.
The rated engine power is adapted to the power requirement of
the pump. The adaptation takes place via the engine speed,
which may therefore not be changed. Depending on power
output, the engines have a turbocharger and, if necessary, also a
charge air cooler.
The engine is typically cooled via a heat exchanger. Water is
supplied from the discharge port of the pump. Before water runs
into the heat exchanger, it flows through a cooling circuit.
See fig. 3. The discharge from the heat exchanger is led via an
open outlet or a visible waste cone back to the suction reservoir.
Fig. 3 Cooling circuit
If the cooling circuit is faulty, and the temperature of the cooling
liquid becomes too high, open isolating valves (pos. C and D) and
close isolating valves (pos. A and B).
4.3.3 Control panel of the engine
The engine is equipped with its own control panel. You can
operate the fire pump set via the controller or via the control panel
of the engine. Normally, operation takes place via the controller.
If the controller fails, only use the control panel of the engine.
Additionally, the control panel of the engine indicates the main
parameters of the engine, such as engine speed, voltage of
battery 1 and 2, oil pressure and temperature of cooling liquid.
The design of the control panel is shown in fig. 4 for JU and JW
engines, and in fig. 5 for three engines. An explanation of the
operating elements and the indicators is given in the table below
fig. 4 and 5. For more information, see the installation and
operating instructions of the engine.
TM06 2243 3814
Pos. Component
1 Base frame
2 Controller
3Pump
4 Automatic air release valve
5 Motor
6 Coupling with coupling guard
56
4
3
1
2
Caution
The injection pump has been set from factory,
and the setting must not be changed.
TM04 5066 2609
CD
AB
English (GB)
5
Fig. 4 Control panel of JU and JW diesel engine
TM06 1271 2014
I1 251
I243376
I3
I4 I5
Pos. Operating element Description
1
Instructions for
emergency operation
Instructions as how to start
the engine via the control
panel.
2 Selector switch
For selection of automatic or
manual operation.
3
Manual start switches,
battery 1 or 2
For manual start of engine
with battery 1 or 2.
4 Overspeed reset
If the engine has been
stopped due to an overspeed
condition, reset the overspeed
alarm with this switch when
the problem has remedied.
5 Warning light
Indicates that the selector
switch is not set to
"AUTOMATIC OR MANUAL
STOP".
6
Overspeed shut down
warning light
Indicates that the engine is
shutdown due to overspeed.
7 Overspeed verification
For testing if the overspeed
function works and the engine
stops in case of overspeed.
The overspeed signal is
generated at 67 % of the rated
speed. Reset overspeed
alarms with the
"OVERSPEED RESET"
switch (pos. 4).
Pos. Indicator Description
I1
Tachometer and
operating hour counter
Shows engine speed and the
number of operating hours
I2 Oil pressure
Shows the oil pressure of the
engine.
I3 Voltmeter, battery 1
Shows the voltage supplied by
battery 1.
I4 Voltmeter, battery 2
Shows the voltage supplied by
battery 2.
I5 Temperature indicator
Shows the temperature of the
cooling liquid.
English (GB)
6
Fig. 5 Control panel of JX diesel engine
* Electronic control module
TM04 5115 2609
9
7
5
3
1
8
6
4
2
10 11 12
Pos. Operating element Description
1 Engine gauge display
Shows relevant engine
parameters and alarm
messages.
2 Voltmeter, battery 1 or 2
Shows the voltage supplied by
battery 1 or 2.
3 Operating hour counter
Shows the number of
operating hours.
4
Battery selector switch,
voltmeter
For selection of battery
voltage to be indicated by the
voltmeter.
5 Selector switch
For selection of automatic or
manual operation.
6 ECM selector switch*
Default position is "PRIMARY
ECM". Only in case of a
failure of the primary ECM,
causing the engine to stop or
not to start, manually switch to
"ALTERNATE ECM."
7
Warning light, manual
operation
Indicates that the selector
switch is not set to automatic
operation.
8
Warning light, alternate
ECM*
Indicates that the ECM
selector switch is set to
"ALTERNATE ECM".
9 Manual stop switch For manual stop of engine.
10
Manual crank switch,
battery 1
For manual start of engine
with battery 1.
11
Manual crank switch,
battery 2
For manual start of engine
with battery 2.
12 Overspeed reset
If the engine has been
stopped due to an overspeed
condition, reset the overspeed
alarm with this switch when
the problem has remedied.
English (GB)
7
The control panel of the JX6 diesel engine is equipped with an
engine gauge display. See fig. 6.
Fig. 6 Diagnostic gauge of JX6 control panel
During normal operation of the diesel engine, the display will
show the engine speed, temperature of cooling liquid, oil
pressure and voltage of battery 1 or 2 selected with the battery
selector switch. See fig. 6.
Fig. 7 Example of indications during normal operation, JX6
If an alarm occurs, the alarm message will be shown instead of
the engine parameters.
Fig. 8 Example of alarm message, JX6
SPN (Suspect Parameter Number) and FMI (Failure Mode
Identifier) codes will be shown along with a description of the
problem and the corrective action needed. If the word "NEXT"
appears above the arrow buttons, you can view further codes by
scrolling with the arrow buttons. See fig. 6, pos. C. Press the
enter button to return to the parameter screen. See fig. 6, pos. D.
You find an overview of possible alarm messages in the service
instructions together with SPN and FMI codes.
4.4 Controller
4.4.1 General description
The fire pump set is operated via a controller especially sized for
electric motors driving fire pumps. The controller starts the pump
automatically and monitors the motor. It is FM-approved.
As soon as the sprinklers are activated due to an alarm and water
is consumed, the pressure in the discharge pipe will be reduced.
If the pressure falls below the cut-in pressure set on the control
panel, the pump will start automatically.
For test run and setup, manual operation is possible.
The individual controller models differ mainly by starting method
and power range.
Starting method direct on line
This model is used where the electricity works or the capacity of
the power source permits direct-on-line starting.
Full voltage is applied to the motor as soon as the controller
receives a start command.
Starting method star/delta open transitionWhen the controller
receives a start command, the motor is connected in star. After a
time delay, it changes over to delta connection with full voltage to
the motor windings. This controller is of the open transition type.
The motor is disconnected from the mains during the transition
from start (star) to run (delta) mode.
4.4.2 Controller design
The controller is placed in a control cabinet mounted on the base
frame (compact unit) or delivered separately for wall- or floor-
mounting (flex unit). The controller is operated by means of the
control panel in the cabinet door. The control cabinet supplies the
motor with the electricity required for starting and operating the
motor.
TM04 5116 2609
Pos. Designation Description
A Display
Shows the four most important
engine parameters:
engine speed
temperature of cooling liquid (°F)
oil pressure (psi)
battery voltage (1 or 2).
If an alarm occurs, the alarm
message will be shown instead of
the engine parameters.
B Menu button Opens the main menu.
C Arrow buttons Scrolls through the menus.
D Enter button
Opens selected submenus.
Activates settings and functions.
E
Indicator light
Engine stopped
(red)
Lights up if a fault occurred that will
stop the diesel engine, such as
overspeed.
F
Indicator light
Warning (amber)
Lights up if a warning condition
occurs.
TM04 5117 2609
FE
A
D
CB
TM04 5118 2609
Note
You cannot make settings in the diagnostic
gauge. Do not use the main menu button.
See fig. 6, pos. B.
English (GB)
8
4.5 Nameplate
All important data of the fire pump set are stated on the pump
nameplate. See fig. 9.
Nameplate for AEF pump
Fig. 9 Example of nameplate for AEF pump
5. Operating conditions
5.1 Minimum inlet pressure
At any time, there must be a positive inlet pressure.
We recommend a minimum inlet pressure of 5 psi.
5.2 Maximum inlet pressure
The sum of actual inlet pressure plus pump pressure against a
closed valve must always be lower than the maximum
permissible operating pressure. See section 5.8 Maximum
operating pressure. The maximum inlet pressure is a function of
the closed-valve pressure and the maximum pump pressure. It is
stated on the nameplate.
5.3 Minimum flow rate
Only brief periods of operation during start and stop are
permissible with a closed discharge valve. Prolonged operation at
less than 15 to 20 % of the pump's rated capacity will cause
heating of the pumped liquid, impeller erosion, short life of
bearings and packing due to stress or vibration. This may cause
shaft damage and wear on stationary parts on some pumps.
Therefore, we recommend that you install a bypass pipe to
ensure a minimum flow rate of at least 10 % at maximum
efficiency. The minimum flow rate helps to dissipate any
excessive heat and thus protect the pump against overheating.
5.4 Pumped liquids
The pumps are suitable for clean and non-aggressive water, not
containing solid particles or fibres.
5.5 Water temperature
Maximum permissible water temperature is 40 °C.
5.6 Pump temperature
The pumps can handle temperatures from 0 to 120 °C.
5.7 Pump speed
The maximum pump speed is stated on the test report and shown
on the nameplate for the fire pump set.
TM06 2123 3814
Pos. Description
1 Pump type
2 Approvals
3 Type designation
4 Number of stages
5 Actual impeller diameter
6 Serial number
7 Rated flow rate
8 Rated head
9 Rated speed
10 Head at 150 % flow rate
11 Maximum head
12 Maximum power
13 Maximum suction lift
14 Manufacturer
Warning
Do not operate the pump at any pressure, flow
rate or liquid temperature other than those for
which the pump was originally purchased. Do not
pump any other liquid than the one for which the
pump was originally purchased without the
consent of Peerless or its authorised
representatives. Disregard of this warning can
result in pump failure and serious personal injury
or death.
Caution
Inadequate inlet pressure will result in cavitation
damage to the impeller and casing.
Caution
Generally, the pump is not allowed to run against
a closed valve, as this may cause an increase in
temperature or formation of steam in the pump.
This may cause damage to the pump.
Caution
Operation of the pump with flow only through the
bypass is not allowed.
English (GB)
9
5.8 Maximum operating pressure
The maximum operating pressure is stated on the pump
nameplate.
5.9 Ambient temperature
5.9.1 Electric motor
Minimum ambient temperature: 4 °C.
Maximum ambient temperature: 40 °C (50 °C optional).
5.9.2 Diesel engine
Minimum ambient temperature: 4 °C if the engine includes
preheating.
Maximum ambient temperature: The maximum permissible
ambient temperature at the air filter inlet is 49 °C according to
NFPA 20.
5.10 Relative air humidity
The relative air humidity must not be too high, to prevent
condensation of moisture in the air, as this can lead to damage of
the controller or the motor. If humidity is a problem, install a
space heater with a humidistat.
5.11 Effect of ambient temperature and altitude on
electric motor output
If the ambient temperature exceeds 40 °C (fig. 10), or the motor is
installed more than 1000 metres above sea level, the motor must
not be fully loaded due to the low density and consequently low
cooling effect of the air. In these cases, it may be necessary to
use a motor with a higher output.
Fig. 10 Relation between motor output, altitude and ambient
temperature
5.12 Effect of ambient temperature and altitude on
diesel engine output
If the ambient temperature exceeds 25 °C (fig. 11), or if the
engine is installed more than 90 metres above sea level (fig. 12),
the engine must not be fully loaded due to the low density and
consequently low cooling effect of the air. In these cases, it may
be necessary to use a larger engine.
Fig. 11 Relation between engine output and ambient
temperature
Fig. 12 Relation between engine output and altitude
TM00 2189 4198
20 25 30 35 40 45 50 55 60 65 70 75 80
50
60
70
80
90
100
[%]
P1
t [°C]
1000 2250 3500 m
TM03 4718 2606TM03 4717 2606
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
50
60
70
80
90
100
[%]
P2
80 100 120 140 160 180 T [°F]
T [°C]
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
[m]
50
60
70
80
90
100
[%]
P2
0 2000 4000 6000 8000 10000 12000 14000
[ft]
English (GB)
10
6. Installation
6.1 Installation site
Place the fire pump set in a clean, dry, frost-free and well-
ventilated location. Make sure that unauthorised persons do not
have access to the location.
Allow sufficient clearance around the pump set to enable
inspection, repair and assembly work.
6.2 Foundation
We recommend that you install the fire pump set on a concrete
foundation which is heavy enough to provide permanent and rigid
support for the entire fire pump set. The foundation must be
capable of absorbing any vibration, normal strain or shock. As a
rule of thumb, the weight of the concrete foundation must be
1.5 times the weight of the fire pump set. Ordinarily, the
proportions used are one part cement to three parts sand and
four parts medium aggregate.
The concrete foundation must have an absolutely level and even
surface. Provide the foundation with anchor bolts to fasten the fire
pump set.
Recommended length and width of the foundation. See fig. 13.
Note that the length and width of the foundation must be 200 mm
larger than the length and width of the base frame.
See dimension x.
You can calculate the minimum height of the foundation (h
f
) as
follows if the weight of the foundation is assumed to be 1.5 times
the wet weight of the pump set :
The density (δ) of the foundation is usually taken as 2200 kg/m
3
.
In installations where low-noise operation is particularly
important, we recommend a foundation with a weight of up to five
times that of the pump.
Fig. 13 Dimensions of foundation
Warning
The installation must be carried out in
accordance with the following instructions.
Non-compliance may result in functional faults
which will damage the pump components.
Caution
Ensure an adequate supply of air for cooling the
motor, diesel engine and control cabinet.
Warning
Make sure that the weight of the fire pump set
and foundation does not exceed the permissible
bearing load of the floor.
h
f
=
m
pump
× 1.5
L
f
× B
f
× δ
concrete
TM06 0717 0814
X
hf
X
X
X
B
f
Lf
Lf
English (GB)
11
6.3 Levelling
Place the fire pump set on the foundation or an even floor and
anchor it with adequately sized anchor bolts. The entire base
frame must be supported uniformly. See figures 14 and 15.
If necessary, use shims for horizontal levelling of the base frame.
Fig. 14 Correct installation
Fig. 15 Incorrect installation
6.4 Pipework
Arrange the suction and discharge piping in the most simple and
direct layout. The pipes must be of an adequate size, taking also
the pump inlet pressure into consideration. The flow direction is
marked with arrows.
Install the pipes so that air locks are avoided, especially on the
suction side of the pump. See fig. 16.
Fig. 16 Correct and incorrect installation of suction pipe
Fit pipe hangers on the wall, ceiling or floor close to the pump on
the suction and the discharge side. See fig. 17.
The pipes must lie true against the pump flanges without being
stressed. Otherwise, the pump may be damaged.
Fig. 17 Fixing points of the pipes
You can install isolating valves on the suction and the discharge
side of the pump.
Warning
Only qualified staff must lift fire pump set.
When lifting the entire fire pump set, never use
the lifting eyes of the individual components.
Use only suitable lifting equipment in proper
condition.
During transport of the fire pump set, the cabinet
door must be closed and locked.
TM06 0718 0814TM06 0719 0814
Warning
Do not put fingers, hands, arms, etc. into the
suction or discharge openings or into any other
opening, such as that of the air relief valve.
Do not touch the rotating impeller, as this can
cause severe injury.
Do not remove protective covers or packaging
until installation.
Caution
The pipework must not stress the pump housing
or transfer any forces to the pump housing.
Noncompliance may damage the pump.
TM04 5122 2609 TM06 0720 0814
English (GB)
12
6.5 Alignment
6.5.1 Aligning electric motor and pump
Pump and motor are connected by a standard flexible coupling.
If a fire pump set is pre-assembled from factory, the coupling has
been accurately aligned by means of shims inserted under the
pump and motor.
During transport and installation, the pump-motor alignment may
have been affected. Therefore, always check the pump-motor
alignment when you have installed the fire pump set.
The coupling used for connecting the pump and motor is shown in
fig. 18.
Fig. 18 Aligning motor and pump
You find the values for and s
2
in the following table. The value
for s1 is 0.1 mm.
6.5.2 Aligning diesel motor and pump
Pump and engine are connected by a drive shaft.
If a fire pump set is pre-assembled from factory, the coupling has
been accurately aligned by means of shims inserted under the
pump and engine.
During transport and installation, the pump-motor alignment may
have been affected. Therefore, always check the pump-motor
alignment when you have installed the fire pump set.
Follow the instructions below to align the diesel engine and the
pump:
1. Remove the coupling guard.
2. Check the drive shaft for proper parallel offset and angular
tolerance.
3. Fit the coupling guard.
4. Connect the battery cables.
At first, check if the bolts of the drive shaft are tightened with the
correct tightening torque. It may be necessary to use a special
torque tool if there is not enough space for a standard socket.
The following steps describe how to align the drive shaft between
the motor and the pump. We recommend that you use a small
pocket scale or ruler with millimetre markings to make all
measurements.
Warning
Before removing the coupling guard, make sure
that the fire pump set has been switched off and
cannot be accidentally switched on.
Caution
Alignment of motor and pump is important for a
long coupling life. This is particularly important
with increased motor speed. Follow the
installation instructions of the coupling
manufacturer.
TM03 2999 5005
Outside
diameter of
coupling,
[mm]
Clearance, s
2
[mm]
Standard coupling Spacer coupling
Nominal Tolerance Nominal Tolerance
80 - - 4 0/-1
95 - - 4 0/-1
110 - - 4 0/-1
125 4 0/-1 4 0/-1
140 4 0/-1 4 0/-1
160 4 0/-1 4 0/-1
200 4 0/-1 4 0/-1
225 4 0/-1 4 0/-1
250 4 0/-1 4 0/-1
s
1
s
2
ø
90°
90°
90°
90°
Caution
Alignment of diesel engine and pump is
important for a long coupling life. This is
particularly important with increased engine
speed.
Warning
Before removing the coupling guard, disconnect
the battery cable.
English (GB)
13
Checking the horizontal parallel offset
A: To check the horizontal parallel offset, the driveshaft must be in
the proper orientation.
1. Rotate the shaft so that the reference "AB" on the flywheel
drive disc is in 12 o'clock position. See fig. 19.
2. Measure from the face of the flywheel drive disc to point E as
shown in fig. 19 (point E is to the furthermost point on the
drive shaft joined bore diameter). See the horizontal offset in
table below.
Checking the horizontal angular alignment
B: With the driveshaft in the same orientation as in step A, check
the horizontal angular alignment of the shaft.
1. Measure from the face of the pump shaft flange to point G as
shown in fig. 19 (point G is to the furthermost point on the
drive shaft joined bore diameter). This measurement must be
equal to the measurement at point E ± 0.5 mm.
Fig. 19 Horizontal alignment
Checking the vertical parallel offset
C: To check the vertical parallel offset, the driveshaft must be re-
orientated.
1. Rotate the shaft 90 ° so the reference "CD" on the flywheel
adapter disc is in 12 o'clock position. See fig. 20.
2. Measure from the face of the flywheel adapter disc to point H.
Point H is furthermost point on the drive shaft joined bore
diameter. See fig. 20. See the vertical offset in table below.
Checking the vertical angular alignment
D: With the driveshaft in the same orientation as in step C, check
the vertical angle alignment of the shaft.
1. Measure the face of the pump shaft flange to point J. Point J
is the same as point G, with the driveshaft rotated 90 °.
See fig. 20. This measurement must be equal to the
measurement at point H ± 1 mm.
Reinstall all guards and grease fittings before reconnecting the
battery cables.
Fig. 20 Vertical alignment
See also the installation and operating instructions for the drive
shaft.
TM06 1531 2614
E
G
Flanged
pump hub
Flywheel
adapter disc
TM06 1532 2614
H
J
English (GB)
14
Horizontal and vertical offset for drive shaft
Engine type Drive shaft type
SAE
flywheel
Flywheel
drive disc
Horizontal
offset
[mm]
Vertical
offset
[mm]
Bolt grade
Bolt
torque
[ft/lbs]
JU4H-UFAEA0
CDS10-SC (UL listed) 11.5 CF10 58 ± 1 60 ± 1
8
(hi-tensile)
50
JU4H-UF10
JU4H-UF12
JU4H-UF14
JU4H-UF20
JU4H-UF22
JU4H-UF24
JU4H-UFAB26
JU4R-UFAEA9
JU4R-UF09
JU4R-UF11
JU4R-UF13
JU4R-UF19
JU4R-UF21
JU4R-UF23
JU4H-UFAEE8
CDS20-SC (UL listed) 11.5 CF20 68 ± 1.5 70 ± 1
8
(hi-tensile)
75
JU4H-UFAEF2
JU4H-UF30
JU4H-UF32
JU4H-UF34
JU4H-UF40
JU4H-UF42
JU4H-UFH0
JU4H-UFH2
JU4H-UFH8
JU4H-UFADJ8
JU4H-UFADJ2
JU4R-UF40
JU4R-UFAEE7
JU4R-UFAEF1
JU6H-UF30
CDS20-S1 (UL listed) 11.5 CF20 68 ± 1.5 70.5 ± 1
8
(hi-tensile)
75
JU6H-UF32
JU6H-UF34
JU6H-UFD0
JU6H-UFD2
JU6R-UFAAD9
JU6R-UFAAD1
JU6R-UFAA29
JU6R-UFAA31
JU6R-UFAA33
English (GB)
15
JU4H-UF50
CDS30-S1 (UL listed) 11.5 CF30 84 ± 1 86.5 ± 1
8
(hi-tensile)
30
JU4H-UF52
JU4H-UF54
JU4H-UF58
JU4H-UFAD5G
JU4H-UFADJG
JU4H-UFADP0
JU4H-UFADR0
JU4H-UFADW8
JU4H-UFADY8
JU4R-UF49
JU4R-UF51
JU4R-UF53
JU6H-UF50
JU6H-UF52
JU6H-UF54
JU6H-UF58
JU6H-UF60
JU6H-UF62
JU6H-UF68
JU6H-UF84
JU6H-UFM0
JU6H-UFM2
JU6H-UFM8
JU6H-UFG8
JU6H-UFABL0
JU6H-UFABL2
JU6H-UFABL8
JU6H-UFAD58
JU6R-UFAAG7
JU6R-UFAAL7
JU6R-UFAAL9
JU6R-UFAAL1
JU6R-UFAAM7
JU6R-UFAAM9
JU6R-UFAAM1
JU6R-UFAA57
JU6R-UFAA49
JU6R-UFAA51
JU6R-UFAA53
JU6R-UFAA67
JU6R-UFAA59
JU6R-UFAA61
JU6R-UFAA83
JU6H-UFADM8
JU6H-UFADMG
JU6H-UFADNG
JU6H-UFAB76
JU6H-UFADK0
JU6H-UFADN0
JU6H-UFADQ0
JU6H-UFADR0
Engine type Drive shaft type
SAE
flywheel
Flywheel
drive disc
Horizontal
offset
[mm]
Vertical
offset
[mm]
Bolt grade
Bolt
torque
[ft/lbs]
English (GB)
16
JU4H-UFAD98
CDS50-SC*
Only at 1470
to 2100 rpm
(UL listed)
N/A
11.5
CF50 109 ± 2 112.5 ± 1
8
(hi-tensile)
50
JU6H-UFAAQ8
SC81A (not
UL listed)
JU6H-UFAAPG
JU6H-UFAARG
JU6H-UFADP8
JU6H-UFADP0
JU6H-UFAD88
JU6H-UFAD98
JU6H-UFADT0
JU6H-UFADR8
JU6H-UFADS8
JU6H-UFADS0
JU6H-UFAAS0
JU6H-UFADW8
JU6H-UFADX8
JU6H-UFADX9
JU6H-UFADX10
JU6H-UFADX11
JU6H-UFADX12
JW 6H-UFAD80
JW 6H-UFADD0
JW 6H-UFADF0
JW 6H-UFADJ0
JW 6H-UFAAM8
JW 6H-UFAD70
JW 6H-UFAA80
DP6H-UFAAX8
14
DP6H-UFAA50
DP6H-UFAA88
DP6HUFAA62
DP6H-UFAA70
DQ6H-UFAA48
DQ6H-UFAA40
DQ6H-UFAA50
DQ6H-UFAA60
DQ6H-UFAA88
DQ6H-UFAA98
Engine type Drive shaft type
SAE
flywheel
Flywheel
drive disc
Horizontal
offset
[mm]
Vertical
offset
[mm]
Bolt grade
Bolt
torque
[ft/lbs]
English (GB)
17
* CDS50-SC listed drive shafts at 2100 rpm only for JW6H-
UFAA80 and JW6H-UFAD80, 1760 rpm only for DP6H-
UFAA88 and at 1470 rpm only for DP6H-UFAA70. Any other
speed would require the non-listed drive shaft SC81A.
JX6H-UFADF0
N/A
SC2160A (not
UL listed)
11.5
180-10
123.5 ± 1.5 126.5 ± 1
8
(hi-tensile)
210
JX6H-UFAD60
JX6H-UFADK0
JX6H-UFAD88
JX6H-UFADN0
JX6H-UFADP0
14
DR8H-UFAA40
DR8H-UFAA5G
DR8H-UFAA68
DR8H-UFAA62
DR8H-UFAA98
DR8H-UFAA92
DS0H-UFAAM0
DS0H-UFAAN0
DS0H-UFAA68
DS0H-UFAA60
DS0H-UFAA98
DS0H-UFAA92
DT2H-UFAA20
DT2H-UFAA58
DT2H-UFAA50*
DT2H-UFAA60
DT2H-UFAA88
SC2390 (not
UL listed)
142.5 ± 1.5 145.5 ± 1.5DT2H-UFAA98
DT2H-UFAA92
Engine type Drive shaft type
SAE
flywheel
Flywheel
drive disc
Horizontal
offset
[mm]
Vertical
offset
[mm]
Bolt grade
Bolt
torque
[ft/lbs]
English (GB)
18
6.6 Air supply
Figure 21 shows a possible arrangement of supplied and
discharged air ensuring a sufficient supply of fresh air.
Fig. 21 Supply and discharge of air
If required, install louvres to open as soon as the engine starts.
This will ensure an adequate supply of fresh air and removal of
engine heat.
6.7 Exhaust system
Install exhaust pipes as straight and with as few bends as
possible to enable discharge of combustion gases with a
minimum of back-pressure. Install the supplied silencer
horizontally and at a sufficient distance to the engine.
The exhaust system is to be arranged so that no condensation
water can enter the engine.
The exhaust system must be fixed to the building. The flexible
connection piece must not be used to compensate for misaligned
pipework.
The minimum diameter of the exhaust pipes must not be smaller
than that of the exhaust port of the engine.
6.8 Separate control cabinet
The controller must be located as close as practical to the motor
and within sight of the motor.
Ensure easy accessibility to the controller and its components
and adequate air supply for cooling.
Wall-mounted controller
Attach the controller to the structure or wall not less than 305 mm
(12 inches) above floor level. Drill holes in the wall according to
the drilling template on the rear panel of the control cabinet.
Use dowels and screws of adequate size. Use all four mounting
holes.
Floor-mounted controller
Attach the controller to the floor using all holes of the mounting
feet. The mounting feet provides the required 305 mm (12 inches)
clearance for current-carrying parts. We recommend that you use
a concrete slab to avoid water accumulation at the controller's
feet.
TM03 5501 3706
Warning
The exhaust system must be installed correctly
according to local regulations and must have no
leaks. Operation without exhaust system is not
permitted.
Exhaust must be directed safely to the open air
through the exhaust system. Exhaust must not
escape indoors. Risk of suffocation!
Hot exhaust pipes must be protected to prevent
accidental touch. Risk of scalding!
0
9
0
9
0
8
0
8
0
1
0
1
0
2
0
2
0
3
0
3
0
4
0
4
0
6
0
6
0
7
0
7
0
5
0
5
0
Warning
Installation in hazardous locations and
potentially explosive environments is not
allowed. The controller must be located or
protected so it will not be damaged by water
escaping from pump or pump connections.
Caution
The controller is not designed for outdoor
installation. It must not be exposed to direct
sunlight and must be installed in a dry, well
ventilated but frost-free location.
Warning
When drilling the holes, take care not to damage
any cables or water and gas pipes. Ensure a safe
installation.
English (GB)
19
7. Electrical connection
See the wiring diagrams supplied with the pump set for correct
connection and cable sizing.
7.1 Checking the direction of rotation on electric units
1. Turn circuit breaker to "ON". If the pump does not start, press
the "START" button A2 and stop immediately.
2. Observe the direction of rotation.
3. If the direction of rotation is not correct, switch off the power
supply, and interchange two phases in the terminal box or in
the controller.
8. Maintenance
8.1 Maintenance intervals
Fire pump set
Visible check: Every six months.
Tightness of bolts, etc.: Every six months.
Alignment, motor and pump: Every six months.
Pump
Stuffing box: Every six months.
Gaskets: Every six months.
Lubrication of bearing: Every six months.
Replacement of bearings: Every six years.
Motor
Motor cables: Every six months.
Lubrication of bearings: Every six months.
Replacement of bearings: Every six years.
Fan: Every three years.
Coupling
Coupling guard: Once a week.
Coupling assembly: Every six months.
Lubrication of drive shaft: Once a year.
Controller
Checking of wire connections: Every six months.
Visible inspection: Every six months.
Testing of indicator lights: Once a week.
Checking of wire connections: Once a year.
Diesel engine
9. Service, spare parts and accessories
The installation and (or) use of such products may negatively
alter and thus impair the specified properties of the fire pump set.
The usage of non-original spare parts and accessories renders
any liability on behalf of Peerless for resulting damages null and
void.
Any malfunctions which cannot be repaired should only be
corrected by Peerless or authorised specialist companies.
Please provide an exact description in the event of a malfunction
so that our service technician can prepare and provide the
appropriate spare parts.
Please obtain the technical data for the system from the
nameplate.
10. Warranty
The warranty is governed by the framework of our general terms
of delivery. Liability for any damage resulting from incorrect
installation, electrical connection or use, as well as liability for
consequential damage, is excluded. The start of the warranty
period is to be verified.
11. Further documentation
These installation and operating instructions are to be used in
conjunction with the following documentation:
wiring diagram of controller.
service instructions of the fire pump set.
service instructions of major components (motor, engine,
control panel).
12. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
Subject to alterations.
Warning
Check that the supply voltage specified on the
nameplate of the control cabinet corresponds to
the local conditions.
The electrical connection should be carried out
by qualified staff in accordance with local
regulations.
Caution
Only watertight hub fittings must be used when
entering the cabinet to preserve the NEMA rating
of the cabinet.
Note
The operator is responsible for ensuring that all
maintenance, inspection and installation work is
performed by qualified staff. A regular
maintenance plan will help avoid expensive
repairs and contribute to trouble-free, reliable
operation. We recommend that you place a
maintenance contract with Peerless.
Warning
Before starting work on the pump, make sure that
the power supply has been switched off and
cannot be accidentally switched on.
Maintenance work must only be carried out by
qualified staff.
Note
You find more detailed information about
maintenance in the service instructions.
Interval
Inspection Replacement
Oil level Once a week -
Oil change with filter - Once a year
Cooling system Once a week -
Cooling liquid - Once a year
Fuel system and filter Once a week Once a year
Exhaust system Once a week -
Air filter Once a week Every six months
V-belt Once a month Once a year
Warning
Spare parts and accessories not supplied by
Peerless are not inspected or approved by
Peerless.
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22

Grundfos AEF Installation And Operating Instructions Manual

Type
Installation And Operating Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI