Pulsar MSRK1012 - v1.0 Operating instructions

Type
Operating instructions
MSRK 1012
v.1.0
MSRK 13,8V/1A/OC
Buffer, switch mode power supply module
with automatic operation control.
EN**
Edition: 1 from 11.06.2014
Supersedes the edition: ------------
www.pulsar.pl MSRK1012
2
Features:
DC 13,8V/1A uninterruptible power supply
high efficiency 86%
low voltage ripple
battery charging and maintenance control
excessive discharging (UVP) protection
battery output full protection against short-circuit
and reverse polarity connection
jumper selectable battery charge current
0,2A/0,5A
START facility for manual battery connection
LED indication
EPS technical output indicating AC power loss
OC type
PSU technical output indicating PSU failure OC type
LoB technical output indicating battery low voltage
OC type
adjustable times indicating AC power failure
protections:
SCP short-circuit protection
OLP overload protection
OHP overheat protection
overvoltage protection
warranty 5 year from the production date
CONTENTS:
1. Technical description.
1.1. General description.
1.2. Block diagram.
1.3. Description of components and connectors.
1.4. Specifications
2. Installation.
2.1. Requirements.
2.2. Installation procedure.
3. Operating status indication.
3.1. LED indication.
3.2. Technical outputs.
4. Operation and use.
4.1. Overload or short circuit of the PSU module output.
4.2. Running the PSU module from the bartery.
4.3. Deep discharge battery protection UVP.
4.4. Maintenance.
1. Technical description.
1.1 General description.
A buffer PSU module is intended for an uninterrupted supply to devices requiring stabilised voltage of 12V
DC (+/-15%). The PSU module provides voltage of 13,8V DC with current capacity:
1. Output current 1A + 0,2A battery charge
2. Output current 0,7A + 0,5A battery charge
Total device current + battery: 1,2A max.
In case of power failure, a battery back-up is activated immediately.
www.pulsar.pl MSRK1012
3
1.2. Block diagram (fig.1)
Fig.1. Block diagram of the PSU module
1.3. Description of components and connectors PSU module.
Table 1. Elements of the PSU module pcb (fig. 2).
Element no.
Description
[1]
P
BAT
; pins - configuration of UVP battery protection function
P
BAT
= protection (disconnection) of the battery off
P
BAT
= protection (disconnection) of the battery on
T
AC
; pins T
AC
- configuration of time lag of AC failure indication
T
AC
= time lag T= 10s
T
AC
= time lag T= 60s
Legend: jumper installed jumper removed
[2]
START button (launching from battery)
[3]
V
ADJ
potentiometer, DC12 ÷ 14,5V adjustment
[4]
F
BAT
fuse in the battery circuit, F2A / 250V
[5]
Terminals:
~AC~ AC power input
EPS technical output of AC power failure indication
hi-Z state = AC power failure
0V state = AC power - O.K.
PSU technical output of PSU failure indication
hi-Z state = failure
0V state = PSU status O.K.
LoB technical output of low battery voltage indication
hi-Z state = battery voltage U
BAT
<11,5V
0V state = battery O.K.
+BAT- terminals for battery connection
+AUX- DC power output, (+AUX= +U, -AUX=GND)
Description: hi-Z high impedance, 0V connection to the ground GND
[6]
LEDs optical indication:
AC - AC voltage
LB - battery charge
AUX - output voltage DC
[7]
Connector to the external LED indicators.
[8]
I
BAT
jumper battery charging current selection
I
BAT
= Ibat =0,2A
I
BAT
= Ibat =0,5A
Legend: jumper installed jumper removed
www.pulsar.pl MSRK1012
4
Fig.2. View of the PSU module
1.4 Specifications:
- electrical parameters (tab.3)
- mechanical parameters (tab.4)
- operating parameters (tab.5)
Electrical parameters (tab. 3).
18V÷22V AC
30VA min. (e.g. AWT150,AWT468)
1,4 A max.
50Hz
17 W
86%
11V÷ 13,8 V DC – buffer operation
10V÷ 13,8 V DC – battery-assisted operation
1A + 0,2A battery charge
0,7A + 0,5A battery charge
12V÷ 14,5V DC
50 mV p-p max.
15 mA
0,2A /0,5A - jumper selectable
Electronic - current limitation and/or activation of the F
BAT
melting fuse in the battery circuit (failure requires fuse
replacement). Automatic return.
110% ÷ 150% (@25ºC) of power supply, manual restart (the
fault requires disconnection of the DC output circuit)
F 2A - current limitation, F
BAT
fuse (in case of a failure, fuse-
element replacement required)
varistors
U<10V (± 5%) disconnect of connection battery,
configuration by the P
BAT
jumper
- red, normal status: permanently illuminated, failure: off
- green, normal status: permanently illuminated, failure: off
- yellow, the light intensity depends on battery charging
current
- OC type: 50mA max.
Normal operation: L state (0V),
failure: hi-Z state,
- delay time 10s/60s (+/-20%) jumper selectable T
AC
- OC type: 50mA max.
Normal operation: L state (0V),
failure: hi-Z state,
www.pulsar.pl MSRK1012
5
- OC type, 50mA max.
Normal operation (UBAT >11,5V): L state (0V),
failure (UBAT <11,5V): hi-Z state
F2A / 250V
Mechanical parameters (tab. 4).
Enclosure dimensions
86 x 58 x 25 (WxLxH) [mm] (+/- 2)
Fixation
Dowel pins x4 (PCB fi=4,2 mm)
Net/gross weight
0,06kg/0,14kg
Connectors
Outputs: Ф0,41÷1,63 (AWG 26-14)
Battery output BAT: 6,3F-2,5, 30cm
Operating parameters (tab.5).
Environmental class
II
Operating temperature
-10ºC...+40ºC
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation.
2.1. Requirements.
The buffer PSU module is to be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC and low-voltage installations. The unit should be mounted in
confined spaces, in accordance with the II-nd environmental class, with normal relative humidity (RH=90% maximum,
without condensing) and temperature from -10°C to +40°C.
The unit should be mounted in a metal enclosure (cabinet) in a vertical position so as to ensure free, convection
air flow through the vents.
In order to meet the EU requirements, follow the guidelines on: power supply, enclosures and shielding:
- according to application. The module requires 18-22V AC power supply with galvanic. (transformer) isolation.
1. Output current 1A + 0,2A battery charge
2. Output current 0,7A + 0,5A battery charge
Total device current + battery: 1,2A max.
As the PSU module is designed for a continuous operation and is not equipped with a power-switch,
therefore an appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user
shall be informed about the method of unplugging (most frequently through separating and assigning an
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations.
2.2. Installation procedure.
1. Before installation, cut off the voltage in the 230V power-supply circuit.
2. Install the enclosure or cabinet and lead the cables through the cable ducts.
3. Install the PSU module on mounting pins (the mounting pins should be installed before the assembly of the
enclosure/cabinet).
4. Deliver the AC voltage to the ~AC~ terminals.
5. Connect the receivers’ cables to the +AUX, -AUX terminals of the terminal box on the PSU board.
6. If needed, connect the device cables to the technical outputs:
- EPS; technical output indicating AC power failure
- PSU; technical output indicating PSU failure.
- LoB; technical output indicating low battery voltage
7. Using the I
BAT
pins, determine the maximum battery charging current the should be determine, in accordance
with battery parameters.
8. Using the P
BAT
pins, determine whether the function of disconnecting the discharged battery U<10V (+/-5%) is to
be on or off. The battery protection is on if the P
BAT
jumper is removed.
9. Make the connections between the battery and the power supply panel paying special attention to the correct
polarity.
10. Connect the ~ 230V AC power to the transformer. The corresponding LEDs on the PCB of the power supply module
should be ON: red AC and green AUX LED. The yellow LB LED should be ON during battery charging.
11. Check the output voltage (the PSU voltage without load should amount to 13,6 V÷ 13,9 V, during battery
www.pulsar.pl MSRK1012
6
charging 11 V÷ 13,8 V). If the value of the voltage requires adjustment, it should be set by the V
ADJ
potentiometer, monitoring the voltage at the AUX output of the PSU module.
12. Check the current consumption of the receivers, taking into account the battery charging current, so as not to
exceed the total current efficiency of the PSU (section 1.1).
13. Once the tests and control operation have been completed, close the enclosure/cabinet.
3. Operating status indication.
3.1 LED indication.
The PSU module is equipped with three diodes indicating operating status: AC, LB, AUX.
AC- red diode: under normal status (AC supply) the diode is permanently illuminated. The absence of AC
supply is indicated by the AC diode going off.
LB - yellow diode: indicates the battery charging process; the intensity of illumination is dependent on the
charging current.
AUX- green diode: indicates the DC supply status in the output of the PSU module. Under normal status,
the diode is permanently illuminated and in case of a short-circuit or overload, the diode goes off.
3.2. Technical outputs.
The PSU module is equipped with indication outputs:
EPS - technical output indicating AC power failure.
The output indicates AC power failure. Under normal status with the AC supply on, the output is shorted
to ground GND. In case of power failure, the PSU will switch the output into hi-Z high impedance state after
a time set by the T
AC
jumper.
PSU output indicating failure PSU module.
The output indicates failure PSU module. Under normal status (correct operation) the output is shorted to
ground GND. If there is no DC voltage at the output (eg short circuit), the output is switched into hi-Z high
impedance state.
PSU failure can be caused by the following events:
- Short circuit at the output
- Output overload
- DC/DC voltage converter failure
- Under voltage protection activation
LoB output indicating low battery voltage.
The output indicates low battery voltage. Under normal status (U
BAT
> 11,5V) the output is shorted to
ground GND, when the battery voltage drops too low (U
BAT
< 11,5V) the output is switched into hi-Z high
impedance state.
The power supply technical outputs are open collector (OC) type, as shown schematically below.
Fig. 3. Electrical diagram of OC technical outputs.
www.pulsar.pl MSRK1012
7
4. Operation and use.
4.1 Overload or short circuit of the PSU module output.
The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load
of the PSU module exceeds I
max
(load 110% ÷ 150% @25ºC of the PSU module power), the output voltage is
automatically cut off and indicated by the green diode going off. To restore the output power, cut off the output load
for approximately 1 minute.
In case of of the short-circuit to the AUX, BAT output, or incorrect connection of the battery, the fuse F
BAT
in
the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the
replacement of the fuse.
4.2 Running the PSU module from the battery.
The power supply module is equipped with the button on the PCB allowing to run the PSU from the battery,
when needed. To do that, press and hold the START button on the unit board for 1 second.
4.3 Deep discharge battery protection UVP.
The power supply is equipped with deep discharge battery protection (UVP). If the voltage at the battery
terminals drops below 10V±0.5V during battery-assisted operation, the batteries will be disconnected. The battery
protection is on when the P
BAT
jumper is off.
Caution.
It is not recommended to disable UVP since deep discharge of the batteries reduces their ability to
store energy, their capacity and lifetime.
4.4 Maintenance.
Any and all maintenance operations may be performed following the disconnection of the PSU module from the
power supply network. The PSU module does not require performing any specific maintenance measures, however, in
the case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse
replacement, use a replacement of the same parameters.
www.pulsar.pl MSRK1012
8
WEEE MARK
According to the EU WEE Directive It is required not to dispose of electric or electronic waste as
unsorted municipal waste and to collect such WEEE separately.
The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled
according to the applicable law.
THE GENERAL WARRANTY CONDITIONS
1. Pulsar K. Bogusz Sp.j. (the manufacturer) grants a five-years warranty for the equipment, counted from the
device’s production date.
2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the
manufacturer’s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects,
unless such defects have been reported within the warranty period (item 1).
3. The equipment subject to warranty is to be brought to the place where it was purchased, or directly to the main
office of the manufacturer.
4. The warranty applies to complete equipment, accompanied by a properly filled warranty claim with a description
of the defect.
5. Should the claim be accepted, the manufacturer is obliged to provide warranty repairs, at the earliest
convenienve, however not later that within 14 days from the delivery to the service centre of the manufacturer.
6. The repair period mentioned in item 5 may be prolonged, if there are no technical possibilities to carry out the
repairs, or if the equipment has been conditionally accepted, due to the breaking warranty terms by the claimant.
7. All the services rendered by force of the warranty are carried out at the service centre of the manufacturer,
exclusively.
8. The warranty does not cover the defects of the equipment, resulting from:
- reasons beyond the manufacturer's control,
- mechanical damage,
- improper storage and transport,
- use that violates the operation manual or equipment’s intended use
- fortuitous events, including lightning discharges, power failures, fire, flood, high temperatures and chemical
agents,
- improper installation and configuration (in defiance with the manual),
9. The warranty is void in any of the following circumstances:
- construction changes
- repairs carried out by any unauthorized service center
- damage or removal of warranty labels
- modifications of the serial number
10. The liability of the manufacturer towards the buyer is limited to the value of the equipment, determined
according to the wholesale prices suggested by the manufacturer on the day of purchase.
11. The manufacturer takes no reponsibility for the defects that result from:
- the damaging, malfunctioning or inability to operate the equipment
- defects that result from using the equipment outside its stated specifications and operating parameters failing to
abide by the recommendations and requirements contained in the manual, or the use of the equipment.
Pulsar K.Bogusz Sp.j.
Siedlec 150, 32-744 Łapczyca, Poland
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
http:// www.pulsar.pl, www.zasilacze.pl
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Pulsar MSRK1012 - v1.0 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI