3M Power Clamp Wiremount Plug, 358 Series Operating instructions

Type
Operating instructions

This manual is also suitable for

3M
Power Clamp Wiremount Connectors
Instructions
Scope: This document describes the termination instructions for 3M
Power Clamp Wiremount Connectors Series 355 and 358.
3M Part Numbers
35505-6XX0-XXX XX
35805-6XX0-XXX XX
Applicable Documents:
TS-2273 Power Clamp Wiremount Socket, Series 355
TS-2285 Power Clamp Wiremount Plug, Series 358
March 2009
78-9100-8291-2-A
2 78-9100-8291-2-A
3M
Power Clamp Wiremount Connectors
1.0 Recommended Tools
1.1 For cable and wire cutting:
a. Standard cable and wire cutting tool which
can provide a sharp and clean cut to the
wire end
1.2 For IDC termination (Figure 1):
a. Standard slip joint pliers which can provide
a parallel closing action
b. Pliers that can provide parallel closing
action. These are the preferred tool.
Figure 1
2.0 Cable or Discrete Wire
Preparation
2.1 Cut the cable or discrete wire to desired length.
2.2 Peel the cable jacket. Expose one inch (2.5 cm)
or more of wire.
2.3 Spread out the individual wire tips to the
approximate width of the connector and trim
off wire tips so the ends of the wire are even
when inserted into the connector. Wire should
be cut clean and have minimal deformation at
wire tip.
2.4 Verify wire gauge and diameter matches
specifications for connector. Each connector
is marked with appropriate wire gauge and
wire diameter range. This information can also
be found on the product technical data sheets
or drawings.
Figure 2
3.0 Wire Insertion
3.1 When electric wire is thin, it can easily be
inserted while the cover is in the horizontal
position. Insert the wire (Figure 3).
Figure 3
3.2 When the electric wire is thick, the insulation
displacement contacts (IDC) inside the cover
may interfere with wire insertion. If this
occurs, the cover can be raised at an angle to
eliminate interference (Figures 4 and 5).
a. Raise the cover.
b. Insert the electric wires.
c. Carefully return the cover to the original
horizontal position. Each IDC should align
with the opening in the cover. Do not force
the cover as this may bend the IDCs.
78-9100-8291-2-A 3
3M
Power Clamp Wiremount Connectors
Figure 4
Cover
Body
IDC
Figure 5
3.3 Position the electric wire so that it is fully
inserted into the cover. Wires should be even
or flush with the back edge of the cover
(Figure 6).
Figure 6 - Cutaway Section
4.0 Termination to IDC
4.1 Using one of the recommended tools, apply
pressure to the center of the cover. The cover
should move vertically into the connector body
(Figures 7, 8, 9 and 10). The most effective
tool is a parallel-jaw type pliers as seen in
Figure 11.
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
4 78-9100-8291-2-A
3M
Power Clamp Wiremount Connectors
4.2 After pushing the cover center, use the pliers to
vertically push down both edges of the cover
(Figures 12 and 13).
Figure 12
Figure 13
5.0 Verification and Inspection
5.1 The cover edges contain latches that provide
retention of the cover to the body. Verify the
latches are engaged on both the left and right
cover edges (Figures 14 and 15).
Figure 14
Figure 15
5.2 The cover should be fully seated into the body.
The top of the cover should be flush with
the top of the connector body on front, back,
left and right edges. If the cover is not fully
seated or latches not fully engage, then press
with pliers again to securely engage the cover
(Figures 16 and 17).
Figure 16 - Defective State
Figure 17 - Acceptable State
78-9100-8291-2-A 5
3M
Power Clamp Wiremount Connectors
3M Power Clamp Connector
TYPE-B (35505-6XX0-BXX
XX, 35805-6XX0-BXX XX)
Special Instructions
The 3M Power Clamp Connector TYPE-B is intended
for use for shielded cable with a drain wire. It can be
used for cables without drain wires or discrete wire
as well. The connector may terminate up to three
insulated wires and one uninsulated drain wire.
Figure 18
Figure 19
6.0 Recommended Tools
6.1 Same as section 1.0 above.
7.0 Cable or Discrete Wire
Preparation
7.1 Same as section 2.0. Additionally:
a. Remove braided or foil shield to edge of
cable jacket. Do not cut the drain wire.
b. Using finger, twist uninsulated drain wire
seven or more times until the individual
strands are tightly wound. Insure all debris
is removed from the drain wire.
Figure 20
Figure 21
8.0 Wire Insertion
8.1 Same as section 3.0. Additionally:
a. Position wire into the appropriate hole per
the following table:
Position
Cover
Marking
CC-Link Applications
Wire Description
Custom Application
Wire Description
1 B DA Blue Insulated Wire Insulated Wire
2 W DB White Insulated Wire Insulated Wire
3 Y DG Yellow Insulated Wire Insulated Wire
4 NC None – No Connect None – No Connect
5 SLD Drain Wire Drain Wire
9.0 Termination to IDC
9.1 Follow section 4.0.
Figure 22
10.0 Verification and Inspection
10.1 Follow section 5.0.
3M is a trademark of 3M Company.
Important Notice
All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable,
but the accuracy or completeness is not guaranteed.
Before using this product, you must evaluate it and determine if it is suitable for
your intended application.
You assume all risks and liability associated with such use.
Any statements related to the product which are not
contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless
expressly agreed upon, in writing, by an authorized officer of 3M.
Warranty; Limited Remedy; Limited Liability.
This product will be free from defects in material and manufacture for a period of one (1) year from the time of purchase.
3M MAKES NO
OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR
A PARTICULAR PURPOSE.
If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's
option, to replace or repair the 3M product or refund the purchase price of the 3M product.
Except where prohibited by law, 3M will
not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of
the legal theory asserted.
3
Electronic Solutions Division
Interconnect Products
6801 River Place Blvd.
Austin, TX 78726-9000
800-225-5373
www.3M.com/interconnects
Please Recycle. Printed in USA.
© 3M 2009. All Rights Reserved.
78-9100-8291-2-A
Technical Assistance
Please contact 3M Customer Service should you need additional assistance.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

3M Power Clamp Wiremount Plug, 358 Series Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI