Haier MRV WATER User guide

Category
Split-system air conditioners
Type
User guide
SYJS-05-2016 REV.A Edition: 2016-05
Service Manual
MRV W (380V)
CONTENTS
1. General Information ................................................................................................................................ 1
1.1 Safety ................................................................................................................................................. 1
1.2 Feature ............................................................................................................................................... 3
1.3 Products Lineup .................................................................................................................................. 6
2. Specication ........................................................................................................................................... 8
3. Dimension ............................................................................................................................................ 18
3.1 Single unit ......................................................................................................................................... 18
3.2 Combination unit ............................................................................................................................... 19
4. Piping diagram...................................................................................................................................... 23
5. Wiring diagram ..................................................................................................................................... 25
6. Operation range.................................................................................................................................... 26
7. Sound pressure level ............................................................................................................................ 27
8. Capacity Calculation Due to Capacity Modication Coefcient ............................................................ 28
9. Installation ............................................................................................................................................ 32
10. Branch pipe dimension ....................................................................................................................... 65
11. Gather pipe dimension ........................................................................................................................ 66
12. Outdoor PCB photo ............................................................................................................................ 67
13. Outdoor PCB dip switch setting .......................................................................................................... 68
14. Outdoor unit control ............................................................................................................................ 81
14.1 Compressor startup control ............................................................................................................ 81
14.2 Compressor operation control ........................................................................................................ 81
14.3 Oil return operation control ............................................................................................................. 81
14.4 SV1 control ..................................................................................................................................... 81
14.5 SV6 control ..................................................................................................................................... 81
15. Failure code ........................................................................................................................................ 82
16. Troubleshooting .................................................................................................................................. 88
Appendix I Accessories List ................................................................................................................... 132
Appendix II Sensor Resistance Table ..................................................................................................... 134
Appendix III Enthalpy-Humidity Chart..................................................................................................... 143
1
General Information
• This manual should always be accessible and close to this air condition equipment.
There are two types of indications, " WARNING" and " CAUTION". The indication preventing from death
or heavy injury is listed as " WARNING". Even the indication listed as " CAUTION" may also cause serious
accident. Both of them are related to safety, and should be strictly followed.
•After installation and start-up commissioning, please handover the manual to the user. The manual should be well
kept in safe place and close to the unit.
The installation or the maintenance should be performed by an authorized agency. The wrong operation of this air
condition equipment may cause water leakage, electric shock or re.
• Please install the unit on the top of a solid foundation or structure which is strong enough to support the unit.
• The installation of this air condition equipment should follow local construction codes.
Use the right cable size, secure the terminal rmly, organize the cables well and make sure no tension is added
on cables. Cable insulation should not be damaged. The incorrect installation may lead to overheat or re.
• Must install leakage protection switch, or it will cause electric shock.
• Please install the ow switch which in the outdoor accessory in the middle of the outlet pipe.
In winter, if you do not use for short periods of time, please ensure the machine 24 hours power on, if you do not
use for a long time, please sent out the water in the system, prevent frost crack system.
When installing or moving the unit, the refrigerant system should be vacuumed and recharged with R410A
refrigerant. If any other gas enters the system, it may lead to abnormal high pressure which may cause damage or
injury.
Please use the proper manifolds or branches during the system installation. The wrong parts may cause
refrigerant leakage.
• Keep the drain pipe away from toxic gas vents to prevent possible pollution of indoor environment.
During or after the installation, please check whether there is refrigerant leakage. If any leakage, please take any
measures for ventilation. The refrigerant may be toxic at some concentration levels. The unit connect with closed
water system
• The unit is not explosion-proof. Please keep it away from ammable gases.
The water pipe should be installed per this manual to ensure proper drainage. The pipe should be well insulated
to avoid condensation. Wrong installation may lead to water leakage.
Both liquid pipe and the gas pipe should be also well insulated. Not enough insulation may lead to system
performance deterioration or humidity formation.
• This air condition equipment is not intended to be operated by persons with lack of experience and training, unless
they have supervision or instruction concerning use of this air condition equipment.
• Please keep children away from this air condition equipment.
• The grade of waterproof and dustproof is IPX0, Please pay attention to waterproof.
WARNING
1. General Information
1.1 Safety
2
Grounding wire should be connected with the grounding bar. The grounding wire can not be connected to the gas
pipe, water pipe, lightening rod or the telephone grounding wire. Improper grounding may cause electric shock.
• Units installed on roof should have appropriate access and handrail.
Use the wrench to fasten the nut and are at proper torque. Excessive torque may cause ared section to broke
leading to refrigerant leakage.
After refrigerant pipe installation, please take nitrogen leakage test to avoid refrigerant leakage.
• R410A is the only permitted refrigerant.
To avoid mischarging wrong refrigerant, the check valve diameter is changed for R410A. To strengthen the pipe,
the ared pipe dimension is also changed. Please use R410A specied tools as shown below.
When charging refrigerant, the refrigerant must be in liquid state from the tank.
To prevent EMC interference on other appliances, please keep indoor unit, outdoor unit, power cable and
connecting wire at least 1m away from those appliances.
Fluorescent lamp (reverse phase or rapid start type) may interfere with the remote controller's signal. Please
install indoor unit away from uorescent lamp. The farther the better.
• The temperature and ow of the outdoor unit inlet water need to conform to the requirements of the specication,
the water temperature is too low or the water is too small will cause the unit malfunction.
The water pipe network including water lter and tube heat exchanger need to regularly clean, otherwise it will
decrease the capacity.
• The quality of the circulating water must conform to the specications. otherwise it will decrease the system life.
R410A specied tools Remarks
1 Gauge manifold Range: HP>4.5MPa,LP>2MPa
2 Charge hose Pressure: HP 5.3MPa, LP 3.5MPa
3 Electronic weight for charging R410A No other means permitted
4Torque wrench
5 Flare tool
6 Copper pipe gauge for adjusting projecting margin
7Vacuum pump tting Vacuum pump must be equipped with check valve
8 Leakage detector Only Helium detector permitted
CAUTION
3
General Information
1.2.2 Double EEVs control
The double EEVs control the 2 stages heat exchanger separately, which can adjust the condenser volume and
optimize system performance.
1.2.3 Energy Saving: Heat recovery between different refrigerant system
Heat recovery is achieved within the water loop among different refrigerant systems, higher whole system efciency
due to cooling and heating simultaneously in different refrigerant systems.
1.2 Feature
1.2.1 User friendly outdoor structure
Compact inner structure and core parts.
4
f i l
50
45
45
40
Temperature range o
f
water
i
n
l
et
745
45
40
35
Condensing unit ambient
temperature range
30
25
040
Temperature range of indoor
20
15
10
7
Cooling:1927
(Heating: 1520)
The condensing unit water flow range is
50
min
Standard 96L/min)
5
0
7
0
50
min
Standard 96L/min)
1.2.5 Water pump controlled together with the outdoor
The reserved water pump linkage control realizes the pump linkage control, reduces the energy consumption and
eliminates hidden risks.
1.2.6 High reliability
Wide operation range
1.2.7 High convenience (use/installation/service)
Various mode and priority selection.
The outdoor units are smaller and can be staked, reducing the installation space and increasing the customers
usable space.
5
General Information
Operation Range of Air Conditioner
Condition Cooling Heating
Outdoor Environment temperature 0-40°C
Outdoor Environment humidity <80%
Indoor Temperature 17-32°C 15-30°C
Water Inlet Temperature 7-45°C
Rated water ow
8HP: 4.8m3/h
10HP: 6.0m3/h
12HP:7.2m3/h
1.2.10 Reliable performance
a. High COP
High efciency and great energy saving are always the purchased aim for each Haier air conditioning system. Haier
MRV has been designed to get high COP from the reasonable structure and the excellent electric system
COP
8HP 6.02
10HP 5.43
12HP 4.81
b. Approved for RoHS certicate
All the parts in the unit have been approved for RoHS certicate. The parts are in conformance with RoHS directive.
Thus Haier MRV will be environmental for human and nature.
The directive is to approximate the laws of the Member States on the restrictions of the use of hazardous
substances in electrical and electronic equipment and to contribute to the protection of human health and the
environmentally sound recovery and disposal of waste electrical and electronic equipment.
C. Operation condition:
To use the air conditioner normally. Please perform as to the below conditions.
1.2.8 Easier maintenance
a. Backup operation
If one outdoor unit malfunction happens, the other units provide emergent operation until repair achieved.
b. Auto check function.
Failure codes displayed by LED in outdoor PCB or controllers are so detailed for us to find the fail place more
quickly, and can judge the failure content easily.
6
1.3 Products Lineup
1.3.1 Outdoor Units
Appearance Power supply
(Ph, V, Hz) Model Capacity(kW) Refrigerant
3Ph, 380-400V,
50/60HZ
AV08IMWEWA 22.4
R410A
AV10IMWEWA 28
AV12IMWEWA 33.5
AV16IMWEWA 44.8
AV18IMWEWA 50.4
AV20IMWEWA 56
AV22IMWEWA 61.5
AV24IMWEWA 67.0
AV26IMWEWA 72.8
AV28IMWEWA 78.4
AV30IMWEWA 84.0
AV32IMWEWA 89.5
AV34IMWEWA 95.0
AV36IMWEWA 100.5
7
General Information
1.3.2 Indoor units lineup
4-WAY CASSETTE TYPE/PB-700lB
AB092MCERA
AB122MCERA
AB162MCERA
HIGH WALL EEV INSIDE
AS072MGERA AS162MGERA
AS092MGERA AS182MGERA
AS122MGERA AS242MGERA
4-WAY CASSETTE TYPE/PB-950JB
AB182MCERA
AB242MCERA
AB282MCERA
AB302MCERA
AB382MCERA
AB482MCERA
MED ESP DUCT TYPE (80/120Pa)
AD182MZERA
AD242MZERA
AD282MZERA
AD302MNERA
AD382MNERA
AD482MNERA
LOW ESP DUCT TYPE
AD072MLERA
AD092MLERA
AD122MLERA
AD162MLERA
AD182MLERA
AD242MLERA
MED ESP DUCT TYPE (50/96Pa)
AD182MMERA
AD242MMERA
AD282MMERA
AD302MMERA
AD382MMERA
AD482MMERA
HlGH ESP DUCT TYPE
AD182MHERA
AD242MHERA
AD282MHERA
AD302MHERA
AD382MHERA
AD482MHERA
AD722MHERA
AD962MHERA
CONVERTlBLE TYPE
AC092MCERA
AC122MCERA
AC162MCERA
AC182MCERA
AC242MCERA
AC282MFERA
AC302MFERA
AC382MFERA
AC482MFERA
SLIM LOW ESP DUCT
AD072MSERA
AD092MSERA
AD122MSERA
AD162MSERA
AD182MSERA
AD242MSERA
BUILIT-IN FLOOR STANDING
AE072MLERA
AE092MLERA
AE122MLERA
AE162MLERA
AE182MLERA
AE242MLERA
2-WAY CASSETTE/1055IB
AB072MBERA
AB092MBERA
AB122MBERA
AB162MBERA
AB182MBERA
CONSOLE TYPE
AF072MAERA
AF092MAERA
AF122MAERA
AF182MAERA
ROUND-WAY SMART AIR FLOW CASSETTE/ PB-950KC
AB072MRERA
AB092MRERA
AB122MRERA
AB162MRERA
AB182MRERA
AB242MRERA
AB282MRERA
AB302MRERA
AB382MRERA
AB482MRERA
AB602MRERA
DC SLIM LOW ESP DUCT
AD072MSERA(D)
AD092MSERA(D)
AD122MSERA(D)
AD162MSERA(D)
AD182MSERA(D)
AD242MSERA(D)
8
2. Specication
Model AV08IMWEWA AV10IMWEWA AV12IMWEWA
Equivalent HP 8 10 12
Combination model / / /
Power supply V-Ph-
Hz 3~/380-400/50/60 3~/380-400/50/60 3~/380-400/50/60
Cooling
Rated capacity kW 22.4 28 33.5
Rated capacity kBtu/h 76.4 95.5 114.3
Rated power input kW 4.5 6.00 7.70
Max. power input kW 13.00 15.00 17.00
EER 4.98 4.67 4.35
Rated current A 7.20 9.60 12.32
Max. current A 20.79 23.99 27.19
Heating
Rated capacity kW 25 31.5 37.5
Rated capacity kBtu/h 85.3 107.5 128.0
Rated power input kW 4.15 5.80 7.80
Max. power input kW 13.00 15.00 17.00
EER 6.02 5.43 4.81
Rated current A 6.64 9.28 12.47
Max. current A 20.79 23.99 27.19
Compressor
Brand MITSUBISH
ELECTRIC
MITSUBISH
ELECTRIC
MITSUBISH
ELECTRIC
Model ANB66F ANB66F ANB66F
Type DC INV. SCROLL DC INV. SCROLL DC INV. SCROLL
Capacity W 22000 22000 22000
Power input W 6500 6500 6500
Rated current (RLA) A 23.7 23.7 23.7
Speed rps 60 60 60
Crankcase heater W 38 38 38
Refrigerant oil brand ITOCHU
CORPORATION
ITOCHU
CORPORATION
ITOCHU
CORPORATION
Refrigerant oil type FVC68D FVC68D FVC68D
Refrigerant oil charge ml 2300+1000 2300+1000 2300+1000
Heat
exchanger
Material Cooper Cooper Cooper
Type Axial Axial Axial
9
Specication
Model AV08IMWEWA AV10IMWEWA AV12IMWEWA
Heat
exchanger
Water ow rate range m³/h 2.4-7.2 3.0-9.0 3.6-10.8
Water pressure drop kPa 35 50 70
Max water pressure MPa 1.6 1.6 1.6
Inlet/Outlet water
connection pipe mm DN32 DN32 DN32
Connection type /
model Inch Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Control panel enclosure IP class Standard IPX0 IPX0 IPX0
Outdoor sound level (sound pressure
level) dB (A) 50 51 53
Outdoor sound level (sound power
level) dB (A) 61 62 64
Outdoor
unit
Dimension (W*H*D) mm 775×545x995 775×545x995 775×545x995
Packing (W*H*D) mm 875×655×1182 875×655×1182 875×655×1182
Net weight kg 172 172 172
Gross weight kg 183 183 183
Refrigerant Type R410A R410A R410A
Charged volume*3 kg 2 2 2
Throttle type EXV EXV EXV
Design pressure MPa 4.15 4.15 4.15
Refrigerant
piping
Liquid pipe mm Ф9.52 Ф9.52 Ф12.7
Gas pipe mm Ф19.05 Ф22.2 Ф25.4
Oil pipe mm Ф9.52 Ф9.52 Ф9.52
Total pipe lenth m 300 300 300
Max. pipe length
(Equivalent/ Actual) m150/120 150/120 150/120
Max.Diff. indoor/
outdoor unit m
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher
than outdoor)
Max.Diff. indoor/indoor
unit m 15 15 15
Connectable indoor unit ratio % 50-130 50-130 50-130
Maximum indoor units Piece 13 16 19
Connection
wiring
Power wiring mm ² 6 10 10
Signal wiring mm² Shield wire(0.75-
2)*2
Shield wire(0.75-
2)*2
Shield wire(0.75-
2)*2
Operation range °C Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
10
Model AV16IMWEWA AV18IMWEWA AV20IMWEWA
Equivalent HP 16 18 20
Combination model 08+08 08+10 10+10
Power supply V-Ph-
Hz 3~/380-400/50/60 3~/380-400/50/60 3~/380-400/50/60
Cooling
Rated capacity kW 44.8 50.4 56
Rated capacity kBtu/h 152.9 172.0 191.1
Rated power input kW 9.00 10.50 12.00
Max. power input kW 26.00 28.00 30.00
EER 4.98 4.80 4.67
Rated current A 14.39 16.79 19.19
Max. current A 41.58 44.78 47.98
Heating
Rated capacity kW 50.0 56.5 63
Rated capacity kBtu/h 170.6 192.8 215.0
Rated power input kW 8.30 9.95 11.60
Max. power input kW 26.00 28.00 30.00
EER 6.02 5.68 5.43
Rated current A 13.27 15.91 18.55
Max. current A 41.58 44.78 47.98
Compressor
Brand MITSUBISH
ELECTRIC
MITSUBISH
ELECTRIC
MITSUBISH
ELECTRIC
Model ANB66F+ANB66F ANB66F+ANB66F ANB66F+ANB66F
Type DC INV. SCROLL DC INV. SCROLL DC INV. SCROLL
Capacity W 22000+22000 22000+22000 22000+22000
Power input W 6500+6500 6500+6500 6500+6500
Rated current (RLA) A 23.7+23.7 23.7+23.7 23.7+23.7
Speed rps 60 60 60
Crankcase heater W 38+38 38+38 38+38
Refrigerant oil brand ITOCHU
CORPORATION
ITOCHU
CORPORATION
ITOCHU
CORPORATION
Refrigerant oil type FVC68D FVC68D FVC68D
Refrigerant oil charge ml (2300+1000)*2 (2300+1000)*2 (2300+1000)*2
Heat
exchanger
Material Cooper Cooper Cooper
Type Axial Axial Axial
11
Specication
Model AV16IMWEWA AV18IMWEWA AV20IMWEWA
Heat
exchanger
Water ow rate
range m³/h 2.4-7.2+2.4-7.2 2.4-7.2+3.0-9.0 3.0-9.0+3.0-9.0
Water pressure drop kPa 35+35 35+50 50+50
Max water pressure MPa 1.6 1.6 1.6
Inlet/Outlet water
connection pipe mm DN32 DN32 DN32
Connection type /
model Inch Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Control panel enclosure IP class Standard IPX0 IPX0 IPX0
Outdoor sound level (sound
pressure level) dB (A) 53 54 54
Outdoor sound level (sound power
level) dB (A) 64 65 65
Outdoor
unit
Dimension (W*H*D) mm (775×545×995)*2 (775×545×995)*2 (775×545×995)*2
Packing (W*H*D) mm (875×655×1182)*2 (875×655×1182)*2 (875×655×1182)*2
Net weight kg 344 344 344
Gross weight kg 366 366 366
Refrigerant Type R410A R410A R410A
Charged volume*3 kg 2+2 2+2 2+2
Throttle type EXV EXV EXV
Design pressure MPa 4.15+4.15 4.15+4.15 4.15+4.15
Refrigerant
piping
Liquid pipe mm Ф12.7 Ф15.88 Ф15.88
Gas pipe mm Ф28.58 Ф28.58 Ф28.58
Oil pipe mm Ф9.52 Ф9.52 Ф9.52
Total pipe lenth m 300 300 300
Max. pipe length
(Equivalent/ Actual) m150/120 150/120 150/120
Max.Diff. indoor/
outdoor unit m
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
Max.Diff. indoor/
indoor unit m 15 15 15
Connectable indoor unit ratio % 50-130 50-130 50-130
Maximum indoor units Piece 23 29 33
Connection
wiring
Power wiring mm ² 12 16 20
Signal wiring mm² Shield wire
(0.75-2)*2 Shield wire
(0.75-2)*2 Shield wire
(0.75-2)*2
Operation range °C Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
12
Model AV22IMWEWA AV24IMWEWA AV26IMWEWA
Equivalent HP 22 24 26
Combination model 10+12 12+12 08+08+10
Power supply V-Ph-
Hz 3~/380-400/50/60 3~/380-400/50/60 3~/380-400/50/60
Cooling
Rated capacity kW 61.5 67.0 72.8
Rated capacity kBtu/h 209.8 228.6 248.4
Rated power input kW 13.70 15.40 15.00
Max. power input kW 32.00 34.00 41.00
EER 4.49 4.35 4.85
Rated current A 21.91 24.63 23.99
Max. current A 51.18 54.38 65.57
Heating
Rated capacity kW 69.0 75.0 81.5
Rated capacity kBtu/h 235.4 255.9 278.1
Rated power input kW 13.60 15.60 14.10
Max. power input kW 32.00 34.00 41.00
EER 5.07 4.81 5.78
Rated current A 21.75 24.95 22.55
Max. current A 51.18 54.38 65.57
Compressor
Brand MITSUBISH
ELECTRIC
MITSUBISH
ELECTRIC MITSUBISH ELECTRIC
Model ANB66F+ANB66F ANB66F+ANB66F ANB66F+(ANB66F)
+(ANB66F)
Type DC INV. SCROLL DC INV. SCROLL DC INV. SCROLL
Capacity W 22000+22000 22000+22000 22000+(22000)+
(22000)
Power input W 6500+6500 6500+6500 6500+(6500)+(6500)
Rated current
(RLA) A 23.7+23.7 23.7+23.7 23.7+(23.7)+(23.7)
Speed rps 60 60 60
Crankcase heater W 38+38 38+38 38+(38)+(38)
Refrigerant oil
brand
ITOCHU
CORPORATION
ITOCHU
CORPORATION
ITOCHU
CORPORATION
Refrigerant oil type FVC68D FVC68D FVC68D
Refrigerant oil
charge ml (2300+1000)*2 (2300+1000)*2 (2300+1000)*3
Heat
exchanger
Material Cooper Cooper Cooper
Type Axial Axial Axial
13
Specication
Model AV22IMWEWA AV24IMWEWA AV26IMWEWA
Heat
exchanger
Water ow rate
range m³/h 3.0-9.0+3.6-10.8 3.6-10.8+3.6-10.8 2.4-7.2+(2.4-
7.2)+(3.0-9.0)
Water pressure
drop kPa 50+70 70+70 35+(35)+(50)
Max water pressure MPa 1.6 1.6 1.6
Inlet/Outlet water
connection pipe mm DN32 DN32 DN32
Connection type /
model Inch Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Control panel enclosure IP class Standard IPX0 IPX0 IPX0
Outdoor sound level (sound
pressure level) dB (A) 55 56 55
Outdoor sound level (sound
power level) dB (A) 66 67 66
Outdoor
unit
Dimension (W*H*D) mm (775×545×995)*2 (775×545×995)*2 (775×545×995)*3
Packing (W*H*D) mm (875×655×1182)*2 (875×655×1182)*2 (875×655×1182)*3
Net weight kg 344 344 516
Gross weight kg 366 366 549
Refrigerant Type R410A R410A R410A
Charged volume*3 kg 2+2 2+2 2+(2)+(2)
Throttle type EXV EXV EXV
Design pressure MPa 4.15+4.15 4.15+4.15 4.15+(4.15)+(4.15)
Refrigerant
piping
Liquid pipe mm Ф15.88 Ф15.88 Ф19.05
Gas pipe mm Ф28.58 Ф28.58 Ф31.8
Oil pipe mm Ф9.52 Ф9.52 Ф9.52
Total pipe lenth m 300 300 300
Max. pipe length
(Equivalent/ Actual) m150/120 150/120 150/120
Max.Diff. indoor/
outdoor unit m
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
Max.Diff. indoor/
indoor unit m 15 15 15
Connectable indoor unit ratio % 50-130 50-130 50-130
Maximum indoor units Piece 36 39 43
Connection
wiring
Power wiring mm ² 20 20 22
Signal wiring mm² Shield wire
(0.75-2)*2 Shield wire
(0.75-2)*2 Shield wire
(0.75-2)*2
Operation range °C Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
14
Model AV28IMWEWA AV30IMWEWA AV32IMWEWA
Equivalent HP 28 30 32
Combination model 08+10+10 10+10+10 10+10+12
Power supply V-Ph-
Hz 3~/380-400/50/60 3~/380-400/50/60 3~/380-400/50/60
Cooling
Rated capacity kW 78.4 84.0 89.5
Rated capacity kBtu/h 267.5 286.6 305.4
Rated power input kW 16.50 18.00 19.70
Max. power input kW 43.00 45.00 47.00
EER 4.75 4.67 4.54
Rated current A 26.39 28.79 31.51
Max. current A 68.77 71.97 75.17
Heating
Rated capacity kW 88.0 94.5 100.5
Rated capacity kBtu/h 300.3 322.4 342.9
Rated power input kW 15.75 17.40 19.40
Max. power input kW 43.00 45.00 47.00
EER 5.59 5.43 5.18
Rated current A 25.19 27.83 31.03
Max. current A 68.77 71.97 75.17
Compressor
Brand MITSUBISH ELECTRIC
Model ANB66F*3 ANB66F*3 ANB66F*3
Type DC INV. SCROLL DC INV. SCROLL DC INV. SCROLL
Capacity W22000+(22000)+(22000)
Power input W6500+(6500)+(6500) 6500+(6500)+(6500) 6500+(6500)+(6500)
Rated current (RLA) A23.7+(23.7)+(23.7) 23.7+(23.7)+(23.7) 23.7+(23.7)+(23.7)
Speed rps 60 60 60
Crankcase heater W38+(38)+(38) 38+(38)+(38) 38+(38)+(38)
Refrigerant oil
brand
ITOCHU
CORPORATION
ITOCHU
CORPORATION
ITOCHU
CORPORATION
Refrigerant oil type FVC68D FVC68D FVC68D
Refrigerant oil
charge ml (2300+1000)*3 (2300+1000)*3 (2300+1000)*3
Heat
exchanger
Material Cooper Cooper Cooper
Type Axial Axial Axial
15
Specication
Model AV28IMWEWA AV30IMWEWA AV32IMWEWA
Heat
exchanger
Water ow rate
range m³/h 2.4-7.2+(3.0-
9.0)+(3.0-9.0)
3.0-9.0+(3.0-
9.0)+(3.0-9.0)
3.0-9.0+(3.0-
9.0)+(3.6-10.8)
Water pressure
drop kPa 35+(50)+(50) 50+(50)+(50) 50+(50)+(70)
Max water pressure MPa 1.6 1.6 1.6
Inlet/Outlet water
connection pipe mm DN32 DN32 DN32
Connection type /
model Inch Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Inner Thread / G 1
1/4"
Control panel enclosure IP class Standard IPX0 IPX0 IPX0
Outdoor sound level (sound
pressure level) dB (A) 55 56 57
Outdoor sound level (sound
power level) dB (A) 66 67 68
Outdoor
unit
Dimension
(W*H*D) mm (775×545×995)*3 (775×545×995)*3 (775×545×995)*3
Packing (W*H*D) mm (875×655×1182)*3 (875×655×1182)*3 (875×655×1182)*3
Net weight kg 516 516 516
Gross weight kg 549 549 549
Refrigerant Type R410A R410A R410A
Charged volume*3 kg 2+(2)+(2) 2+(2)+(2) 2+(2)+(2)
Throttle type EXV EXV EXV
Design pressure MPa 4.15+(4.15)+(4.15) 4.15+(4.15)+(4.15) 4.15+(4.15)+(4.15)
Refrigerant
piping
Liquid pipe mm Ф19.05 Ф19.05 Ф19.05
Gas pipe mm Ф31.8 Ф31.8 Ф31.8
Oil pipe mm Ф9.52 Ф9.52 Ф9.52
Total pipe lenth m 300 300 300
Max. pipe length
(Equivalent/ Actual) m150/120 150/120 150/120
Max.Diff. indoor/
outdoor unit m
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
50(Outdoor higher
than indoor)
40(Indoor higher than
outdoor)
Max.Diff. indoor/
indoor unit m 15 15 15
Connectable indoor unit ratio % 50-130 50-130 50-130
Maximum indoor units Piece 46 50 53
Connection
wiring
Power wiring mm ² 26 30 30
Signal wiring mm² Shield wire
(0.75-2)*2 Shield wire
(0.75-2)*2 Shield wire
(0.75-2)*2
Operation range °C Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
Circulating water
inlet7°C 45°C
16
Model AV34IMWEWA AV36IMWEWA
Equivalent HP 34 36
Combination model 10+12+12 12+12+12
Power supply V-Ph-
Hz 3~/380-400/50/60 3~/380-400/50/60
Cooling
Rated capacity kW 95.0 100.5
Rated capacity kBtu/h 324.1 342.9
Rated power input kW 21.40 23.10
Max. power input kW 49.00 51.00
EER 4.44 4.35
Rated current A 34.23 36.95
Max. current A 78.37 81.57
Heating
Rated capacity kW 106.5 112.5
Rated capacity kBtu/h 363.4 383.9
Rated power input kW 21.40 23.40
Max. power input kW 49.00 51.00
EER 4.98 4.81
Rated current A 34.23 37.42
Max. current A 78.37 81.57
Compressor
Brand MITSUBISH ELECTRIC MITSUBISH ELECTRIC
Model ANB66F+(ANB66F)+(ANB66F) ANB66F+(ANB66F)+(ANB66F)
Type DC INV. SCROLL DC INV. SCROLL
Capacity W22000+(22000)+(22000) 22000+(22000)+(22000)
Power input W6500+(6500)+(6500) 6500+(6500)+(6500)
Rated current (RLA) A23.7+(23.7)+(23.7) 23.7+(23.7)+(23.7)
Speed rps 60 60
Crankcase heater W38+(38)+(38) 38+(38)+(38)
Refrigerant oil brand ITOCHU CORPORATION ITOCHU CORPORATION
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml (2300+1000)*3 (2300+1000)*3
Heat
exchanger
Material Cooper Cooper
Type Axial Axial
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148

Haier MRV WATER User guide

Category
Split-system air conditioners
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI