Eaton PowerXL fieldbus connection DeviceNET for DA1 drive DX-NET-DEVICENET Owner's manual

Type
Owner's manual

This manual is also suitable for

Manual
PowerXL
DX-NET-DEVICENET
Field bus connection DeviceNet
or Variable Frequency Drives DA1
02/14 MN04012005Z-EN
All brand and product names are trademarks or registered trademarks of the owner
concerned.
Emergency On Call Service
Please call your local representative:
http://www.eaton.eu/aftersales
or
Hotline of the After Sales Service:
+49 (0) 180 5 223822 (de, en)
AfterSalesEGBo[email protected]
For customers in US/Canada contact:
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance with placing an order,
stock availability or proof of shipment, expediting an existing order, emergency ship-
ments, product price information, returns other than warranty returns, and informa-
tion on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m. – 6:00 p.m. EST)
After-Hours Emergency: 800-543-7038 (6:00 p.m. – 8:00 a.m. EST)
Drives Technical Resource Center
Voice: 877-ETN-CARE (386-2273) option 2, option 6
(8:00 a.m. – 5:00 p.m. Central Time U.S. [UTC-6])
www.eaton.com/drives
Original Operating Instructions
The German-language edition of this document is the original operating manual.
Translation of the original operating manual
All editions of this document other than those in German language are translations of
the original German manual.
1
st
published 2014, edition date 02/14
© 2014 by Eaton Industries GmbH, 53105 Bonn
Production: René Wiegand
Translation: globaldocs GmbH
All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm
or any other process) or processed, duplicated or distributed by means of electronic
systems without written permission of Eaton Industries GmbH, Bonn.
Subject to alteration without notice.
Rückenbreite festlegen! (1 Blatt = 0,106 mm, gilt nur für XBS)
(1 Blatt = 0,080 mm für Eberwein Digitaldruck bei 80 g/m
2
)
I
Before commencing the installation
Disconnect the power supply of the device.
Ensure that devices cannot be accidentally restarted.
Verify isolation from the supply.
Earth and short circuit the device.
Cover or enclose any adjacent live components.
Follow the engineering instructions (AWA/IL) for the
device concerned.
Only suitably qualified personnel in accordance with
EN 50110-1/-2 (VDE 0105 Part 100) may work on this
device/system.
Before installation and before touching the device ensure
that you are free of electrostatic charge.
The functional earth (FE, PES) must be connected to the
protective earth (PE) or the potential equalisation. The
system installer is responsible for implementing this
connection.
Connecting cables and signal lines should be installed so
that inductive or capacitive interference does not impair
the automation functions.
Install automation devices and related operating elements
in such a way that they are well protected against
unintentional operation.
Suitable safety hardware and software measures should
be implemented for the I/O interface so that an open
circuit on the signal side does not result in undefined
states in the automation devices.
Ensure a reliable electrical isolation of the extra-low
voltage of the 24 V supply. Only use power supply units
complying with IEC 60364-4-41 (VDE 0100 Part 410) or
HD384.4.41 S2.
Deviations of the mains voltage from the rated value must
not exceed the tolerance limits given in the specifications,
otherwise this may cause malfunction and dangerous
operation.
Emergency stop devices complying with IEC/EN 60204-1
must be effective in all operating modes of the automation
devices. Unlatching the emergency-stop devices must not
cause a restart.
Devices that are designed for mounting in housings or
control cabinets must only be operated and controlled
after they have been installed and with the housing
closed. Desktop or portable units must only be operated
and controlled in enclosed housings.
Measures should be taken to ensure the proper restart of
programs interrupted after a voltage dip or failure. This
should not cause dangerous operating states even for a
short time. If necessary, emergency-stop devices should
be implemented.
Wherever faults in the automation system may cause
injury or material damage, external measures must be
implemented to ensure a safe operating state in the event
of a fault or malfunction (for example, by means of
separate limit switches, mechanical interlocks etc.).
Depending on their degree of protection, frequency
inverters may contain live bright metal parts, moving or
rotating components or hot surfaces during and
immediately after operation.
Removal of the required covers, improper installation or
incorrect operation of motor or frequency inverter may
cause the failure of the device and may lead to serious
injury or damage.
The applicable national accident prevention and safety
regulations apply to all work carried on live frequency
inverters.
The electrical installation must be carried out in
accordance with the relevant regulations (e. g. with
regard to cable cross sections, fuses, PE).
Transport, installation, commissioning and maintenance
work must be carried out only by qualified personnel
(IEC 60364, HD 384 and national occupational safety
regulations).
Installations containing frequency inverters must be
provided with additional monitoring and protective
devices in accordance with the applicable safety
regulations. Modifications to the frequency inverters
using the operating software are permitted.
All covers and doors must be kept closed during
operation.
To reduce the hazards for people or equipment, the user
must include in the machine design measures that restrict
the consequences of a malfunction or failure of the drive
(increased motor speed or sudden standstill of motor).
These measures include:
Other independent devices for monitoring safety-
related variables (speed, travel, end positions etc.).
Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks).
Never touch live parts or cable connections of the
frequency inverter after it has been disconnected from
the power supply. Due to the charge in the capacitors,
these parts may still be live after disconnection. Fit
appropriate warning signs.
Eaton Industries GmbH
Safety instructions
Danger!
Dangerous electrical voltage!
II
DX-NET-DEVICENET 02/14 MN04012005ZDE www.eaton.com 1
Table of contents
0 About this manual ..................................................................... 3
0.1 Target group................................................................................. 3
0.2 Reading conventions.................................................................... 4
0.2.1 Hazard warnings of material damages ......................................... 4
0.2.2 Hazard warnings of personal injury .............................................. 4
0.2.3 Tips............................................................................................... 4
0.3 Abbreviations and Symbols.......................................................... 5
0.4 Units of measurement ................................................................. 6
0.5 Data Types ................................................................................... 6
1 Device series............................................................................... 7
1.1 Checking the Delivery .................................................................. 7
1.2 Key to part numbers..................................................................... 8
1.3 Designation at DX-NET-DEVICENET ............................................ 8
1.4 General rated operational data ..................................................... 9
1.5 Proper use.................................................................................... 10
1.6 Maintenance and inspection ........................................................ 11
1.7 Storage......................................................................................... 11
1.8 Service and warranty.................................................................... 11
1.9 Disposal........................................................................................ 11
2 Engineering................................................................................. 13
2.1 DeviceNet .................................................................................... 13
2.2 LED indicators .............................................................................. 14
2.2.1 LED MS........................................................................................ 14
2.2.2 LED NS......................................................................................... 14
3 Installation .................................................................................. 15
3.1 Introduction .................................................................................. 15
3.2 Notes on the documentation ....................................................... 16
3.3 Notes on the mechanical surface mounting ................................ 16
3.4 Mounting for frame sizes FS2 and FS3........................................ 17
3.5 Mounting from frame size FS4 .................................................... 19
3.6 Installing the fieldbus connection................................................. 21
3.6.1 Pin assignment............................................................................. 21
3.6.2 Bus termination resistor............................................................... 22
3.6.3 Max. cable lengths ....................................................................... 22
3.7 Install field bus ............................................................................. 23
2 DX-NET-DEVICENET 02/14 MN04012005ZDE www.eaton.com
4 Commissioning .......................................................................... 25
4.1 DA1 variable frequency drives ..................................................... 25
4.2 EDS file ........................................................................................ 25
4.3 Addressing................................................................................... 25
4.4 Engineering the module............................................................... 26
4.5 General information about the DeviceNet field bus system ........ 28
4.5.1 Object model ............................................................................... 28
4.6 Supported objects........................................................................ 29
4.6.1 Identity Object (01
hex
).................................................................. 30
4.6.2 DeviceNet Object (03
hex
)............................................................. 31
4.6.3 ADI Object (A2
hex
) ....................................................................... 32
4.6.4 Connection Object (05
hex
) ........................................................... 33
4.7 Operation ..................................................................................... 41
4.7.1 Cyclic data.................................................................................... 41
4.8 Parameter .................................................................................... 46
4.8.1 List of parameters........................................................................ 47
0 About this manual
0.1 Target group
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 3
0 About this manual
0.1 Target group
This manual describes the DeviceNet connection DX-NET-DEVICENET for
the variable frequency drives of the DA1 device series.
It is aimed at experienced drive specialists and automation technicians.
A thorough knowledge of theDeviceNet field bus system and the
programming of a DeviceNet master is required. Knowledge of handling the
DA1 variable frequency drive is also required.
Please read this manual carefully before installing and operating the
DeviceNet connection.
We assume that you have a good knowledge of engineering fundamentals,
and that you are familiar with handling electrical systems and machines, as
well as with reading technical drawings.
DeviceNet is an open field bus standard that is based on the
CAN protocol and is specified in European standard EN 50325.
The specification for the DeviceNet standard is managed and
maintained by ODVA (Open DeviceNet Vendors Association).
To make it easier to understand some of the images included in
this manual, the housing and other safety-relevant parts have
been left out.
The components described here must be used only with a
properly fitted housing and all necessary safety-relevant parts.
Please follow the notes in the IL040004ZU instruction leaflet.
All the specifications in this manual refer to the hardware and
software versions documented in it.
More information on the series described here can be found on
the Internet under:
www.eaton.eu/powerxl
For more information on DeviceNet, please visit ODVA‘s
website at:
www.odva.org
0 About this manual
0.2 Reading conventions
4 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
0.2 Reading conventions
Symbols used in this manual have the following meanings:
Indicates instructions to be followed.
0.2.1 Hazard warnings of material damages
0.2.2 Hazard warnings of personal injury
0.2.3 Tips
NOTICE
Warns about the possibility of material damage.
CAUTION
Warns of the possibility of hazardous situations that may
possibly cause slight injury.
WARNING
Warns of the possibility of hazardous situations that could result
in serious injury or even death.
DANGER
Warns of hazardous situations that result in serious injury or
death.
Indicates useful tips.
0 About this manual
0.3 Abbreviations and Symbols
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 5
0.3 Abbreviations and Symbols
The following abbreviations are used in this manual:
ADI Application Data Instance
CIP Common Industrial Protocol
COS Change of State
CW Control Word
LED Light Emitting Diode (LED)
LSB Least Significant Bit
MAC ID Media Access Control Identifier
MSB
Most Significant Bit
ODVA Open DeviceNet Vendor Association
The user organization (www.odva.org
) for DeviceNet
PC Personal Computer
PDI Process Data Interface
PNU Parameter number
PD Process Data
PLC Programmable logic controller
SW Status Word
UL
Underwriters Laboratories
xx
hex
Used to indicate hexadecimal numbers
(x = 0, 1, …, 9, A, B, C, D, E, F)
0 About this manual
0.4 Units of measurement
6 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
0.4 Units of measurement
Every physical dimension included in this manual uses international metric
system units, otherwise known as SI (Système International d’Unités) units.
For the purpose of the equipment's UL certification, some of these
dimensions are accompanied by their equivalents in imperial units.
Table 1: Unit conversion examples
0.5 Data Types
This manual refers to the following data types for the DeviceNet field bus
system:
Table 2: Data types in DeviceNet
designation US-American
value
US-American
designation
SI value Conversion value
Length 1 in (’’) inch 25.4 mm 0.0394
Power 1HP=1.014PS horsepower 0.7457 kW 1.341
Moment of
torque
1 lbf in pound-force inches 0.113 Nm 8.851
Temperature
F (T
F
) Fahrenheit -17.222 °C (T
C
) T
F
=T
C
×9/5+32
Rotational
speed
1rpm Revolutions per minute 1min
-1
1
Weight
1lb pound 0.4536 kg 2.205
Flow rate 1cfm cubic feet per minute 1.698 m
3
/n 0.5889
Data type Data Length Range Name
[Bits] Min Max
BOOL 1 0 (FALSE) 1 (TRUE) Boolean
SINT
8 -128 127 Signed Short Integer
USINT 8 0 255 Unsigned Short Integer
INT 16 -32768 32767 Integer
UINT
16 0 65535 Unsigned Integer
DINT 32 -2
31
2
31
-1 Signed Double Integer
UDINT 32 0 2
32
-1 Unsigned Double Integer
1 Device series
1.1 Checking the Delivery
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 7
1 Device series
1.1 Checking the Delivery
Your fieldbus connection was carefully packaged and handed over for
shipment. The devices should be shipped only in their original packaging with
suitable transportation materials. Please observe the labels and instructions
on the packaging and for handling the unpacked device.
Open the packaging with adequate tools and inspect the contents
immediately after receipt in order to ensure that they are complete and
undamaged.
The packaging must contain the following parts:
a DX-NET-DEVICENET fieldbus connection
the instruction leaflet IL040004ZU.
Figure 1: Equipment supplied with fieldbus connection DX-NET-DEVICENET
Before opening the package, please check the nameplate on it
to make sure that you received the correct connection.
NS
MS
DeviceNet
1 Device series
1.2 Key to part numbers
8 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
1.2 Key to part numbers
The catalog number selection and the part no. for the DX-NET-… field bus
connection card have the following syntax:
Figure 2: Catalog number selection of field bus interface card DX-NET-…
1.3 Designation at DX-NET-DEVICENET
The following drawing shows the DX-NET-DEVICENET fieldbus connection.
Figure 3: Designations at DX-NET-DEVICENET
a Network status LED (NS)
b DeviceNet connection sockets
c Module status LED (MS)
d 50-pole adapter extension
e Screws for securing DA1 variable frequency drive
DX - NET - DEVICENET Explanation
DEVICENET
NET = Network (Network, Field bus)
DX = card
(accessories for the variable frequency drives of the PowerXL™
series)
NS
MS
DeviceNet
1 Device series
1.4 General rated operational data
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 9
1.4 General rated operational data
Technical Data Symbol Unit Value
General
Standards meets the requirements of the EN 50178 (standard for electrical safety)
Production quality
RoHS, ISO 9001
Degree of protection IP20
Interference emissions as per
EN 61000-6-4
Conducted and radiated interference as per EN 55011
Interference immunity EN 61000-6-2:
EN61000-4-2 Electrostatic discharge
EN61000-4-3 Radiated, radio-frequency electromagnetic fields
Fast transient electrical interference/burst as per EN 61000-4-4 Shock waves
as per EN 61000-4-5
EN61000-4-6 Conducted interferences
Environmental conditions
Operating temperature ϑ °C -40 (no hoarfrost) up to +70
Storage temperature ϑ °C -40 - +85
Climatic proofing p
w
% < 95, relative humidity, no condensation permitted
Altitude H m max. 1000
Vibration g m/s
2
5 – according to IEC 68-2-6
10 - 500 Hz
0.35 mm
DeviceNet connections
power supply V 3.3
interface DeviceNet connection via 5-pin screw terminals
data transfer Automatic baud rate detection
Communication protocol
DeviceNet IEEE 802.3 according to DS301; DeviceNet adapter (Slave)
Functions Implicit and Explicit Messaging; UCMM; Change of State;
Cyclic I/O, Polled I/O
Data volume byte
256 In/Out
Baud rate kBit/s
125 - 500
1 Device series
1.5 Proper use
10 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
1.5 Proper use
The DX-NET-DEVICENET fieldbus connection is an electrical piece of
equipment that can be used to control DA1 variable frequency drives and
connect them to a standard DeviceNet field bus system. It is intended to be
installed in a machine or assembled with other components into a machine
or system. It makes it possible for DA1 series variable frequency drives to be
integrated as slaves into DeviceNet field bus systems.
Figure 4: How the DX-NET-DEVICENET fieldbus connection can be integrated
into a DeviceNet network
a PC
b Head-end controller (master) with DeviceNet interface
c Variable frequency drive DA1 with DX-NET-DEVICENET connection
d Motor(s)
The DX-NET-DEVICENET fieldbus connection is not a household
appliance, but rather a component intended exclusively for use
in commercial applications.
Observe the technical data and connection requirements
described in this manual.
Any other usage constitutes improper use.
L
1
/
L
L
2
/N
L
3
D
C-
U
DC+
BR
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
16 1
7
1
8
COM
V
W
L
1
/
L
L
2/N
L
3
D
C-
U
DC+
BR
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
16 1
7
1
8
COM
V
W
1 Device series
1.6 Maintenance and inspection
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 11
1.6 Maintenance and inspection
The DX-NET-DEVICENET fieldbus connection will not require any
maintenance if the general rated operational data ( Page 9), as well as all
DeviceNet-specific technical data, is adhered to. However, external factors
can influence the components’s lifespan and function. We therefore
recommend that the devices are checked regularly and the following
maintenance measures are carried out at the specified intervals.
Table 3: Recommended maintenance
The
DX-NET-DEVICENET fieldbus connection has not been designed in such
a way as to make it possible
to
replace
or
repair
it. If the card is damaged by
external influences, repair is not possible.
1.7 Storage
If the fieldbus connection is stored before use, suitable ambient conditions
must be ensured at the site of storage:
Storage temperature: -40 - +85 °C,
Relative average air humidity: < 95 %, no condensation permitted.
1.8 Service and warranty
Contact your local sales partner if you have a problem with your Eaton
fieldbus connection.
When you call, have following data ready:
the exact part no. (= DX-NET-DEVICENET),
the date of purchase,
a detailed description of the problem which has occurred with the
DX-NET-DEVICENET fieldbus connection.
Information concerning the guarantee can be found in the Terms and
Conditions Eaton Industries GmbH.
24-hour hotline: +49 (0) 180 5 223 822
e-mail:
AfterSalesEGBo[email protected]
1.9 Disposal
The DX-NET-DEVICENET fieldbus connection can be disposed of as electrical
waste in accordance with the currently applicable national regulations.
Dispose of the device according to the applicable environmental laws and
provisions for the disposal of electrical or electronic devices.
Maintenance measures Maintenance interval
Check the filter in the control panel doors
(see the manufacturer's specifications)
6 - 24 months (depending on the environment)
Check the tightening torques of the control signal terminals regularly
Check connection terminals and all metallic surfaces for
corrosion
6 - 24 months (depending on the environment)
1 Device series
1.9 Disposal
12 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
2 Engineering
2.1 DeviceNet
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 13
2 Engineering
2.1 DeviceNet
DeviceNet was developed by Rockwell Automation and ODVA (Open
DeviceNet Vendors Association) as an open field bus standard based on the
CAN protocol.
DeviceNet is an object-oriented bus system and works using a producer/
consumer model.
DeviceNet‘s application layer uses the CIP protocol (Common Industrial
Protocol). CIP defines the transfer of I/O data in real time via I/O messages
(I/O messaging or implicit messaging), as well as the transfer of request and
response data for configuration, diagnostic, and management purposes
(explicit messaging). CIP is an object-oriented protocol and is typically used
to network sensors, variable frequency drives, and actuators with higher-
level automation devices (PLCs).
DeviceNet devices within a DeviceNet network can function as a client
(master), server (slave), or both.
DeviceNet networks can support a maximum of 64 bus nodes.
Baud rates of 125, 250, or 500 kBaud can be achieved (depending on the
type of cable used).
2 Engineering
2.2 LED indicators
14 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
2.2 LED indicators
The two LEDs on the module are used to indicate the module status and
network status, making it possible to quickly diagnose the unit.
Figure 5: MS and NS LED indicators
2.2.1 LED MS
The MS LED indicates the module‘s status within the DeviceNet network.
2.2.2 LED NS
The MS LED indicates the network communications status.
NS MS
DeviceNet
LED status Description
off No supply voltage is applied.
green flashing The module is in standby mode. The configuration is incorrect or incomplete, or a
configuration does not exist.
green illuminating
The module is working properly.
red flashing An error has occurred.
illuminated red
A fatal error has occurred . Module needs to be replaced.
green-red flashing The module is running a self-test.
LED status Description
off Module is not online.
green flashing The module is online, but a communication connection has not yet been established.
green illuminating The module is online and a communication connection has been established
red flashing Time-out of at least one I/O connection (time-out state).
illuminated red A fatal network error has occurred.
The module has terminated communications.
green-red flashing
The module is running a self-test.
3 Installation
3.1 Introduction
DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com 15
3 Installation
3.1 Introduction
This chapter provides a description of the mounting and the electrical
connection for the fieldbus connection DX-NET-DEVICENET.
In the case of DA1 variable frequency drives, the way in which the DX-NET-
DEVICENET fieldbus connection needs to be installed will depend on the
corresponding variable frequency drive‘s size.
Figure 6: Flush mounting of fieldbus connection
In the case of DA1 variable frequency drives with sizes FS2 and FS3, the
fieldbus connection will need to be plugged into the variable frequency drive
from below. In the case of sizes FS4 and up, the fieldbus connection will
need to be mounted on the right side, underneath the variable frequency
drive's front enclosure cover.
While installing and/or mounting the fieldbus connection, cover
all ventilation slots in order to ensure that no foreign bodies can
enter the device.
Perform all installation work with the specified tools and without
the use of excessive force.
L2/N L3DC-
L1/L
DC+ BR U V W
12345678910111213
14 15 16 17 18
COM
11 12 13
14 15 16 17 18
N
S
M
S
Devi
c
e
Ne
t
3 Installation
3.2 Notes on the documentation
16 DX-NET-DEVICENET 02/14 MN04012005ZEN www.eaton.com
3.2 Notes on the documentation
Documents containing installation instructions:
IL4020010Z instruction leaflet for DA1 variable frequency drive
in size FS2 and FS3
IL4020011Z instruction leaflet for DA1 variable frequency drive
from size FS4
These documents are also available as PDF files on the Eaton Internet
website. They can be quickly located at
www.eaton.com/moeller
Support
by entering the document number as the search term.
3.3 Notes on the mechanical surface mounting
Figure 7: Make sure that the equipment is de-energized
when performing installation work
DANGER
Make sure that the equipment is fully de-energized when
performing the handling and installation work required to
mechanically set up and install the fieldbus connection.
When
installing
the
DX-NET-DEVICENET
fieldbus connection,
it
will be necessary to open the DA1 variable frequency drive‘s
enclosure. We recommend that this mounting work be carried
out before the electrical installation of the variable frequency
drive.
L1/L
L2/N
L3
DC-
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58