elco VARION C-POWER Operation and Maintenance Manual

Type
Operation and Maintenance Manual
Made in Germany
Operating manual
Combined heat and power unit
VARION® C-POWER
ELCO/Control
02.2017
2
Operating manual VARION® C-POWER ELCO/Control / 02.2017
Contents
1. Document information. . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Validity. . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . 3
1.3 Explanation of symbols . . . . . . . . . . . . . . . . 3
2. Safety information ...........................4
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Authorised target groups . . . . . . . . . . . . . . . 4
2.2.1 Manufacturer .......... .............. 4
2.2.2 Operator ............................ 4
2.2.3 Trained personnel .................... 4
2.2.4 User ............................... 4
2.3 General safety instructions . . . . . . . . . . . . . . 5
3. Product information ..........................6
3.1 Product overview . . . . . . . . . . . . . . . . . . . . 6
3.2 Operational display. . . . . . . . . . . . . . . . . . . 6
3.3 Menu structure . . . . . . . . . . . . . . . . . . . . . 7
4. Operation ..................................8
4.1 Start screen . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Main menu . . . . . . . . . . . . . . . . . . . . . . 10
4.2.1 Operation mode .................... 11
4.2.2 Measured data ..................... 12
4.2.3 Time program ...................... 14
4.2.4 Logbook ........................... 18
4.2.5 Operating hours ..................... 19
4.2.6 Safety shutdowns ................... 22
4.2.7 Technician level ..................... 23
4.2.8 System ............................ 30
4.3 Level protection . . . . . . . . . . . . . . . . . . . 34
4.4 Electric vehicle charging button. . . . . . . . . . . 35
5. Service repairs .............................36
5.1 Fault resolution . . . . . . . . . . . . . . . . . . . . 36
3
Document informaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
i
1. Document information
i
1.1 Validity
This operating manual belongs to the documentation for
the combined heat and power unit VARION® C-POWER,
which is referred to in this manual as the “system.
This operating manual is a supplement to the operating
manual for the system and describes control via the
operational display with the software.
Valid from software status:
B Version 3.20
Use on the following systems:
B S
B
M
B M+
For descriptions of the system, observe the associated
operating manual:
Operating manual for “VARION® C-POWER S, M, M+.
This manual is protected by copyright law. Duplication,
reproduction and transmission is only permitted with the
permission of the manufacturer.
Subject to change without notice.
1.2 Safety instructions
D DANGER!
Information highlighted with the word HAZARD warns
against a hazardous situation that will lead to death or
severe injury.
D WARNING!
Information highlighted with the word WARNING warns
against a hazardous situation that can lead to death or
severe injury.
D CAUTION!
Information highlighted with the word CAUTION warns
against a situation that can lead to minor or moderate
injuries.
D ATTENTION!
Information highlighted with the word ATTENTION
warns against a situation that can lead to material or
environmental damage.
1.3 Explanation of symbols
Text
A Required action
B List
D
Cross reference to another point in this document
Cross reference to other documents that must be
observed
4
Safety informaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
2. Safety information
2.1 Intended use
The software serves to control and monitor the system. The
software is operated via the operational display on the
control cabinet.
The software is installed by the manufacturer. Only the
manufacturer is permitted to implement measures for
maintaining and updating the software.
Intended use also includes reading and following this
manual.
Any other use is considered contrary to intended use.
2.2 Authorised target groups
This manual is intended for various target groups that are
authorised for specific duties.
2.2.1 Manufacturer
The manufacturer, ELCO GmbH, supplies the product and
has the following duties:
B
Training experts on assembly,
maintenance,
disassembly
and
disposal.
B
Commissioning the system.
Only the manufacturer has access to the “expert level” area
of the software.
2.2.2 Operator
The operator is responsible for the building in which the
product is installed. The operator has the following duties:
B Fulfilling the requirements specified by the energy
provider (e.g. registration, approval, compensation).
B Meeting the installation location requirements.
B Training the user.
B Complying with statutory occupational health and safety
obligations.
B Complying with the valid safety, accident prevention and
environmental protection regulations.
B Providing and complying with the documentation.
B Ensuring that the product is always kept in a technically
sound condition.
B Storing the system when necessary.
2.2.3 Trained personnel
Trained personnel are responsible for the assembly,
maintenance, disassembly and disposal of the product.
The following points must be observed:
B All tasks must only be performed by qualified personnel
who have been trained by the manufacturer and who
are familiar with assembly technology, gas and water
installations, and current safety regulations.
B Special installation tasks (e.g. tasks involving the
building structure or the ventilation system) must only
be performed by the suitably qualified personnel of
specialist companies.
B Electrical installations must only be performed b
y
qualified, skilled electricians.
Only qualified personnel trained by the manufacturer have
access to the “technician level” area of the “RMB/Control”
software.
2.2.4 User
Users may perform operational and cleaning tasks on this
product. Obligations of the user:
B To be trained on the product by the operator.
B To be familiar with this manual.
Trained users have access to the non-protected areas of
the software, but not to the “expert level” and “technician
level” areas.
5
Safety informaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
2.3 General safety instructions
D WARNING!
Danger of death with a failure to observe the manual!
This manual contains important information for handling the
system safely. Potential hazards are specifically highlighted.
Failing to observe such information can lead to death or
severe injuries.
A Read the manual carefully.
A Follow the safety instructions contained in this manual.
A Follow the safety instructions on the system
A Store the manual in an accessible place.
If you can smell gas, immediately proceed as follows:
B Close the gas valve.
B Do not generate any naked flames.
B Do not operate any electrical switches
(e.g. light switches, all-pole separating points).
B Do not use any electrical appliances in the
hazardous area (e.g. telephone).
B Ventilate the rooms.
B Inform the manufacturer, gas utility company or qualified
service company.
Use of the system is prohibited in the following cases:
B If the system or individual components are damaged.
B If the system has been altered or modified without
authorisation.
B If the supply and return lines (e.g. gas, flue gas, exhaust
air, water, electricity, drain) are altered or modified
without authorisation.
B If any safety devices are missing or inoperable.
B During the construction phase of the building.
B If the system has been in storage for more than
12 weeks after delivery.
B If the system has been decommissioned for more than
12 weeks.
B For children or individuals who are incapable of
assessing the hazards associated with operating the
system.
The manufacturer does not accept any liability or guarantee
for damage or loss in the following cases:
B Failing to observe this manual.
B Contrary-to-intended use.
B Improper handling.
B Use by unauthorised target groups.
B Failing to meet the installation location requirements.
B Using replacement parts that have not been authorised
by the manufacturer.
B Bypassing the system’s safety devices.
B Removing the system’s seals and sealants.
B Failing to comply with the maintenance intervals.
Additional safety instructions are provided in the respective
chapters of this manual.
D
„4. Operation“ (page 8).
D
„5. Service repairs“ (page 36).
6
Product informaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
3. Product information
3.1 Product overview
The software is operated via the operational display on
the system’s control cabinet. The operational display is
equipped with a touch-sensitive screen
(“touchscreen”).
The control cabinet contains all the components
required to control the system.
B
D
A
C
A Operational display
B Control cabinet housing
C Emergency stop switch
D Master switch
3.2 Operational display
By touching the screen (“touchscreen”), the user is able to
execute functions and call up screen pages.
If entries are necessary (e.g. names, values) then a
corresponding on-screen keypad is automatically displayed.
A
B
C
D E F
A Area for system identification with:
B Information on the system and manufacturer
B Information on the software and the software
version
B Identification (ID no.) of the system
Touching calls up the “system” menu.
B Date and time information. Touching calls up the “date/
time” menu.
C Function keys for direct access to important menus (from
right to left):
B Start screen
B Main menu
B Electric vehicle charging button
B Time program
B Peak load boiler
B Level protection
Touching calls up the corresponding menu.
D Status area with continuous display of important
performance data:
B Current performance and degree of modulation
B Water pressure in the motor circuit
B Electricity consumption in the building
B Buffer load and buffer tank temperatures
B Engine circuit supply temperature
B Operation mode
B Operating hours
Touching calls up the associated menu.
E Working area with display of the selected menu.
Including:
B Menu path information (top left)
B Access to the previous menu (top right)
B Status bar (bottom)
F Button for direct access to the start screen.
7
Product informaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
3.3 Menu structure
2.2 Measureddata1
2.3 TimeProgram-page1
1 Homepage 2 MainMenu 2.1 Operatingmode
24-hours-trend
7-days-trend
2.4 Logbook
2.5 OperatingHours
DischargePump
2.6 SafetyShutdowns
2.7 TechnicianLevel
Trend
Password
Measureddata2
TimeProgram-page2
Timeframe
Non-productive-time
Help
3-hours-trend
2.8 System Date/Time
StartConditions
PumpTest
Master/Slave
MaintenanceCounter
Extraboiler
Language
ExpertLevel
3
4
ElectricalCarCharging
Button
8
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4. Operation
D ATTENTION!
Risk of damage to the system with a failure to observe the
operating instructions!
This chapter contains important information regarding
the safe operation of the system. Incorrect settings in the
control mechanism can damage the system or shorten its
service life.
A Read this chapter carefully before operating the system.
A Follow the safety instructions.
Trained users have access to the non-protected areas,
but not to the “expert level” and “technician level” areas.
The system must only be operated by qualified users.
D
„2.2.4 User“ (page 4).
Only qualified personnel trained by the manufacturer have
access to the “technician level” area.
D
„2.2.3 Trained personnel“ (page 4).
Only the manufacturer has access to the “expert level”
area.
D
„2.2.1 Manufacturer“ (page 4).
In order to operate the system via the software,
the following preconditions must be satisfied:
B The system is completely and correctly assembled.
B The system is switched on.
For information regarding assembly, observe the associated
operating manual:
Operating manual for “VARION® C-POWER S, M, M+.
Function keys
The following function keys are permanently displayed for
direct access to the respective menu:
Symbol Meaning
Start screen
D
„4.1 Start screen“ (page 9).
Main menu
D
„4.2 Main menu“ (page 10).
Electric vehicle charging button
D
„4.4 Electric vehicle charging button“
(page 35).
Time program
D
„4.2.3 Time program“ (page 14).
Peak load boiler
D
Technician level – peak load boiler“
(page 25).
Level protection
D
„4.3 Level protection“ (page 34).
Background colours
The background colour of the screen changes depending on
the system state.
The following colours are possible:
Colour Meaning
Orange System is switched off
Blue System is switched on and waiting for requests
Green System running and producing energy
Red A safety shutdown has switched the system off
The screens for the non-protected areas and the technician
level are described in the following, according to the menu
structure.
D
„3.3 Menu structure“ (page 7).
9
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4.1 Start screen
The start screen displays an overview of the actuated system in accordance with the hydraulic plan (the actual layout may vary).
The following information is displayed:
B Temperature in the system (“cabin”)
B Flue gas temperature
B Supply and return temperature of the buffer tank
B Supply temperature of the heating circuit
B Buffer tank temperatures T1 to T4
B Release of the peak load boiler ("SLK")
B Output pump 2
10
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4.2 Main menu
The main menu branches into the following submenus:
B Operation mode
B Values
B Time program
B Logbook
B Operating data
B Safety shutdowns
B Technician level
B System
In order to switch to a certain submenu:
A Touch the corresponding button.
11
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4.2.1 Operation mode
The system can be operated in five modes of operation (including shutdown).
Operation mode
OFF The system is in hibernation mode. The system does not start according to
temperature requirements.
1 – Ready for electric vehicle
charging button
Special mode for charging electric vehicles. It is still possible to produce electricity in
this mode too, if the storage battery is fully charged.
Once the electric vehicle charging button has been pressed, the system runs for two
hours.
D
„4.4 Electric vehicle charging button“ (page 35).
2 – Summer mode In summer operation mode, the system only operates at minimum capacity.
The system only starts if the storage battery has insufficient charge.
This mode is expedient if less heat is required.
3 – Heat-optimised The system starts if a temperature requirement has been set. If the storage battery
has reached a specific percentage charge, the system begins to power down
steplessly.
This mode is expedient if the power consumption is fundamentally lower than the
nominal output of the system.
4 – Electricity-optimised The system starts to operate according to a temperature requirement. Once a
specific storage battery charge has been reached, the system aligns itself to the
electricity consumption of the building.
This mode helps to increase own consumption of the power generated.
In order to put the system into the desired operation mode:
A Touch the corresponding button (“activate here”) on the right side.
After the start, the system has a warm-up phase lasting a few minutes. Only then is the selected output reached.
The selected operation mode is displayed bottom left in the status area.
12
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4.2.2 Measured data
Measured data – page 1
Display of the measured temperature at different positions:
B Engine outlet
B Engine backflow
B Buffer supply line
B Buffer return line
B Buffer tank temperatures T1 to T4
B Room air
B CHP interior
B Building heating circuit (T5)
B Flue gas before heat exchanger (“AWT”)
B Flue gas after heat exchanger (“AWT”)
B Engine oil
Normal temperature ranges are displayed with a green bar. If the colour of the bar changes to red then the temperature has
reached a critical value.
13
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
Measured data – page 2
Display of the following values and states:
B Water pressure in the engine circuit
B Speed pump 1
B Speed pump 2
B Gas pressure (ON/OFF)
B Grid / phase (ON/OFF)
B Thermal request (ON/OFF)
B Electricity consumption in the building
14
Operaon
Operating manual VARION® C-POWER – ELCO/Control/ 02.2017
4.2.3 Time program
Time program – page 1
The runtime behaviour of the system is planned in the “time program” menu. Ten time windows are available here:
B Page 1: Time window T1 to T5
B Page 2: Time window T6 to T10
The control distinguishes between “productive time” and “non-productive time”.
B Productive time: Times stored in the ten time windows
B Non-productive time: All further times that have not been saved
In order to call up the desired time window:
A Touch the corresponding green button.
In the time window, the behaviour of the system during productive times is stipulated. The following information is required:
B Day of the week (Monday to Sunday)
B Timeframe (time of day)
B Shut-off upon reaching load (degrees in %) of the buffer tank
B Maximum output (in kW)
B Modulation release. In modulation mode, the system adjusts its output to the current requirement. Otherwise the system
always delivers the maximum output specified.
Factory setting of the system for the productive time:
Monday to Friday from 05.00 hrs to 22.00 hrs, Saturday and Sunday from 07.00 hrs to 23.30 hrs.
15
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
Time program – page 2
Time program – timeframe
16
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
Time program – behaviour during non-productive times
In order to specify the behaviour during non-productive times, two options are available in a separate menu.
1. Setting with the following information:
B Maximum output (in kW)
B Shut-off upon reaching load (degrees in %) of the buffer tank
B Modulation release
2. Setting determines that the system switches off automatically during non-productive times. In this case the system does
not react with temperature requirements. When a productive time is reached, the system starts in the last operation mode
selected.
17
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
Time program – help
A help menu is available to explain the time program.
18
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4.2.4 Logbook
The logbook records events and states to the precise second, e.g.:
B Start time after temperature request
B Reset of the maintenance counter
In order to scroll in the logbook:
A Touch the arrow keys on the right side.
19
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
4.2.5 Operating hours
Display of the operating hours of the past seven days as column graphics and as numeric values:
B The current day is at the far right with an orange background.
B To the left of this are displays of the preceding six days.
The following information is displayed by the column graphics:
B Total operating time (operation hours)
B Countdown until next maintenance due
B Number of engine starts
B Average runtime per engine start
By touching the corresponding symbol on the screen, it is possible to display four trends:
B Current trend (updated every second)
B 3-hour trend (the data recorded over the last 3 hours)
B 24-hour trend (the data recorded over the last 24 hours)
B 7-day trend (the data recorded over the last 7 days)
The following information is recorded and displayed in diagram form to present the trends:
B Engine temperature (yellow)
B Electrical output (green)
B Buffer storage battery charge (blue)
B Power consumption (red, optional)
B Modulation rate (purple)
B Target storage battery charge (orange)
20
Operaon
Operating manual VARION® C-POWER – ELCO/Control / 02.2017
Operating hours – current trend
Operating hours – 3-hour trend
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

elco VARION C-POWER Operation and Maintenance Manual

Type
Operation and Maintenance Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI