  • Hello, I'm your chat assistant. I've reviewed the Aiphone AX Series Application Note, which details how to configure the AX-084C, AX-248C, and AX-320C models for mantrap door unlocking. This document explains how to connect the door release terminals and operate the system using the master station. I'm ready to answer your questions about using these door release system.
  • How do I unlock a mantrap door using the AX Series?
    What do the door release outputs on the Central Exchange Unit correspond to?
    What happens if there is no door station connected to a door port?
105/23
Aiphone Corporation | www.aiphone.com | (800) 692-0200
APPLICATION NOTE
AX SERIES
For more details about the features and information above, please contact Technical Support.
This guide explains how to unlock a mantrap door using the AX Series. This can be used for any application where a door without a
door station needs to be unlocked.
Mantrap Wiring and Conguration
Introduction
Door release outputs on the Central Exchange Unit (AX-084C, AX-248C, or AX-320C) correspond to the matching door selector buttons
on the right side of the master station. For example, the rst button from the top is linked to the L1/L1 outputs on the Central Exchange
Unit, the second down is linked to L2/L2, and so on. This is true even if there is not a door station connected to a particular door port.
Connect the mantrap door release terminals to the desired output on the Central Exchange Unit. Once the visitor is in the mantrap, tap
the matching door selector button on the master station. The light on the button will illuminate when it is active. While the light is on,
press the Key button on the master station to unlock the door. Press the O button on the master once the visitor is out of the mantrap.
Instructions
Wiring Example
The main door will be
answered and released by
pressing door selector #1. The
mantrap will be released by
pressing door selector #2.
Mantrap Door Release L2/L2
Main Door Release L1/L1
If updating dimensions, be sure to update the GLC layer too.
Please refer to the Product Dimensions Master located here:
H:\Engineering Services\Product Dimensions Master Document\Product Dimensions Master.xlsx
AX-8M, AX-8MV, AX-8MV-W
7-5/ 8"
6-7/8"
2-9/16"
1-7/ 8"
Master Station M1
Door Station D1
If updating dimensions, be sure to update the GLC layer too.
Please refer to the Product Dimensions Master located here:
H:\Engineering Services\Product Dimensions Master Document\Product Dimensions Master.xlsx
AX-DV
7-11/16 "
3-15/16" 1"
Central Exchange Unit
AX-084C
Cat 5e/6
Cat 5e/6
18/2 Cable
18/2 Cable
Door
Release
and Power
Door
Release
and Power
Door station ports on the Central
Exchange Unit are enabled by default.
Leave any ports being used for the
mantrap enabled in the AX Setup Tool.
24V DC
Power
/