Zeta PMP-REP Installation guide

Type
Installation guide
REPEATER
The Premier M Plus Repeater (PMP-REP) is available in 2 versions, active or passive.
The Active panel can control the system (silence reset etc). Only 1 active repeater is allowed on a
system.
The Passive repeater is display only (ie it can not silence or reset the system. You can connect up to
8 passive repeaters onto a system.
The repeater is connected to the control panel via 4 cables. Two for power, 2 for data.
Connections
Panel Repeater
AA
BB
AUX Power +28V SUPPLY +
AUX SUPPLY -Power 0V
DOC: WD-PMP-REP/M+EN54
ISS: 1
DATE: 06/12/2010
Premier M+
12 438
7
65
9101112
13 14 15 16 17 18
19 20 21
22
23 24
MADE IN UK
RĂ©mi B. GLT EXPORTS LTD.
www.zetaalarmsystems.com
Date: 05/10/2010
PCB Ref number: 21-1003 v5.2
Stock No: PCB/ Base Board M+
Unused sounders must use
a 10K restistor End of Line
Unused zones must use a diode End of Line
Unused sounders must use a 10K resistor End of Line
B
A
Serial
Repeater
+28V
0V
AUX. Power
NC
Power supply faults
+
-
Sounder 4
+
-
Sounder 3
+
-
Sounder 2
-
Sounder 1
+
-
Fire Routing
Equipement
FAULT Relay
N.O. N.C.
COM
FIRE Relay
N.O. N.C.COM
+28V
0V
Power Supply
Earth
+28V Supply
Fuse 6AT
Fire Routing
Equipment
Fuse 100mAT
Sounder 1
Fuse
400mA
Sounder 2
Fuse
400mA
Aux Supply
Fuse 250mAT
Sounder 3
Fuse 400mA
Sounder 4
Fuse 400mA
Earth
Connection
COM
Connect to faultRelay
+
Remove Jumper
to disable
earth monitoring
eta
ALARM SYSTEMS
Z
eta
ALARM SYSTEMS
  • Page 1 1