![](//vs1.manuzoid.com/store/data-gzf/77eee262165ac6f2bb86f81eb35af153/2/000610259.htmlex.zip/bg11.jpg)
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
Installing Input/Output (I/O) Circuit Cards
Refer to the following procedure, and install the I/O circuit card(s)
into the respective mounting positions of the
586505000/586505500 LMS1000 Main and Expansion Cabinet(s)
or 582140000/582140001/582126100 Power System Primary and
Secondary Power Bay(s), as required.
Note that in 582140000, 582140001, and 582126100 Power
Systems, an LMS CPU circuit card must be installed in a bay that is
to be populated with LMS I/O circuit card(s). LMS I/O circuit card
mounting positions are provided inside the
582140000/582140001/582126100 bays.
PROCEDURE:
Note:
Refer to Figure 3 through Figure 6 as this procedure is
performed.
1.
586505000/586505500 LMS1000 Cabinet: To access the
circuit card mounting position, rotate the two captive
fasteners on the front of the cabinet until the arrow on
the fastener points up or down, and pivot the door open.
or
582140000/582140001/582126100 Power System:
Open the bay's front door to access the CPU circuit card
mounting positions.
2. Connect an approved grounding strap to your wrist.
Attach the other end to a suitable ground.
3.
582140000/582140001/582126100 Power System:
Loosen the two screws securing the circuit card retaining
angle, and slide the retaining angle down.
4. Unpack the LMS1000 I/O circuit card(s) to be installed.
Four (4) Input Analog Circuit Card (P/N 506336)
Eight (8) Input Analog Circuit Card (P/N 514528)
Twelve (12) Input Analog Circuit Card (P/N 520838)
Eight (8) Input Temperature Circuit Card (P/N 506333)
Four (4) Input Binary Circuit Card (P/N 506332)
Eight (8) Input Binary Circuit Card (P/N 506334)
Four (4) Output Form-C Relay Circuit Card (P/N 506335)
Note:
A maximum of six 12-input analog circuit cards can be
installed in the 586505000/586505500 Main Cabinet or
582140000/582140001/582126100 Primary Power Bay.
DO NOT install 12-input analog circuit cards in
586505000/586505500 Expansion Cabinets or
582140000/582140001/582126100 Secondary Bays.
5. If you are installing a four input analog circuit card, make
the following jumper adjustments.
a. Four jumpers are provided on the four input analog
circuit card. Each jumper is associated to an input
and sets the input to either monitor 50 mv and 100
mv DC shunt inputs, 0-60 volt DC inputs, or 20 ma
current loop inputs. Refer to Figure 4, and set each
jumper for the type of input to be monitored.
6. If you are installing an eight input binary circuit card,
make the following jumper adjustments.
a. Eight jumpers are provided on the eight input binary
circuit card. Each jumper is associated to an input.
The second connection point for each binary input is
determined by the placement of the appropriate
jumper. These jumpers are factory set to the "-BAT"
position. For each binary input, refer to Figure 5 and
place the appropriate jumper either in the "+BAT" or
"-BAT" connection position. Refer to "Eight Input
Binary Circuit Card Connections, P/N 506334" in this
section for a description of the connection made by
the placement of these jumpers.
7. If you are installing a four output (Form-C) relay circuit
card, make the following jumper adjustment.
a. A jumper is provided on the four output (Form-C)
relay circuit card. The placement of this jumper
enables or disables the commands SET RLY (Set
Relay) and CLR RLY (Clear Relay). Refer to Figure 6
and set this jumper per site requirements.
8. Each I/O circuit card can be installed in any of the circuit
card mounting positions in any cabinet or bay, but install
circuit cards from left to right, in the next available empty
mounting position (as viewed from the front of the
cabinet or bay). DO NOT SKIP SLOTS. Circuit cards are
installed in the cabinet or bay with the component side
facing the left as viewed from the front. Slide the circuit
card(s) into its mounting location, ensuring the rear edge
connector is firmly seated.
Note:
In 582140000/582140001/582126100 Power Systems,
the recommended method is to populate LMS
Input/Output circuit cards from left to right, and MCA
Customer Alarm Relay circuit cards from right to left.
9.
586505000/586505500 LMS1000 Cabinet: If a
temperature circuit card(s) has been installed, attach the
green wire connected to the circuit card(s) to one of the
grounding studs provided inside the cabinet. Refer to
Figure 3 for location. Place the lug of the green wire
below the flat washer provided on the grounding stud.
Replace the lock washer and resecure the nut.
582140000/582140001/582126100 Power System: If a
Temperature circuit card(s) has been installed, attach the
green wire connected to the circuit card(s) to one of the