Omega HX200, a versatile dew point/RH transmitter, offers precise humidity measurements for various applications. Its stainless-steel probe with a high-temperature cable enables operations up to 200°C (392°F) and withstands pressures up to 750 PSI. The device provides accurate readings for both dew point and relative humidity (%RH) along with temperature. With its 4-20mA output, the HX200 seamlessly integrates with data acquisition systems and PLCs. Additionally, the RS232 interface allows for remote monitoring and configuration.

Omega HX200, a versatile dew point/RH transmitter, offers precise humidity measurements for various applications. Its stainless-steel probe with a high-temperature cable enables operations up to 200°C (392°F) and withstands pressures up to 750 PSI. The device provides accurate readings for both dew point and relative humidity (%RH) along with temperature. With its 4-20mA output, the HX200 seamlessly integrates with data acquisition systems and PLCs. Additionally, the RS232 interface allows for remote monitoring and configuration.

User’s Guide
HX200
Dew point/RH Transmitter
Servicing North America:
U.S.A. Omega Engineering, Inc.
Headquarters: Toll-Free: 1-800-826-6342 (USA & Canada o n l y)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660 Fax: (203) 359-7700
E-mail: info@omega.com
For Other Locations Visit omega.com/worldwide
Available Models: All models will display either dew point & temperature or RH & temperature.
Outputs will vary depending on model.
HX200HD
Remote Dew Point/Temperature Transmitter 4 to 20mA only
HX200HR
Remote RH/Temperature Transmitter 4 to 20mA only
HX200HD-RS
Remote Dew Point/Temperature Transmitter 4 to 20mA or RS232
HX200HR-RS
Remote RH Point/Temperature Transmitter 4 to 20mA or RS232
HX200HD-W
Wall Mount Dew Point/Temperature Transmitter 4 to 20mA only
HX200HR-W
Wall Mount RH/Temperature Transmitter 4 to 20mA only
HX200HD-W-RS
Wall Mount Dew Point/Temperature Transmitter 4 to 20mA or RS232
HX200HR-W-RS
Wall Mount RH Point/Temperature Transmitter 4 to 20mA or RS232
HX200HD-RS
HX200HD-W-RS
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains and reserves
the right to alter specifications without notice.
HX200 Series
QUICK STARTUP GUIDE
Installing the probe for compressed air and dryer applications.
For the HX200HD/HX200HD-RS
Install fitting on to probe fitting threads facing the probe’s filter.
Apply Teflon tape to the external threads of the fitting.
Slide probe to desire depth. Note: be sure sinter filter is clear of the ferrule on the NPT fitting,
hand tight and then use a wrench a do a quarter turn,
Check for leaks, if leaks occur tightened down on fitting another 1/8” turn until leaks have been
eliminated, probe is rated to 750psi.
Installing the probe for environmental applications
For the HX200HR/HX200HR-RS
Mount probe using a ½” (ID) mounting clamp (not provided) over probe and attached it to a
surface where measuring. Avoid installation in direct line with water injection.
For the mounting the HX200 series Electronics
Mount the electronics with two # 8 sheet metals screws
Mounting centers are 3.1” from each other.
Power 12 to 28Vdc, 24 Vdc (typical) 25mA max
HX200 Connections:
Connect red wire (+) to the positive excitation source and the black wire (-) to a negative
excitation. The output load if isolated from the excitation voltage can be in line with either the red
or black wire. If the load shares a common connection to the negative excitation voltage, the
HX200 (-) terminals must be connected to the (+) of the load device.
HX200-RS Connections:
Connect white wire (+) to the positive excitation source and the black wire (-) to a negative excitation.
If using the unit as a loop powered device, the output load if isolated from the excitation voltage can
be in line with either the white or black wire. If the load shares a common connection to the negative
excitation voltage, the unit (-) terminals must be connected to the (+) of the load device. RS232
connections: Receive is the gray conductor, transmit is the blue conductor, ground is the brown
conductor.
Verify that the received signal agrees with the display value.
Things to avoid: submersion in liquids, condensing conditions and dew points above 95C (live
steam)
Quick reminder: provide sufficient air flow to sensor (positioning of sensor is important because
response time can be affected.
HX200-RS wiring
RXin Gray Wire
TXout Blue wire
GND Brown Wire
(+) 24VDC White Wire
(-) RTN Black Wire
HX200- wiring
(+) 24VDC Red Wire
(-) RTN Black Wire
INTRODUCTION
3.1 GENERAL DESCRIPTION
The HX200 Series is a family of humidity probes and electronic modules that offer %RH and dew point
measurements with NIST traceable calibration. All stainless-steel probe construction coupled with a high
temperature cable allows up to 200c operations. For pressure applications the probe is capable of handling
750PSI.
The HX200 series is offered in 8 versions, dew point/temperature-(HX200HD, HX200HD-RS, HX200HD-W, &
HX200HD-W-RS), % RH/temperature- (HX200HR, HX200HR-RS, & HX200HR-W, & Hx200HR-W-RS)
The HX200HD pressure version has an enhance calibration for measuring dew points down to -60C. The
HX200HR -RH version has an accuracy of +/-1.0% at 25C. These two models provide a single two wire loop
powered 4-20mA interface. The HX200-RS version has all the features of the prior models but has a RS232
signal that outputs RH, temperature and dew point. These units accept a voltage source from 12 to 28Vdc,
24Vdc is recommended. These units will display temperature along with RH or dew point depending on the
version selected. The RS232 allows a user to scale their outputs ranges as well as displayed units. The unit
and sensor are connected via a 1-meter high temperature cable. This unit has a single output, 4-20mA
output wiring and can provide a signal up to 400 ft.
3.2.1 HX200 Series
Operating temperature: 0C to 200C, no- condensation condition, non-steam applications, max dew point 95C
Electronics 0C to 85C
All units will come with a traceable NIST calibration certificate.
For the HX200HR series
HX200HR is ideal for environmental chamber, clean rooms and high temperature applications
One Analog Output: 4-20mA Loop Power corresponds 0-100% RH.
Output signal resolution: 0.03%RH
Power Supply: 12 to 28Vdc, 25 mA max. 24Vdc
recommended Display resolutions: 0.1% RH
RH Accuracy: +/- 1% at 25C
Temp. Accuracy: +/- 0.5°C from 0 to 100C, >100C +/-1C
Mounting: Cable Length: 1 meter (except wall units)
SS Material: Probe, filter guard and fitting
Dimensions of Probe: Length: 6.5” (185mm), O.D.: 0.5” (13mm)
For the HX200HD series
HX200HD series are ideal unit for compressed air and dryer applications.
One Analog Output: 4-20mA Loop Power corresponds -60 to 40C dew point
Output signal resolution: 0.03C
Power Supply: 12 to 28Vdc, 25 mA max.
Display resolutions: 0.1C
Dew Point: Accuracy: +/- 1.0C from 40c to -20C, +/-3.0C <-20C
Temp. Accuracy: +/- 0.5°C from 0 to 100C, >100C +/-1C
Mounting: Cable Length: 1 meter (except wall units)
SS Material: Probe, filter guard and fitting
Fitting: ½” NPT stainless steel (included)
Pressure rating: 750psi
Dimensions of Probe: Length: 6.5” (185mm), O.D.: 0.5” (13mm)
For the HX200-RS series
The HX200-RS meets all the specs listed above for both the HX200HD and HX200HR.
Digital Output: Bidirectional RS-232C outputs will display RH, dew point and temperature, in
the streaming command. The loop power will not function if using the RS232.
Switches for DP or RH and Fahrenheit or Celsius
Located on the circuit board there are two switches. The switch on the left will allow
for the customer to switch between DP or RH and the switch on the right allows for
the customer to switch between Celsius and Fahrenheit.
Communications from PC to the device
You can streamline your data via the RS232 that gives you all three
measurement units.
Using the terminal emulation program, i.e.: HyperTerminal, Tera term, etc.
Rs232 SETTINGS
19.2k Baud Rate
Flow control: none
8 Bits
No Parity
1 Stop Bit
The red block switch has 2 switches,
the one furthest from the blue connector
is for changing the reading from Dew
Point to RH or vice versa, and the
switch closes to the white connector is
for changing it to degree F or C for both
dew point and temperature.
Update rate is 5 seconds for dew point, or RH and temperature
To change the scaling
Connect the HX200 series to the PC via the above settings
When finished connecting to the PC and the protocol is set:
Hit the “escape” key
The main menu will appear (upper case lettering is used to change the commands)
(O)utput
(R)s232
E(X)it
Select output and follow the instruction.
It will show the present scaling and if you want to change the scaling, select S for Set
and enter the scaling change.
Select ‘Y” to save settings and X for exit until live data streaming appears on your
PC, the new scaling has been changed
Wiring Diagram-HX200 Loop Powered
Iout (4-20mA)
Red
Power
Supply
24 VDC
@500mA
HX200
Black
A
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of
13 months
from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month
grace period to the normal
one (1) year product warranty
to cover handling and shipping time. This
ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, and strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth
in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in
such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED
RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR
WARRANTY
RETURNS, please have the
following information available BEFORE contacting
OMEGA:
1.
Purchase Order number under which the product
was PURCHASED,
2.
Model and serial number of the product under
warranty, and
3.
Repair instructions and/or specific problems
relative to the product.
FOR NON-WARRANTYREPAIRS, consult
OMEGA for current repair charges. Have
the following information available BEFORE
contacting OMEGA:
1.
Purchase Order number to cover the COST
of the repair,
2.
Model and serial number of the product, and
3.
Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2016 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop onlineat omega.com
SM
TEMPERATURE
M
U
Thermocouple,
RTD
&
Thermistor
Probes,
Connectors,
Panels
&
Assemblies
M
U
Wire:
Thermocouple,
RTD
&
Thermistor
M
U
Calibrators
&
Ice
Point
References
M
U
Recorders,
Controllers
&
Process
Monitors
M
U
Infrared
Pyrometers
PRESSURE, STRAIN AND FORCE
M
U
Transducers
&
Strain
Gages
M
U
Load
Cells
&
Pressure
Gages
M
U
Displacement
Transducers
M
U
Instrumentation
&
Accessories
FLOW/LEVEL
M
U
Rotameters,
Gas
Mass
Flowmeters
&
Flow
Computers
M
U
Air
Velocity
Indicators
M
U
Turbine/Paddlewheel
Systems
M
U
Totalizers
&
Batch
Controllers
pH/CONDUCTIVITY
M
U
pH
Electrodes,
Testers
&
Accessories
M
U
Benchtop/Laboratory
Meters
M
U
Controllers,
Calibrators,
Simulators
&
Pumps
M
U
Industrial
pH
&
Conductivity
Equipment
DATA ACQUISITION
M
U
Communications-Based
Acquisition
Systems
M
U
Data
Logging
Systems
M
U
Wireless
Sensors,
Transmitters,
&
Receivers
M
U
Signal
Conditioners
M
U
Data
Acquisition
Software
HEATERS
M
U
Heating
Cable
M
U
Cartridge
&
Strip
Heaters
M
U
Immersion
&
Band
Heaters
M
U
Flexible
Heaters
M
U
Laboratory
Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
M
U
Metering
&
Control
Instrumentation
M
U
Refractometers
M
U
Pumps
&
Tubing
M
U
Air,
Soil
&
Water
Monitors
M
U
Industrial
Water
&
Wastewater
Treatment
M
U
pH,
Conductivity
&
Dissolved
Oxygen
Instruments
M5617/0321
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Omega HX200 Owner's manual

Category
Measuring, testing & control
Type
Owner's manual
This manual is also suitable for

Omega HX200, a versatile dew point/RH transmitter, offers precise humidity measurements for various applications. Its stainless-steel probe with a high-temperature cable enables operations up to 200°C (392°F) and withstands pressures up to 750 PSI. The device provides accurate readings for both dew point and relative humidity (%RH) along with temperature. With its 4-20mA output, the HX200 seamlessly integrates with data acquisition systems and PLCs. Additionally, the RS232 interface allows for remote monitoring and configuration.