Rosemount IO-Link USB Communicator Quick start guide

Type
Quick start guide

Rosemount IO-Link USB Communicator

Below you will find brief product information for Rosemount IO-Link USB Communicator. The IO-Link USB Communicator allows you to apply sensors and actuators with an IO-Link interface (IO-Link devices).

  • The IO-Link devices are described by XML device descriptions, so they can be adjusted and observed in a comfortable and multilingual manner.
  • The tool serves for the pre-adjustment, test, and demonstration of IO-Link devices.
  • The tool is not intended for operations in manufacturing plants.

Rosemount IO-Link USB Communicator

Below you will find brief product information for Rosemount IO-Link USB Communicator. The IO-Link USB Communicator allows you to apply sensors and actuators with an IO-Link interface (IO-Link devices).

  • The IO-Link devices are described by XML device descriptions, so they can be adjusted and observed in a comfortable and multilingual manner.
  • The tool serves for the pre-adjustment, test, and demonstration of IO-Link devices.
  • The tool is not intended for operations in manufacturing plants.
Quick Start Guide
00825-0100-4115, Rev AB
May 2020
Rosemount
IO-Link USB Communicator
Safety messages
WARNING
Installation considerations
Read this guide before working with the product. For personal and system safety, and for optimum
product performance, ensure you thoroughly understand the contents before installing, using, or
maintaining this product.Failure to follow these installation guidelines could result in death or serious
injury. Use the equipment only as specified in this manual. Failure to do so may impair the protection
provided by the equipment. Use the equipment only as specified. Failure to do so may impair the
protection provided by the equipment. Ensure the device is installed by qualified personnel and in
accordance with applicable code of practice. All operation described in this document must be carried
out by authorized, trained personnel only.
Equipment modifications
Do not make changes to the source code or individual components. Changes such as this which are not
explicitly stated in this document may forfeit any rights to technical support by the manufacturer.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end
users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for
all systems used within the facility.
Contents
Overview......................................................................................................................................3
Install hardware............................................................................................................................4
Connections.................................................................................................................................5
Reference information................................................................................................................. 7
Quick Start Guide May 2020
2 Emerson.com/Rosemount
1 Overview
NOTICE
This guide provides basic guidelines for the Rosemount IO-Link USB
Communicator. It does not provide instructions for diagnostics,
maintenance, service, or troubleshooting. This guide is available
electronically on Emerson.com/Rosemount.
This tool allows you to apply sensors and actuators with an IO-Link interface
(IO-Link devices). The IO-Link devices are described by XML device
descriptions so they can be adjusted and observed in a comfortable and
multilingual manner. The tool serves for the pre-adjustment, test, and
demonstration of IO-Link devices. The tool is not intended for operations in
manufacturing plants.
Document purpose
This guide provides information required to install the Rosemount
Transmitter Interface Software.
Release information
Release date: June 1, 2020
May 2020 Quick Start Guide
Quick Start Guide 3
2 Install hardware
Procedure
1. Connect the PC to the USB IO-Link Master with the provided USB
cable.
2. For connection of the interfaces to the IO-Link device, use a standard
4- or 5-pin M12 patch cable.
Quick Start Guide May 2020
4 Emerson.com/Rosemount
3 Connections
Table 3-1: IO-Link connection
M12 (a-Coded connector) interface to the sensor with IO-Link
Pin Signal Function
1 +24 V +24V 1 A / 80 mA
2 IO-Link IO-Link
3 GND 0 V
4 IO-Link IO-Link
5 - NC
Table 3-2: USB connection
Pin Signal Function
1 +5 V VBUS +5VDC/500 mA
2 D- Data -
3 D+ Data +
4 ID Not connected
5 GND Ground
May 2020 Quick Start Guide
Quick Start Guide 5
Table 3-3: Power supply
A USB port provides as standard 500 mA with 5 V. Without wall power supply the IO-
Link Master provides approximately 80 mA with 24 V. Therefore, many IO-Link
devices can be used. If the IO-Link device requires more current, the wall power supply
must be used. The pin assignment is demonstrated below.
Pin Signal
1 +24 V
2 GND
3 GND
Quick Start Guide May 2020
6 Emerson.com/Rosemount
4 Reference information
4.1 Light emitting diodes
The colors and definitions of the light emitting diodes on the USB IO-Link
Master are listed below.
Inscription Color Definition
PWR Yellow Indicates power supply at the USB port
CH1(C/Q) Green/yellow Green: IO-Link mode
LED blinks slowly if no IO-Link connection
LED blinks quickly in pre-operate state
LED constantly lit if IO-Link connection is
active (operate state)
Yellow: SIO mode (indicates digital state at port
C/Q)
CH2(DI/DO) Yellow Indicates the digital state at port DIO
Error Red Flashes in case of errors (e.g. short circuit, errors
in data transmission)
4.2 Dimensions
May 2020 Quick Start Guide
Quick Start Guide 7
*00825-0100-4115*
Quick Start Guide
00825-0100-4115, Rev. AB
May 2020
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 204 8889
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 204 8889
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400
Sunrise, FL 33323, USA
+1 954 846 5030
+1 954 846 5121
Europe Regional Office
Emerson Automation Solutions Europe
GmbH
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
©
2020 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is a mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Rosemount IO-Link USB Communicator Quick start guide

Type
Quick start guide

Rosemount IO-Link USB Communicator

Below you will find brief product information for Rosemount IO-Link USB Communicator. The IO-Link USB Communicator allows you to apply sensors and actuators with an IO-Link interface (IO-Link devices).

  • The IO-Link devices are described by XML device descriptions, so they can be adjusted and observed in a comfortable and multilingual manner.
  • The tool serves for the pre-adjustment, test, and demonstration of IO-Link devices.
  • The tool is not intended for operations in manufacturing plants.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI