Haier AB142ACNAC User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

HBU-14CL03/R1 (AB142ACNAC+AU142AANAC)
HBU-18CL03/R1 (AB182ACNAC+AU182AANAC)
HBU-24CL03/R1 (AB242ACNAC+AU242AANAC)
HBU-28CM03/R1 (AB28NACNAC+AU28NAANAC)
HBU-36CM03/R1 (AB36NACNAC+AU36NAANAC)
HBU-42CM03/R1 (AB42NACNAC+AU42NAANAC)
MANUAL CODE: SYJS-006 EDITION:2002.12.31.
Haier Group
Super low outdoor ambient cooling at -15
Auto-restart function
Group control(if connect with a group controller)
Auto-changeover
Compact design of indoor unit
Weekly timing(if connect with a weekly timer)
With new environment friendly refrigerant R407C
Features
Service Manual
Commercial Air Conditioning
Cassette Type Low Ambient Cooling Series
CONTENTS
1. Description of Products & Features…………………...…….1
2. Specifications…………………………. ………………...……3
3. Safety precaution…………………………..………………….9
4. Net dimensions of indoor and outdoor unit………………...11
5. Installation instructions ……………………. ………………..17
6. Parts and functions …………………………..…… ..……….28
7. Remote controller functions………………………….………31
8. Refrigerant diagram…………………………..……………....43
9. Electrical control functions……………………………………44
10. Diagnostic information(trouble shooting)…………….……51
11. Electrical data.........................................…………….……56
12. Exploded views and parts lists...............……………. ……67
13. Perdormance curves……………............................... ……87
14. Noise level charts.....……………............................... ……93
15. Air velocity distribution …………............................... ……94
CONTENTS
Contents…….................................................………...…….1
- 1 -
1 DESCRIPTION OF PRODUCTS & FEATURES
1.1 Products coding direction
Old code
H BU – 42 C M 03 / R1
Refers to HFC refrigerant
Power: 03(230V/50Hz).04(240V/50Hz).12(115V/60Hz).13(230v/60Hz)
Low ambient cooling
“H” refer to cooling and heating, ”C” refer to cooling only
Nominal cooling capacity (BTU/h), 42=42000BTU/h
Indoor and outdoor unit code: "B" Cassette type; "U" Outdoor unit
“H” means “Haier”
New code
A B 42 N A C N A C
Climate type: T1 (see table 1), and -15 degree cooling
Design number (A stands for fix speed type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407
M stands for cool only type, refrigerant is R22
N stands for cool only type, refrigerant is R407
Appearance character
Product series: one by one type
Applicable voltage: 2 stands for 220-240V/50Hz,4 stands for 220v/60Hz
N stand for 380V/50Hz
Cooling / Heating capacity,42=42000BTU/h
Product type : “B” stands for cassette type, “C” stands for convertible
type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller
system, "E" stands for ceiling concealed type, “U” stands for outdoor unit
Air conditioner
1.2 Brief Introduction to T1 T2 T3 working condition
Table 1
Climate type
Type of Air Conditioner
T1 T2 T3
Cool only
18
43 10 35 21 52
Heat pump
-7
43 -7 35 -7 52
Electricity heating
43 35 52
1.3 Operating Range of air conditioners
Low ambient cooling
Operation Operation Range Outside / Inside
Cooling
-15
0
C – 43
o
C
Dehumidifying
-15
0
C – 43
o
C
- 2 -
DESCRIPTION OF PRODUCTS & FEATURES
1.4 Products characteristic
Completely invisible machine body
The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither
breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air
conditioner allows it to blend right into ceiling.
Superbly efficient healthy filter
Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently.
Flexible and easy installation
Slim design with machine body, completely ceiling concealing and portable shape, all make it
greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce
constructional cost prices. It also features a specific drainage system with up to 600mm lift , which
allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free"
mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit
people's comfortable need much more.
Auto-Restart function
When meeting a power failure during running, no matter how long it will be, once the power is
restored, air conditioner will automatic restart with the previous status.
Safety and reliable control due to various signal controls
1 Inputting with press buttons on the panel
2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe
temperature sensors, outdoor ambient temperature sensors, outdoor coil pipe temperature
sensors)
3 Piping pressure signals
4 Compressor current signals
5 Testing signals
6 System time-shorten signal
7 Water overflowing signal
8 Communication signals between indoor unit and front plate or between indoor unit and outdoor unit .
Precise convenient remote-controlling
When using remote-controlling mode, it is comfortable and convenient to operate.
Silent design
The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to significantly
decrease operating noise.
HFC refrigerant technology
To protect the environment, we have adopted the HFC refrigerant. The HFC R407C is of aero ODP
for the purpose of environmental protection.
Low ambient temperature cooling technology
The system can run the cooling operation at the low ambient temperature -15
- 3 -
DESCRIPTION OF PRODUCTS & FEATURES
Function
Cooling Heating
Capacity BTU/h
14000 /
W
2000 /
EER or COP BTU/W
7.00 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current A
Power cable
Unit model (color)
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Control type (wireless/wired)
Fresh air hole dimension mm
Noise level (H-M-L) dB(A)
kg
External mm×mm×mm
Package mm×mm×mm
kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm
Connect method
Drop
m
Piping length
m
Item Model
HBU-14CL03/R1
1
1PH, 220V-230V, 50HZ
/
Indoor unit
AB142ACNAC / WHITE
CENTRIFUGAL×1
840/650/560
830
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
700×570×276
775×715×361
PVC 18/20
wireless
/
41/39/35
Weight (net / gross)
26/28
Panel
Dimension
L×W×H
630×630×95
685×685×155
Weight (net / gross)
4.2 / 6.3
Outdoor unit
AU142AANAC / WHITE
PG330X2CS-4KU1 / Guangdong TOSHIBA
scroll
Axial-flow×1
800
700/-/-
TP2M/9.52
2/2
0.225
43-60
Dimension
L×W×H
780×250×660
907×344×690
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
49/-/
Four way valve
/
Between
I.U. & O.U.
MAX :5
MAX :15
Total power input
Weight (net / gross)
40/48
Piping
R407C
1.95
6.35
2 SPECIFICATIONS
9.52/48.5
/
- 4 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
18000 /
W
2000 /
EER or COP BTU/W
9.00 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current/Starting current A
Power cable
Unit model (color)
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Control type (wireless/wired)
Fresh air hole dimension mm
Noise level (H-M-L) dB(A)
kg
External mm×mm×mm
Package mm×mm×mm
kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm
Connect method
Drop
m
Piping length
m
Item Model
HBU-18CL03/R1
1
1PH, 220V-230V, 50HZ
/
Indoor unit
AB182ACNAC / WHITE
CENTRIFUGAL×1
500/450/380
1050
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
750×750×280
900×900×420
PVC 18/20
wireless
/
43/42/40
Weight (net / gross)
29/39
Panel
Dimension
L×W×H
750×750×80
800×800×180
Weight (net / gross)
3.5/5.8
Outdoor unit
AU182AANAC / WHITE
PG330X2CS-4KU1 / Guangdong TOSHIBA
scroll
Axial-flow×1
800
700/-/-
TP2M/9.52
2/2
0.225
43-60
Dimension
L×W×H
810×288×680
960×406×760
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
52/-/46
Four way valve
/
Between
I.U. & O.U.
MAX :5
MAX :15
Total power input
Weight (net / gross)
58/66
Piping
R407C
1.95
6.35
/
7.8/38.2
- 5 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
24000 /
W
2800 /
EER or COP BTU/W
8.57 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current A
Power cable
Unit model (color)
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Control type (wireless/wired)
Fresh air hole dimension mm
Noise level (H-M-L) dB(A)
kg
External mm×mm×mm
Package mm×mm×mm
kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm
Connect method
Drop
m
Piping length
m
Item Model
HBU-24CL03/R1
3
1PH,220V~230V,50Hz
/
Indoor unit
AB242ACNAC / WHITE
CENTRIFUGAL×1
700/590/470
1300
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
840×840×240
910×910×300
PVC 18/20
wireless
/
39/37/35
Weight (net / gross)
28/30
Panel
Dimension
L×W×H
950×950×80
980×980×100
Weight (net / gross)
6/9
Outdoor unit
AU242AANAC / WHITE
ZR34K3E-PFJ-522 / Copeland
scroll
Axial-flow×1
840/-/-
3240
TP2M/9.52
3/3
0.62
43-60
Dimension
L×W×H
948×830×340
1050×979×440
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
58/-/50
Four way valve
/
Between
I.U. & O.U.
MAX :15
MAX : 30
Total power input
Weight (net / gross)
70/85
Piping
R407C
2.5
9.52
13.5/65 /
- 6 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
28000 /
W
2800 /
EER or COP BTU/W
10.0 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current A
Power cable
Unit model (color)
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Control type (wireless/wired)
Fresh air hole dimension mm
Noise level (H-M-L) dB(A)
kg
External mm×mm×mm
Package mm×mm×mm
kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm
Connect method
Drop
m
Piping length
m
Item Model
HBU-28CM03/R1
3
3N,380V~400V,50Hz
/
Indoor unit
AB28NACNAC / WHITE
CENTRIFUGAL×1
700/590/470
1300
TP2M/9.52
2/2
0.199
2-7
Dimension
L×W×H
840×840×240
910×910×300
PVC 18/20
wireless
/
39/37/35
Weight (net / gross)
28/30
Panel
Dimension
L×W×H
950×950×80
980×980×100
Weight (net / gross)
6/9
Outdoor unit
AU28NAANAC / WHITE
ZR34K3E-PFJ-522 / Copeland
scroll
Axial-flow×1
840/-/-
3240
TP2M/9.52
3/3
0.62
43-60
Dimension
L×W×H
948×830×340
1050×979×440
PVC,18/20
Capillary
Defrosting
Auto
15.88
FLARED
58/-/50
Four way valve
/
Between
I.U. & O.U.
MAX :15
MAX : 30
Total power input
Weight (net / gross)
70/85
Piping
R407C
2.5
9.52
13.5/65 /
- 7 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
36000 /
W
3900 /
EER or COP BTU/W
9.23 /
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current A
Power cable
Unit model (color)
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Control type (wireless/wired)
Fresh air hole dimension mm
Noise level (H-M-L) dB(A)
kg
External mm×mm×mm
Package mm×mm×mm
kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm
Connect method
Drop
m
Piping length
m
Item Model
HBU-36CM03/R1
5
3N, 380V-400V, 50HZ
/
Indoor unit
AB36NACNAC / WHITE
CENTRIFUGAL×1
780/710/630
950
TP2M/9.52
3/3
0.199
2-7
Dimension
L×W×H
840×1230×280
910×1320×300
PVC 18/20
wireless
/
43/41/38
Weight (net / gross)
38/55
Panel
Dimension
L×W×H
950×1340×80
995×1400×115
Weight (net / gross)
8.4/12
Outdoor unit
AU36NAANAC / WHITE
C-SBN303H8A / SANYO
scroll
Axial-flow×2
840/-/-
6000
TP2M/9.52
5/5
0.92
43-60
Dimension
L×W×H
948×1225×340
1050×1375×440
PVC,18/20
Capillary
Defrosting
Auto
19.05
FLARED
52/-/46
Four way valve
/
Between
I.U. & O.U.
MAX :30
MAX : 50
Total power input
Weight (net / gross)
85/111
Piping
R407C
3.2
9.52
- 8 -
SPECIFICATIONS
Function
Cooling Heating
Capacity BTU/h
42000 /
W
4500 /
EER or COP BTU/W
9.3/
Dehumidifying capacity
10³×m³/h
Power source PH-V-Hz
Running current A
Power cable
Unit model (color)
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Control type (wireless/wired)
Fresh air hole dimension mm
Noise level (H-M-L) dB(A)
kg
External mm×mm×mm
Package mm×mm×mm
kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/min
Air-flow(H-M-L) m³/h
Heat exchanger Type / Diameter
Flow
Total area
Temp. scope
External mm×mm×mm
Package mm×mm×mm
Drainage pipe (material , I.D./O.D.)
Refrigerant control method
Noise level
H-M-L
dB(A)
kg
Refrigerant Type
Charge kg
Pipe Liquid mm
Gas mm
Connect method
Drop
m
Piping length
m
Item Model
HBU-42CM03/R1
5
3N, 380V-400V, 50HZ
/
Indoor unit
AB42NACNAC / WHITE
CENTRIFUGAL×3
980/880/820
2040
TP2M/9.52
3/3
0.199
2-7
Dimension
L×W×H
840×1230×280
911320×300
PVC 18/20
wireless
/
43/41/39
Weight (net / gross)
46/53
Panel
Dimension
L×W×H
950×1340×80
995×1400×115
Weight (net / gross)
8.4/12
Outdoor unit
AU42NAANAC / WHITE
H73A623DBEA / Bristol
scroll
Axial-flow×2
840/-/-
6000
TP2M/9.52
5/5
0.92
43-60
Dimension
L×W×H
948×1225×340
1050×1375×440
PVC,18/20
Capillary
Defrosting
Auto
19.05
FLARED
64/-/-
Four way valve
/
Between
I.U. & O.U.
MAX :30
MAX : 50
Total power input
Weight (net / gross)
85/111
Piping
R407C
3.2
9.52
/
/
- 9 -
SPECIFICATIONS
WARNING
CAUTION
WARNING
CAUTION
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior
environment such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned
countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,
and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold
concentration does occur,there is the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive
use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and
fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat
generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
WARNING
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please
explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's
manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.
Please read these "Safety Precautions" first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, and
those points which are related to the strong possibility of an installation done in error
resulting in death or serious injury are listed in the section. However, there is also a
possibility of serious consequences in relationship to the points listed in the section as well.
- 10 -
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (please see nameplate) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refigerant leakage.
The position of indoor unit must be above the floor 2.5m.
WARNING
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone
ground wire.
Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not
installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
CAUTION
- 11 -
SAFETY PRECAUTIONS
Model: HBU-14CL03/R1 Indoor unit
4 NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Model: HBU-14CL03/R1 Outdoor unit
- 12 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
362
35
75
185
270
122
45
92
104
240
30
90
170
113
131
30
70
32
48
660
270
660
480
30
265
220
200
580
288
810
680
75
65
150
100 100
110
190
170
400
Model: HBU-18CL03/R1 Indoor unit
Model: HBU-18CL03/R1 Outdoor unit
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Model: HBU-24CL03/R1 HBU-28CM03/R1 Indoor unit
180
5555
260
160
240
180
50
30
20
135
1000
以上
安装所需位置
155
950
840
295
950
(悬挂位置)
(天花板开孔)
840
(天花板开孔)
( )
860-890
780
悬挂位置
780
860-890
以上
1500
1500
1500
以上
1500
以上
以上
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
Note (1) Fix the parts with screws
(2)Don't intake the strong wind directly
to the outlet air-flow hole.
(3)A one meter distance should be
kept from the unit top
(4)Don't block the surroudings of the unit with sundries.
Installation Servicing Space(at Least)
Unit:mm
Installation
I
300
100
0
0
150
0
500
100
0
II III
Dimension
L1
Leave space Leave space
Leave space
L2
L3
L4
185 185
55
70
70
Screw Hole
(M10)
580
Power Wiring Terminal
Power Wiring
Distribution Hole
L1
L2
L3
L4
Back Air-flow Hole
Back Air-
flow Hole
Outlet Air-flow Hole
Repairing Space
70
1024
840
25
Model: HBU-24CL03/R1 HBU-28CM03/R1 Outdoor unit
380
18
340
18
- 15 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
1340
950
840
30
220
20
50
280
260
315
270
135
160
300
295
1070
780
860-890
615
615
1250-1280
(ceiling hole)
over1000
mm
155
123055 55
220
over1500
over1500
over1500
over1500
(hanging position)
Model: HBU-36CM03/R1 HBU-42CM03/R1 Indoor unit
- 16 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
185 185
30
52
88
Screw Hole
(M10)
580
950
Power wiring Terminal
70
1818
340
380
1250
25
Note : (1). Fix the parts with screws
(2).Don't intake the strong wind directly
to the outlet air-flow hole.
(3).A one meter distance should be
kept from the unit top
(4).Don't block the surroundings of the unit with sundries
Installation Servicing Space(at Least)
Unit:mm
Installation
I
300
100
0
0
150
0
500
100
0
II III
Dimension
L1
Leave space Leave space
Leave space
L2
L3
L4
L1
L2
L3
L4
Back Air-flow Hole
Back Air-
flow Hole
Outlet Air-flow Hole
Repairing Space
Model: HBU-36CM03/R1 HBU-42CM03/R1 Outdoor unit
- 17 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
5.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner,
shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter
7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor
11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump
15 .Flat screwdriver
5.2 Standard accessories
Part name
QTY
Shape
Clamp
2 Piece
Washer
8 Piece
6 Piece
Clamp Paper pattern
1 Set
6321
3 Piece
Screw(M5 size)
For installation
of
paper pattern
Drain hose
1 Piece
Please check if your unit is delivered with following
Part name
QTY
Shape
Dry battery
Insulator Sealing pad Sealing pad Sealing pad
7
8 9
12
1 Piece 1 Piece
Insulator
2 Piece 1 Piece 1 Piece 2 Piece
Small sizeMedium sizeLarge size
For liquid pipeFor gas pipe
R03, 7#
[Other]
Operation
Manual
Ornament
panel
Remote
controller
54
1110
5.3 Installation of indoor unit
5.3.1 Before installation
Determine the way kto carry unit to installation place.
Don't remove packing until unit reaches installation place.
If unpacking is unkavoidable, protect unit properly.
5.3.2 Selection of installation place
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured.
No block to air flow.
Water drainage is smpoth.
Place strong enough to support unit weight.
Place where inclination is not evident on ceiling.
Enough space for mainenance.
Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)
Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This
is helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio
wave is strong)
- 18 -
INSTALLATION INSTRUCTIONS
5 INSTALLATION INSTRUCTIONS
8
260
260
(2) Ceiling height
Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and Installation
Manual of ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take
necessary measures in case it is not safe. (Distance between holes are marked on paper pattern.
Refer to paper pattern for place need be reinforced)
Installation space
Air inlet
Air outlet
2500 Over
Air outlet
1500 Over
1500 Over
1500 Over
1500 Over
Air outlet
Air inlet
Air inlet
5.3.3 Preparation
Ornament panel 630mm
ceiling opening 600mm
Indoor unit 570mm
Distance between
Indoor unit 570mm
Ceiling opening 600mm
Ornament panel 630mm
suspending bolts 460mm
210mm
335mm
35mm
Overlap between ceiling and
ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
(1) Position of ceiling opening between unit and suspending bolt.
HBU-14
Unit: mm
Ceiling hole size 690
Suspension bolts pitch 620
Suspension bolts pitch 465
Suspension bolts pitch 485
H BU-18
260mm
Overlap between ceiling and
ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
- 19 -
INSTALLATION INSTRUCTIONS
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99

Haier AB142ACNAC User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI