Siemens JXD2(-A) Molded Case Circuit Breaker is a versatile and reliable device designed for use with Siemens JD, JM, LD, LM, JF, & LF Frame Circuit Breakers, Molded Case Switches, & Motor Circuit Interrupters. It features plug-in mounting assemblies for easy installation and removal, and is suitable for a wide range of applications including industrial, commercial, and residential settings. The JXD2(-A) offers enhanced safety features such as pressure wire connectors and tulip clip assemblies to ensure a secure electrical connection.

Siemens JXD2(-A) Molded Case Circuit Breaker is a versatile and reliable device designed for use with Siemens JD, JM, LD, LM, JF, & LF Frame Circuit Breakers, Molded Case Switches, & Motor Circuit Interrupters. It features plug-in mounting assemblies for easy installation and removal, and is suitable for a wide range of applications including industrial, commercial, and residential settings. The JXD2(-A) offers enhanced safety features such as pressure wire connectors and tulip clip assemblies to ensure a secure electrical connection.

Hazardous voltage.
Will cause death or
serious injury.
Turn OFF and lock out all
power supplying this
device before installing
or servicing accessory.
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.
Installation Instructions
Item: Cat. No. TCJ2, TCJ3 Plug-In Adapters
For use with: SIEMENS®JD, JM, LD, LM, JF, &
LF Frame Circuit Breakers, Molded Case
Switches, & Motor Circuit Interrupters in con-
junction with plug-in mounting assemblies Cat.
No.’s PC5777, PC5778, PC5660, PC5661,
PM5661 and PM5778.
Page 1 of 3
Pc. No. 410903A01
BREAKERS TYPES
SAFETY INSTRUCTIONS
JXD2(-A), JXD6(-A), JXD6(-A)ETI,
HJXD6(-A), HHJXD6, SJD6(-A),
SHJD6(-A), JFC, JFF, JM6, JMK
LXD6(-A), LXD6(-A)ETI, HLXD6(-A),
HHLXD6(-A), SLD6(-A), SHLD6(-A),
LFC, LFF, LM6, LMK
CJD6(-A), CJD6(-A)ETI, SCJD6(-A),
JDFP(-A)
CLD6(-A), CLD6(-A)ETI, SCLD6(-A),
LDFP(-A)
NOTE: These instructions outline the recommended
installation procedure.
1. Circuit Breaker Preparation
The circuit breaker should be in the OFF/”O” posi-
tion before installing the plug-in-tulip adapter kit. Turn
off and lock out all power supplying this device be-
fore installing. Verify that
NO
voltage is present be-
fore proceeding with task.
2a. Note: For Current Limiting Circuit Breakers Load end only. (See pg. 3). Place tulip clip assembly (5) on back of
breaker terminal. Attach and shield bracket (13) (From end shield assembly, catalog number’s CLTCJL2 or
CLTCJL3) from front of breaker as shown in fig. 4a. Secure in place with ¼ in. belleville washers (6) and ¼-20 x
1 in. hex head bolts (7) furnished. Tighten bolts to 60-72 in-lbs. [6.78-8.13 N/m] to assure a good electrical
connection.
2b. Attach end shield (14) to end shield bracket (13) using the four molded pan head screws (15). Tighten screws to
5 in-lbs. [.56 N/m] max.
3. Slide one piece end shields (8) into slots provided in breaker case at line and load ends of breaker.
Note: For Current Limiting Circuit Breakers, attach one piece end shields to load end only.
4. Attach terminal shields to line and load side of circuit breaker.
5. Add accessory label (9) to top of breaker as indicated in figures.
BREAKER PREPARATION: REMOVE PRESSURE
WIRE CONNECTORS FROM BREAKER IF PRESENT
2. Place tulip clip assembly (5) on back of breaker in
recess provided in base molding. Secure in place
with ¼” belleville washers (6) and ¼”-20 X 1 hex
head bolts (7) furnished. Recommended tighten-
ing torque for these bolts is 60-72 in-lbs. [6.78-8.13
N/m] to assure a good electrical connection. Re-
peat this procedure for the remaining tulip clip as-
semblies.
Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Installation Instructions
Hazardous voltage.
Will cause death or
serious injury.
Turn OFF and lock out all
power supplying this
device before installing or
servicing accessory.
Page 2 of 3
Pc. No. 410903A01
¼ - 20 x 1 [6.78-8.13 Nm]
60-72 LB.IN.
JXD2(-A), JXD6(-A), JXD6(-A)ETI,
HJXD6(-A), HHJXD6, SJD6(-A), JFC,
JFF, LXD6(-A), LXD6(-A)ETI,
HLXD6(-A), HHLXD6(-A), SLD6(-A),
SHLD(-A), LFC, LFF, JM6, JMK,
LM6, LMK
[2.00] = MM
0.00 = IN
TCJ2
4 x 8
TCJ3
8 x 6
8 x 7
4 x 5
6 x 8
6 x 5
12 x 6
12 x 7
1 x 9
1 x 9
Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Installation Instructions
Page 3 of 3
Pc. No. 410903A01
© 1998 Siemens Energy & Automation, Inc.
Hazardous voltage.
Will cause death or
serious injury.
Turn OFF and lock out all
power supplying this
device before installing or
servicing accessory.
CJD6(-A), CJD6(-A)ETI,
SCJD6(-A)
CLD6(-A), CLD6(-A)ETI,
SCLD6(-A)
¼ - 20 x 1 [6.78-8.13 Nm]
60-72 Lb.In.
[.56 Nm]
5 Lb.In.
15
7
[2.00] = MM
0.00 = IN
TCJ2
TCJ3
2 x 8
4 x 5
8 x 6
8 x 7
2 x 14 8 x 15
2 x 13
3 x 8
6 x 5
1 x 9
12 x 6
3 x 13
12 x 7
12 x 15
3 x 14
1 x 9
  • Page 1 1
  • Page 2 2
  • Page 3 3

Siemens JXD2(-A) Molded Case Circuit Breaker User manual

Type
User manual

Siemens JXD2(-A) Molded Case Circuit Breaker is a versatile and reliable device designed for use with Siemens JD, JM, LD, LM, JF, & LF Frame Circuit Breakers, Molded Case Switches, & Motor Circuit Interrupters. It features plug-in mounting assemblies for easy installation and removal, and is suitable for a wide range of applications including industrial, commercial, and residential settings. The JXD2(-A) offers enhanced safety features such as pressure wire connectors and tulip clip assemblies to ensure a secure electrical connection.