INSTRUCTIONS
© 2018 OJ Electronics A/S
1
67136B 09/18 - (OSH)
OJ Air2 EXT45
• English
• Deutsch
• Français
• Svenska
• Norsk
• Dansk
English
LIST OF FIGURES
The following figures are located at the back of the instructions:
Fig. 1: Dimensions
Fig. 2: RJ12 ports for Modbus communication
Fig. 3: Pin connections in Modbus port
Fig. 4: Electrical terminal connections
Fig. 5: Modbus connection cable
INTRODUCTION
OJ Air2 EXT45 is an extension module for OJ Air2 ventilation systems controlled by
an OJ Air2 Master. The module has been specially designed for ventilation systems.
OJ Air2 EXT45 is equipped with thermistor inputs and analogue/digital inputs
and outputs, allowing more complex and energy ecient ventilation systems to
be designed.
RS485 Modbus communication makes the system ideal for energy management
in buildings.
OJ Air2 EXT45 can be pre-installed in cooling units or other components which
are subsequently integrated with the ventilation system. Thanks to RS485 Mod-
bus connection, OJ Air2 EXT45 can be installed at a minimum of cost.
PRODUCT PROGRAMME
Type Product
OJ Air2 EXT45 Extension module for OJ Air2
OJ Air2 EXT Extension module for OJ Air2
OJ Air2 Master Controller for air handling unit, Modbus, IP20
OJ Air2 Fan IO
IO module with two pressure transmitters and analogue/
digital inputs and outputs
OJ Air2 HTERM Hand terminal for operating OJ Air2 system
OJ Air2 LON LON module for connection to BMS system
INSTALLATION
OJ Air2 EXT45 should be mounted on a standard 35 mm DIN rail and installed in
a control panel or similar enclosure which complies with local requirements on
electrical installations.
The 24 V DC supply voltage is provided via the Modbus connection. The enclo-
sure rating is IP20.
Input and output signals are connected to OJ Air2 EXT45 via screw/socket con-
nectors each of which has screw terminals for max. 1.5 mm² (Cu). A maximum of
two OJ Air2 EXT45 modules can be connected to the OJ Air2 Master.
OJ Air2 EXT45 is equipped with:
• 5 x digital potential-free inputs sa
• 5 x digital potential-free relay outputs, max. 230 V AC/DC, max. 5 A,
cosΦ>0.4
• 4 x analogue inputs (0-10 V DC)
• 4 x analogue outputs (0-10 V DC)2 x RJ12 ports for internal system Modbus
RS485
Supply voltage
The OJ Air2 EXT45 module is provided with a 24 V AC power supply via the
Modbus cable. Modbus connection is illustrated in figs. 2 and 3. Modbus cable
connection is illustrated in fig. 5.
Connection of OJ Air2 hand terminal
It is not possible to connect an OJ Air2 hand terminal to the OJ Air2 EXT45 module.
The hand terminal must always be connected to the OJ Air2 Master using the port
marked
.
Installation of Modbus cable
Modbus is connected to OJ Air2 EXT45 via one of the two RJ12 Modbus ports.
OJ Air2 EXT45 is equipped with two RJ12 ports, allowing Modbus connection
and looping to other Modbus components in the application concerned. The
Modbus ports are connected internally in parallel.
Setting OJ Air2 EXT45 addresses
The Modbus address is set using the switch on the front of the OJ Air2 EXT45
module. The address is specified as a Hex decimal value and can be set within
the address range Hex 21 (switch position 1) to Hex 2F (switch position F). The
address Hex 20 (switch position 0) is reserved for factory testing.
When the OJ Air2 EXT45 module is connected to an OJ Air2 Master, only:
Switch position 1 = Extensionmodul45 1 (HEX 21) or Switch position 2 = Exten-
sionmodul45 2 (HEX 22) can be used as addresses.
Digital inputs
OJ Air2 EXT45 is equipped with five potential-free digital inputs.
Digital input 1 should be connected to the "DIN 1" input, terminals 27 & 28 (GND).
Digital input 2 should be connected to the "DIN 2" input, terminals 29 & 30 (GND).
Digital input 3 should be connected to the "DIN 3" input, terminals 31 & 32 (GND).
Digital input 4 should be connected to the "DIN 4" input, terminals 33 & 34 (GND).
Digital input 5 should be connected to the "DIN 5" input, terminals 35 & 36 (GND).
Electrical connections are shown in fig. 4. (Modbus register see fig. 6).
Digital outputs
OJ Air2 EXT45 is equipped with five potential-free digital relay outputs.
The digital outputs should be connected to max. 230 V AC/DC, max. 5 A, cosΦ>0.4.
Digital output 1 should be connected to the "Dou 1" output, terminals 17 & 18.
Digital output 2 should be connected to the "Dou 2" output, terminals 19 & 20.
Digital output 3 should be connected to the "Dou 3" output, terminals 21 & 22.
Digital output 4 should be connected to the "Dou 4" output, terminals 23 & 24.
Digital output 5 should be connected to the "Dou 5" output, terminals 25 & 26.
Electrical connections are shown in fig. 4. (Modbus register see fig. 6).
Analogue inputs
OJ Air2 EXT45 is equipped with four 0-10 V DC analogue inputs.
Analogue input 1 should be connected to the "Ain 1" input, terminals 9 (GND) & 10 (+)
Analogue input 2 should be connected to the "Ain 2" input, terminals 11 (GND) & 12 (+)
Analogue input 3 should be connected to the "Ain 3" input, terminals 13 (GND) & 14 (+)
Analogue input 4 should be connected to the "Ain 4" input, terminals 15 (GND) & 16 (+)
Accuracy < ±4%, resolution 10 mV, Rin 20 kΩ.
Electrical connections are shown in fig. 4. (Modbus register see fig. 6).
Analogue outputs
OJ Air2 EXT45 is equipped with four 0-10 V DC analogue outputs.
Analogue output 1 should be connected to the "Aou 1" output, terminals 1 (GND) & 2 (+)
Analogue output 2 should be connected to the "Aou 2" output, terminals 3 (GND) & 4 (+)
Analogue output 3 should be connected to the "Aou 3" output, terminals 5 (GND) & 6 (+)
Analogue output 4 should be connected to the "Aou 4" output, terminals 7 (GND) & 8 (+)
Accuracy < ±4%, resolution 10mV, ripple < 10mV, Iout 0-10mA, Rout < 10 Ω.
Electrical connections are shown in fig. 4. (Modbus register see fig. 6).
GND
All GND terminals (terminals 1, 3, 5, 7, 8, 9, 11, 13, 15, 28, 30, 32, 34 & 36) are
interconnected within the module and have the same electric potential.
LEDs
The front of the OJ Air2 EXT45 module is equipped with two LEDs. A "Power"
LED, which lights when the EXT45 module is powered up, and a "Com" LED,
which flashes during Modbus communication.
TECHNICAL DATA
Supply voltage ..............................24 V DC via Modbus
Power consumption at max. load .180 mA
Electrical signal connection ..........Max. 1.5 mm², screw connector terminals
System Modbus ...........................RS485, 38.4 kBd, 24 V DC, RJ12 port
Modbus connection .....................2 x RJ12 6/6 connectors