Anybus AB7565 Installation guide

Type
Installation guide
Anybus X-gateway - FIP IO Slave Interface Network Installation Sheet
www.anybus.comSP1761, rev. 2.00, Apr 2015
Accessories Checklist
The following items are required for installation:
USB cable (included)
FIP IO con guration tool (not included)
FIP IO cable (not included)
Installation and Startup Summary
1. Set the node address
2. Connect the gateway to the network
3. Connect a PC to the gateway via USB (optional)
4. Power up and (if required) con gure the gateway
NOTE: Address 0 and 63 are reserved. Addresses 64 to 99 can only
be used if supported by the eldbus control system (e.g. the PLC).
Technical Support
Technical support, documentation and software downloads are
available at www.anybus.com.
LED Indicators
LED Indication Meaning
GW Status See Gateway Installation Sheet
RUN Green Normal operation
Off No power, or major failure
ERR
Red Major fault (unrecoverable)
Red ( ashing) Bus not connected, or timeout error
Off No error
I/O Green External device error
Off Normal operation
COM Yellow Bus activity
Off No activity
Top-mounted
GW Status
ERR
RUN
I/O
COM
GW Status
ERR
RUN
I/O
COM
USB
(X4)
USB
(X4)
B
otto
m-m
ou
n
ted
Product Overview
The FIP IO Slave interface can be either top- or bottom-mounted.
Both of these options are illustrated below.
Top-mounted Interface
FIP IO Connector (X1)
Node Address x 10
Node Address x 1
Power Connector (X3)
Bottom-mounted Interface
FIP IO Connector (X2)
Node Address x 10
Node Address x 1
FIP IO Connector
Pin Signal
15
96
1, 2, 3, 4, 5 (not connected)
6 A (D+)
7 B (D-)
8 B (D-)
9 A (D+)
Housing PE
Node Address Switches
Two rotary DIP switches are used to set the node address of the
interface between 1 and 99.
Example:
Address = 42 (4 x 10) + (2 x 1)
x10 x1