HELVAR LCM Modular Lighting Control Module Installation guide

Type
Installation guide
Helvar | Data subject to change without notice www.helvar.com 1
Modular LCM Datasheet and
Installation Guide
Overview
The modular LCM is a cost effective method of providing power and control for
lighting installations in industrial, commercial and retail buildings. The system
is designed for ease of installation: mains input is connected using the spacious
wiring compartment, DALI control inputs and outputs are pluggable using industry
standard connectors. The modular approach allows for between 2 and 16 luminaires
to be connected.
System Components
Note: Allow 150mm for total height of unit (including connectors and cable)
159mm 202mm 122mm
Fixing point
127mm
75mm
150mm
105mm
146mm
BVITM6-S2-HELVAR
2 Output Starter Module
BVITM6-S-HELVAR
4 Output Starter Module
BVITM6-E-HELVAR
4 Output Extender Module
Helvar | Modular LCM Installation Guide www.helvar.com 2
Installation of Box
4 x key slots to accept
M6 (1/4”) fixings BESA box fittings
Channel for channel
nuts (zebs)
Removable gland
plate with 3 x
Ø20mm knockouts
3 x Ø20mm knockouts
for rear cable entry
The box should be fixed on a smooth, flat surface or using drop rod fixings attached to channel
nuts.
Ensure that there is easy access to the wiring compartment and all connectors once the box is
in-situ.
Warning: This device works at mains voltage. Be sure to take care when working with
electricity.
Helvar | Data subject to change without notice www.helvar.com 3
Example Network Diagram (Imagine Router System)
L, N, E
Note: Router
supply must be
protected at 6A
maximum.
Power
PL, SWL, N, E
DALI
DA+, DA-
PL, N, E,
DA+, DA- SWL, N, E,
DA+, DA-
E
DALI Emergency Luminaire DALI Luminaire
Sensor
DA+, DA-
Button
Modules
Switch
Inputs
Emergency
Luminaire
Router DALI Subnet Limitations
300m max cable run
64 addresses
240mA
Example: Indicative system schematic only. Max 5 x LCMs per DALI subnet (average 10 port LCM + 1 sensor + 1 Switch input).
Contractor must provide appropriate isolation, cabling and reference other system component install guides.
PL, N, E
E
Ethernet
Imagine 910 Router
(Mounted in restricted
access location).
Helvar | Modular LCM Installation Guide www.helvar.com 4
Wiring
Cable Clamps
Large cables
Luminaire connectors/Lead colours
Small cables
DIM+ (DALI+) Red
DIM- (DALI -) White
Permanent Live Black (6 core only)
Neutral Blue
Earth Green/Yellow
Switched Live Brown
DALI+
DALI -
Permanent Live
Neutral
Earth
Switched Live
Not for use
Not for use
Live
Warning: For correct installation,
connector plugs must be fully engaged
and latched on both sides.
All wiring must be mains rated.
Remove wiring compartment cover.
Wire the box using the diagrams below.
Switched Live for normal fittings
Permanent live feeds emergency fittings
Use the cable clamps to secure the wiring or use cable glands (not supplied). The clamps
can be split, and flipped over to clamp different cable diameters.
Replace wiring compartment cover.
Plug in the luminaires ensuring that the connector latches to the box.
Note: Live is NOT internally
connected and NOT fed through
to outputs. See page 5.
Helvar | Data subject to change without notice www.helvar.com 5
Wiring Layout and Emergency Test
Local lighting switch and local emergency test switch
Emergency test using power interruption
Emergency test using central switch
Warning: Do not wire across phases
DA+
DA-
DA+
DA-
Central
emergency
test switch or
controllable relay
e.g. Helvar 492
Wire link
DA+
DA-
Local emergency
test switch
N E L
N E L
N E L Multiple boxes
Helvar | Modular LCM Installation Guide www.helvar.com 6
WDA005
7860412 Issue 02
2019-09-23
Part numbers
Ratings
Modules
BVITM6-S-HELVAR 4 output starter module
BVITM6-S2-HELVAR 2 output starter module
BVITM6-E-HELVAR 4 output extender module
Connectors
BVITM6-LPR 6 pole luminaire plug red
BVITM6-LPW 6 pole luminaire plug white
Voltage 230VAC +/- 10%
Frequency 50Hz
Terminal Capacity 4mm in wiring compartment
Temperature 0C to 35C
Power Rating system 16A. Rating of each output 10A
Compliance BS5733:2010
?
Helvar Ltd,
Hawley Mill, Hawley Road, Dartford. DA2 7SY. UK
www.helvar.com
+44 (0) 1322 617200
Warning: For lighting purposes with suitable circuit protection. For fixed wiring only.
Important: This device should be installed by a qualified electrician in accordance with
the latest edition of the IEE wiring regulations
UK Patent no. GB2463063
EU Patent pending
EU Registered design no. 001587544-0001, 001587544-0002
Helvar | Data subject to change without notice www.helvar.com 7
Page intentionally blank
Helvar | Modular LCM Installation Guide www.helvar.com 8
Page intentionally blank
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

HELVAR LCM Modular Lighting Control Module Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI