CHAPPEE initia MASTER 2.24 CF Installers And Users Instructions

Type
Installers And Users Instructions

This manual is also suitable for

Επίτις λέητας αερίυ υψηλής απδσης
δηγίες ρήσης για τ ρήστη και τν εγκαταστάτη
High efficiency wall-mounted gas-fired boilers
Installer’s and User’s Instructions
Chaudière murale à gaz à haut rendement
Notice d’emploi destinée à l’utilisateur et à l’installateur
MASTER 2.24 FF
MASTER 2.24 CF
Caldera mural de gas de alto rendimiento
Caldeira mural a gás de alto rendimento
Manual de uso destinado al usuario y al instalador
Manual para o uso destinado ao utente e ao instalador
GB
40
CN
GR
FR
SP
PT
Contents
Instructions pertaining to the user
Instructions prior to installation 41
Instructions prior to commissioning 41
Commissioning of the boiler 41
Room temperature adjustment 42
DHW temperature adjustment 42
Filling the boiler 42
Turning off the boiler 42
Prolonged standstill of the system. Frost protection
(central heating system) 42
Gas change 42
Safety Device Indicators-Activation 42
Servicing instructions 43
Instructions pertaining to the installer
General information 44
Instructions prior to installation 44
The template to x the boiler on the wall 44
Boiler size 45
Installation of ue and air duct 45
Connecting the mains supply 49
Fitting a room thermostat 49
Connecting a programming clock 49
Gas change modalities 50
Control and operation devices 51
Electronic board calibration 52
Positioning of the ignition and ame sensing electrode 52
Check of combustion parameters 52
Output / pump head performances 52
Boiler schematic 53-54
Illustrated wiring diagram 55-56
Technical data 57
Dear Customer,
We are sure your new boiler will comply with all your requirements.
Purchasing one of the CHAPPEE products satises your expectations: good functioning,
simplicity and ease of use.
Do not dispose of this booklet without reading it: you can nd here some very useful
information, which will help you to run your boiler correctly and efciently.
Do not leave any parts of the packaging (plastic bags, polystyrene, etc.) within children’s
reach as they are a potential source of danger.
CHAPPEE boilers bear the CE mark in compliance with the basic requirements
as laid down in the following Directives:
- Gas Directive 90/396/CEE
- Performance Directive 92/42/CEE
- Electromagnetic Compatibility Directive 89/336/CEE
- Low Voltage Directive 73/23/CEE
41
GB
CN
GR
FR
SP
PT
Instructions prior to installation
This boiler is designed to heat water at a lower than boiling temperature at atmospheric
pressure. The boiler must be connected to a central heating system and to a domestic
hot water supply system in compliance with its performances and output power.
Have the boiler installed by a Qualied Service Engineer and ensure the following ope-
rations are accomplished:
a) accurate purging of the whole pipework in order to remove any deposits.
b) careful checking that the boiler is t for operation with the type of gas available. For
more details see the notice on the packaging and the label on the appliance itself.
c) careful checking that the ue terminal draft is appropriate; that the terminal is not
obstructed and that no other appliance exhaust gases are expelled through the same
ue duct, unless the ue is especially designed to collect the exhaust gas coming from
more than one appliance, in conformity with the laws and regulations in force.
d)
careful checking that, in case the ue has been connected to pre-existing ue ducts,
thorough cleaning has been carried out in that residual combustion products may
come off during operation of the boiler and obstruct the ue duct.
Instructions prior to commissioning
Initial lighting of the boiler must be carried out by a licensed technician. Ensure the
following operations are carried out:
a) compliance of boiler parameters with (electricity, water, gas) supply systems settin-
gs.
b) compliance of installation with the laws and regulations in force.
c) appropriate connection to the power supply and grounding of the appliance.
Failure to observe the above will render the guarantee null and void.
Prior to commissioning remove the protective plastic coating from the unit. Do not use
any tools or abrasive detergents as you may spoil the painted surfaces.
Commissioning
of the boiler
To correctly light the burner proceed as follows:
1) provide power supply to the boiler;
2) open the gas cock;
3) turn the selector switch (1) to set the boiler on summertime (
) or wintertime (
) operation;
4) turn the central heating (12) and domestic hot water (13) adjusting controls in order
to light the main burner.
To increase temperature values turn the control clockwise and anticlockwise to
decrease it.
When on summertime operation (
) the main burner and the pump will start running
only when there is a call for hot water.
Instructions pertaining to the user
figure 1
020521_0700
Warning: During initial lighting, until the air contained in the gas pipes is not released,
the burner may fail to light immediately and that may cause a ‘blockage’ of the boiler.
Under such circumstances we recommend you repeat the ignition procedure until gas is
delivered to the burner, and briey set knob (1) to (
) (also see gure 4).
figure 2
Reset Winter OFF Summer
Summer / Winter / Reset selector positions
0503_1109 / CG_1659
GB
42
CN
GR
FR
SP
PT
Room temperature adjustment
The system must be equipped with a room thermostat (see the relevant regulations) to
control the temperature in the rooms.
In case there is no room thermostat, during initial lighting, it will be possible to control
the room temperature by turning control (12).
To increase temperature values turn the control clockwise and anticlockwise to decrease
it. Electronic modulation of the ame will enable the boiler to reach the set temperature
by adapting the gas supply to the burner to the actual heat exchange demand.
DHW temperature
adjustment
The gas valve is provided with an electronic ame-modulating function, which operates
depending on the DHW temperature adjusting control (13) settings and on the quantity
of water drawn from the taps.
This electronic device allows to keep the water coming out of the boiler at a constant
temperature also when small quantities of water are drawn.
To increase temperature values turn the control clockwise and anticlockwise to de-
crease it.
Filling the boiler
Important: Regularly check that the pressure displayed by the pressure gauge (14) is
0.7 to 1.5 bar, with boiler not operating. In case of overpressure, open the boiler drain
valve (Figure 3b).
In case the pressure is lower open the boiler lling tap (Figure 3a).
We recommend you open the tap very slowly in order to let off the air.
During this operation, the Summer/Winter selector (ref. 1, gure 4) must be in the OFF
position (0)
In case pressure drops occur frequently have the boiler checked by a Qualied Service
Engineer.
Figure 3a
Figure 3b
The boiler is supplied with a hydraulic differential pressure sensor, which blocks the boiler
in case water is lacking or the pump is blocked.
Turning off the boiler
The electric supply to the boiler must be removed in order to switch it off. When the
selector (1) is in position (0) the boiler stays off, but the voltage remains present in the
electric circuits of the apparatus.
Prolonged standstill of the system
Frost protection
(central heating system)
We recommend you avoid draining the whole system as water replacements engen-
der purposeless and harmful limestone deposits inside the boiler and on the heating
elements.
In case the boiler is not operated during wintertime and is therefore exposed to danger of
frost we suggest you add some specic-purpose anti-freeze to the water contained in the
system (e.g.: propylene glycole coupled with corrosion and scaling inhibitors).
The electronic management of boilers includes a ‘frost protection’ function in the central
heating system which operates the burner to reach a heating ow temperature of 30° C
when the system heating ow temperature drops below 5°C.
The frost protection function is enabled if:
* electrical supply to the boiler is on;
* the gas service cock is open;
* the system pressure is as required;
* the boiler is not blocked.
Gas change
These boilers produced for natural gas can be converted to work with LPG.
Any gas change must be effected by a Qualied Service Engineer.
Safety device indicators - activation
1 Summer-Winter-Reset selector
2 Gas block indicator
3 Overheat thermostat has switched on
4 Indication of lack of draught
or tripping of the flue gas
thermostat
5 Lack of water
6
DHW sensor anomaly indicator
7 Central heating sensor anomaly indicator
8 Voltage presence indicator
9 DHW production mode indicator
10 Central heating mode indicator
11 Flame presence indicator
The signals 2÷7 display the temperature reached either by the heating system or the
domestic hot water depending whether a heating or domestic hot water temperature
request is in operation.
In the case of an anomaly, the type of anomaly is displayed through a FLASHING
signal.
With regard to the warning (4), the boiler control panel may show the symbol
for
forced air-ow airtight chamber models, or the symbol
for natural draught models
(without fan).
Figure 4
020521_0500
0303_28060303_2807
Filling tap
Drain point
14
14
43
GB
CN
GR
FR
SP
PT
If safety device activation is repeated contact the authorised Technical Assistance
Services.
Servicing instructions
To maintain efcient and safe operation of your boiler have it checked by a Qualied
Service Engineer at the end of every operating period
.
Careful servicing will ensure economical operation of the system.
Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily
ammable cleaners (i.e.: gasoline, alcohol, and so on). Always isolate the electrical supply
to the appliance before cleaning it (see section Turning off the boiler).
Flashing
LED
anomaly
signals
Description
Solution
Call the authorized Technical Assistance
Service. Momentarily move the selector
1 to position
Call the authorized Technical Assi-
stance Service
Call the authorized Technical Assi-
stance Service
Turn selector switch 1 to the position
for a moment
See system-lling chapter on page
Momentarily move the selector 1 to
position
Momentarily move the selector 1 to
position
Lime scale on the domestic hot
water circuit
Heating probe broken
Domestic hot water probe bro-
Lack of water in the heating
circuit
Flue gas thermostat tripped
(2.24 CF)
Safety thermostat intervention
Gas blockage
Call the authorized Technical Assi-
stance Service
Lack of draught (2.24 FF)
GB
44
CN
GR
FR
SP
PT
Instructions pertaining to the installer
General information
Warning: When the selector switch
(1)
is set on Wintertime operation
( )
it may be
necessary to wait some minutes at each intervention of the central heating temperature
adjusting control
(5).
To relight the main burner immediately place the selector switch
(1)
on
(0)
and then again on
( ).
No waiting is needed when the boiler is in the DHW mode
on models with this option.
The following remarks and instructions are addressed to Service Engineers to help them
carry out a faultless installation. Instructions regarding lighting and operation of the boiler
are contained in the ‘Instructions pertaining to the user’ section.
Note that installation, maintenance and operation of the domestic gas appliances must be
performed exclusively by qualied personnel in compliance with current standards.
Please note the following:
*
This boiler can be connected to any type of double- or single feeding pipe convector
plates, radiators, thermoconvectors. Design the system sections as usual though
taking into account the available output / pump head performances, as shown on
page 50.
* Do not leave any packaging components (plastic bags, polystyrene, etc.) within
children’s reach as they are a potential source of danger.
*
Initial lighting of the boiler must be effected by a Qualied Service Engineer.
Failure to observe the above will render the guarantee null and void.
Instructions prior to installation
This boiler is designed to heat water at a lower than boiling temperature at atmospheric
pressure. The boiler must be connected to a central heating system and, on models
withis option, to a domestic hot water supply system in compliance with its performances
and output power.
Before connecting the boiler have the following operations effected:
a)
careful checking that the boiler is t for operation with the type of gas available. For
more details see the notice on the packaging and the label on the appliance itself.
b) careful checking that the ue terminal draft is appropriate; that the terminal is not
obstructed and that no other appliance exhaust gases are expelled through the same
ue duct, unless the ue is especially designed to collect the exhaust gase coming
from more than one appliance, in conformity with the laws and regulations in force
c)
careful checking that, in case the ue has been connected to pre-existing ue ducts,
thorough cleaning has been carried out in that residual combustion products may
come off during operation of the boiler and obstruct the ue duct.
To ensure correct operation of the appliance and avoid invalidating the guarantee, observe
the following precautions
1.
Hot water circuit
if the water hardness is greater than 20 °F (1 °F = 10 mg calcium carbonate per litre of
water) install a polyphosphate or comparable treatment system responding to current
regulations
2.
Heating circuit
2.1. new system
Before proceeding with installation of the boiler, the system must be cleaned
and ushed out thoroughly to eliminate residual thread-cutting swarf, solder and
solvents if any, using suitable proprietary products
2.2.
existing system:
Before proceeding with installation of the boiler, the system must be cleaned
and ushed out to remove sludge and contaminants, using suitable proprietary
products
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-
acid and non-alkaline (e.g. SENTINEL X400 and X100), proceeding strictly in accordance
with the maker’s directions
Remember that the presence of foreign matter in the heating system can adversely affect
the operation of the boiler (e.g. overheating and noisy operation of the heat exchanger)
The template to fix the boiler on the wall
Decide upon the boiler location, then tape the template on the wall.
Connect the pipework to the gas and water inlets prearranged on the template lower
bar.
We suggest you t two G3/4 stop cocks (available on demand) on the central heating
system ow and return pipework; the cocks will allow to carry out important operations
on the system without draining it completely.
If you are either installing the boiler on a pre-existent system or substituting it, we
suggest you also t settling tanks on the system return pipework and under the boiler
to collect the deposits and scaling which may remain and be circulated in the system
after the purge.
When the boiler is xed on the template connect the ue and air ducts (ttings supplied
by the manufacturer) according to the instructions given in the following sections.
When installing the 2.24 CF model boiler with natural draught, make the connection to the
ue using a metal pipe which will provide resistance over time to the normal mechanical
stresses, heat and the effects of the combustion products and any condensation they
form.
Figure 5
MR: G3/4 heating flow
US: G1/2 domestic hot water outlet
GAS: G3/4 gas inlet to the boiler
ES: G1/2 cold water inlet
RR: G3/4 heating return
0303_2808
0309_1101
BOILER CONNECTION POINTS
BOILER HEIGHT 730
45
GB
CN
GR
FR
SP
PT
Flue duct terminal
Coaxial
V
ertical two-pipe
Horizontal two-pipe
Outer
duct
diameter
100
mm
80 mm
80 mm
Max. length
of flue duct
5
m
15 m
30 m
Each 90° bend
reduces the duct
max. length by
1 m
0,5 m
0,5 m
Each 45° bend
reduces the duct
max. length by
0,5 m
0,25 m
0,25 m
Flue
terminal
diameter
100
mm
133 mm
-
Figure 6
Boiler size
2.24 CF 2.24 FF
Installation of flue and air ducts
(2.24 CF)
We guarantee ease and exibility of installation for a gas-red forced draft boiler thanks
to the ttings and xtures supplied (described below).
The boiler is especially designed for connection to an exhaust ue / air ducting, with
either coaxial, vertical or horizontal terminal. By means of a splitting kit a two-pipe system
may also be installed.
Exclusively
install fittings supplied by the manufacturer.
Figure 7
020221_1200
securing clamp
seal
r
estrictor (*)
Figure 8
...coaxial flue - air duct (concentric)
This type of duct allows to disengage exhaust gases and to draw combustion air both
outside the building and in case a LAS ue is tted.
The 90° coaxial bend allows to connect the boiler to a ue-air duct in any direction as it
can rotate by 360°. It can moreover be used as a supplementary bend and be coupled
with a coaxial duct or a 45° bend.
(*) The restrictor must be removed in case the ue duct length exceeds 1 m.
If the ue outlet is placed outside, the ue-air ducting must protrude at least 18mm out
of the wall to allow alluminium weathering tile to be tted and sealed to avoid water
leakages.
Ensure a minimum downward slope of 1 cm towards the outside per each metre of
duct length.
A 90° bend reduces the total duct length by 1 metre.
A 45° bend reduces the total duct length by 0.5 metre.
0609_0705 / CG_1792
0503_0904 / CG_1636
0503_0905 / CG_1638
GB
46
CN
GR
FR
SP
PT
Horizontal flue terminal installation options
LAS flue duct installation options
L max = 5 m
L max = 5 m
L max = 4 m
L max = 4 m
L max = 5 m
Vertical flue terminal installation options
This type of installation can be carried out both on a at or pitched roof by tting a
terminal, an appropriate weathering tile and sleeve, (supplementary ttings supplied
on demand).
L max = 4 m
L max = 4 m L max = 3 mL max = 2 m
For detailed instructions concerning the installation of ttings refer to the technical data
accompanying the ttings.
0503_0906 / CG_1639
0503_0907 / CG_1640
0503_0908 / CG_1641
47
GB
CN
GR
FR
SP
PT
… separated flue-air ducting
This type of ducting allows to disengage exhaust ue gases both outside the building
and into single ue ducts.
Comburant air may be drawn in at a different site from where the ue terminal is lo-
cated.
The splitting kit consists of a ue duct adaptor (100/80) and of an air duct adaptor.
For the air duct adaptor t the screws and seals previously removed from the cap.
The restrictor must be removed in case you install separated ue and air duct termi-
nals.
The 90° bend allows to connect the boiler to ue-air ducting regardless of direction as it
can be rotated by 360°. It can moreover be used as a supplementary bend to be coupled
with the duct or with a 45° bend.
020130_0700
A 90° bend reduces the total duct length by 0.5 metre.
A 45° bend reduces the total duct length by 0.25 metre.
0609_2101
GB
48
CN
GR
FR
SP
PT
(L1 + L2) max = 30 m
L max = 10 m
NB: For C52 types, terminals for combustion air suction and combustion product extrac-
tion must never be tted on opposite walls of the building.
L max = 10 m
L max = 12 m
Separated vertical flue terminals installation options
Important: if tting a single exhaust ue duct, ensure it is adequately insulated (e.g.: with
glass wool) wherever the duct passes through building walls.
For detailed instructions concerning the installation of ttings refer to the technical data
accompanying the ttings.
Split
flue air control adjustment
The adjustment of this control is required to optimise performance and combustion param-
eters. The air suction coupling can be rotated to adjust excess air according to the total
length of the ue and intake ducts for the combustion air.
Turn this control clockwise to increase excess combustion air and anticlockwise to
decrease it.
The maximum length of the suction duct must be 10 metres.
If the ue duct exceeds 6 m, the condensate collection kit (supplied as an accessory)
must be tted close to the boiler.
To improve optimisation a combustion product analyser can be used to measure the CO
2
contents of the ue at maximum heat output, gradually adjusting air to obtain the CO
2
reading in the table below, if the analysis shows a lower value.
To properly install this device, also refer to the technical data accompanying the tting.
Separated horizontal flue terminals installation options
IMPORTANT: Ensure a minimum downward slope of 1 cm toward the outside per each
metre of duct length.
In the event of installation of the condensate collection kit, the angle of the drain duct
must be directed towards the boiler.
0609_1102
0503_0911 / CG_1644
0503_2201 / CG_1643
49
GB
CN
GR
FR
SP
PT
020130_0800
Figure 9
CO2%
(L1+L2)
MAX CONTROL POSITION
G.20 G.30 G.31
0÷4 1
4÷18 2 6,7
7,3 7,3
18÷30 3
indice
opening
Connecting the mains supply
Electrical safety of the appliance is only guaranteed by correct grounding, in compliance
with the applicable laws and regulations.
Connect the boiler to a 220-230V monophase + ground power supply by means of the
three-pin cable supplied with it and make sure you connect polarities correctly.
Use
a double-pole switch with a contact separation of at least 3mm in both po-
les.
In case you replace the power supply cable t a HAR H05 VV-F’ 3x0.75mm
2
cable with
an 8mm diameter max.
…access to the power supply terminal block
isolate the electrical supply to the boiler by the double-pole switch;
unscrew the two screws securing the control board to the boiler;
rotate the control board;
unscrew the lid and gain access to the wiring (Figure 10).
A 2A fast-blowing fuse is incorporated in the power supply terminal block (to check or
replace the fuse, pull out the black fuse carrier).
(L) = Live brown
(N) = Neutral blue
(
) = Ground yellow/green
(1) (2) = room thermostat terminal
Figure 10
020130_0900
terminal board
Figure 11
9402250715
Fitting a room thermostat
gain access to the power supply terminal block (Figure 11) as described in the previous
section;
remove the jumper placed on terminals (1) and (2);
insert the duplex cable through the core hitch and connect it to the two terminals.
Connecting a programming clock
* connect the programming clock motor to the main PCB CN1 connector (terminals
1 and 2);
* connect the programming clock switch to the CN1 connector terminals (3 and 4) and
remove the jumper.
In case you are tting a battery-operated programming clock do not connect the CN1
connector terminals (1 and 2).
GB
50
CN
GR
FR
SP
PT
Figure 13
0207_0405
Honeywell gas valve
SIT gas valve
aa
b
b
Pc
Gas change modalities
A Qualied Service Engineer may adapt this boiler to operate with natural gas (G. 20) or
with liquid gas (G. 30, G. 31).
The procedure for calibrating the pressure regulator may vary according to the type of
gas valve tted (HONE
YWELL or SIT; see gure 12).
Carry out the following operations in the given sequence:
A) substitute the main burner injectors;
B)
change the modulator voltage;
C) proceed with a new max. and min. setting of the pressure adjusting device.
A) Substitute the main burner injectors
carefully pull the main burner off its seat;
substitute the main burner injectors and make sure you tighten them fast to avoid
leakage. The nozzle diameters are specied in table 2.
B)
Change the modulator voltage
remove the 2 screws securing the control board cover and hinge it upward;
set the jumper or the switch, according to the type of gas used, as described in the
chapter on page 52.
C) Pressure adjusting device setting
connect the positive pressure test point of a differential (possibly water-operated)
manometer to the gas valve pressure test point (Pb) (Figure 12); connect, for sealed
chamber models only, the negative pressure test point of the manometer to a “T”
tting in order to join the boiler adjusting outlet, the gas valve adjusting outlet (Pc)
and the manometer. (The same measurement can be carried out by connecting the
manometer to the pressure test point (Pb) after removing the sealed chamber front
panel);
If you measure the pressure of burners by different means you may obtain an altered
result in that the low pressure created in the sealed chamber by the fan would not
be taken into account.
C1) Adjustment to rated output
open the gas tap and rotate knob (1) to set the boiler to the Winter setting ( );
open a hot water tap to reach a minimum 10 l/minute ow rate or ensure that maximum
heating requirements are set;
remove the modulator cover;
adjust the tube brass screw (A) Fig. 13 to obtain the pressure settings shown at table
1 on page 51;
check that boiler feeding dynamic pressure, as measured at the inlet gas valve
pressure test point (Pa) (Figure 12) is correct (30 mbar for G.30, 37 mbar for G.31,
20 mbar for natural gas);
C2) Adjustment to reduced heat output
detach the modulator feeding cable and unscrew the (B) Fig. 13 screw to reach the
pressure setting corresponding to reduced heat output (see table 1 on page 51);
connect the cable again;
t the modulator cover and seal.
C3) Final checks
apply the additional dataplate, specifying the type of gas and settings applied.
SIT Gas Valve
mod. SIGMA 845
Figure 12
Honeywell Gas Valve
mod. VK 4105 M
9912221500
0207_0406
Pc
Pb
Pa
51
GB
CN
GR
FR
SP
PT
Table of burner pressures - heat output
2.24 FF 2.24 CF
mbar mbar mbar kW kcal/h
G20 G30 G31
2,0 5,1 6,0 9,3 8.000 Reduced heat output
2,3 5,7 6,9 10,5 9.000
2,7 6,6 8,5 11,6 10.000
3,2 8,0 10,3 12,8 11.000
3,8 9,6 12,2 14,0 12.000
4,5 11,2 14,4 15,1 13.000
5,2 13,0 16,7 16,3 14.000
5,9 15,0 19,1 17,4 15.000
6,8 17,0 21,8 18,6 16.000
7,6 19,2 24,6 19,8 17.000
8,6 21,5 27,6 20,9 18.000
9,5 24,0 30,7 22,1 19.000
10,6 26,6 34,0 23,3 20.000
11,2 28,2 36,1 24,0 20.600 Rated heat output
1 mbar = 10,197 mmH
2
0
Table 1
Consumption table - burner injectors
2.24 FF 2.24 CF
Gas used
G20 G30 G31 G20 G30 G31
main injector diameter
(mm) 1,28 0,74 0,74 1,18 0,74 0,74
no. of injectors
13 13 13 13 13 13
Table 2
2.24 FF - 2.24 CF
Consumption 15 °C - 1013 mbar G20 G30 G31
Rated heat output 2,78 m
3
/h 2,07 kg/h 2,04 kg/h
Reduced heat output
1,12 m
3
/h 0,84 kg/h 0,82 kg/h
p.c.i. 34,02 MJ/m
3
45,6 MJ/kg 46,3 MJ/kg
Table 3
mbar mbar mbar kW kcal/h
G20 G30 G31
2,3 4,8 6,3 9,3 8.000
2,6 5,4 6,7 10,5 9.000
3,1 6,5 8,3 11,6 10.000
3,7 7,8 10,1 12,8 11.000
4,4 9,3 12,0 14,0 12.000
5,2 11,0 14,1 15,1 13.000
6,1 12,7 16,3 16,3 14.000
6,9 14,6 18,7 17,4 15.000
7,9 16,6 21,3 18,6 16.000
8,9 18,7 24,0 19,8 17.000
10,0 21,0 27,0 20,9 18.000
11,1 23,4 30,0 22,1 19.000
12,3 25,9 33,3 23,3 20.000
13,1 27,5 35,3 24,0 20.600
1 mbar = 10,197 mmH
2
0
Table 1
Control and operation devices
The boiler has been designed in full compliance with European reference standards and
in particular is equipped with the following:
Central heating temperature adjustment potentiometer
This potentiometer sets the central heating ow max. temperature. Its temperature
range goes from 30 °C min. to 80 °C max.
To increase the temperature turn knob (12) clockwise and anticlockwise to decrease
it.
Domestic hot water temperature adjusting potentiometer
This potentiometer sets the domestic hot water max. temperature. Its temperature
range goes from 35 °C min. to 55 °C max according to the water inlet ow rate.
To increase the temperature turn knob (13) clockwise and anticlockwise to decrease
it.
Air pressure switch for forced draft models (2.24 FF)
This switch allows the main burner to switch on provided the exhaust ue duct
efciency is perfect.
In the event of one of the following faults:
the ue terminal is obstructed
the venturi is obstructed
the fan is blocked
the connection between the venturi and the air pressure switch is not active
the boiler will stay on stand-by and the light (4) will ash.
Overheat thermostat (2.24 CF)
Thanks to a sensor placed on the heating ow, this thermostat interrupts the gas ow
to the main burner in case the water contained in the primary system has overheated.
Under such conditions the boiler is blocked and relighting (briey rotating selector
(1) to position (
) will only be possible after the cause of the anomaly has been
removed.
It is forbidden to disenable this safety device
Flame ionization detector
The ame sensing electrode, placed on the right of the burner, guarantees safety of
operation in case of gas failure or incomplete interlighting of the main burner. Under
such conditions the boiler is blocked. Rotate selector (1) briey to position (
) to
restore normal operating conditions.
Hydraulic pressure sensor
This device enables the main burner only to be switched on if the system pressure
is over 0.5 bars.
Supplementary running of the pump
The electronically-controlled supplementary running of the pump lasts 3 minutes,
when the boiler is in the central heating mode, after the burner has switched off due
to a room thermostat or intervention.
Frost protection device (central heating system)
Boilers electronic management includes a “frost protection” function in the central
heating system which operates the burner to reach a heating ow temperature of
30°C when the system heating ow temperature drops below 5 °C.
This
function is enabled when the electrical supply to the boiler is on, the gas supply
is on and the system pressure is as required.
Pump-blocking prevention
In case there is no call for heat either from the central heating system for 24 hours
on end the pump will automatically switch on for 10 seconds.
This function is enabled if the electrical supply to the boiler is on.
Hydraulic safety valve (heating circuit)
This device is set to 3 bar and is used for the heating circuit.
The safety valve should be connected to a siphoned drain. Use as a means of draining
the heating circuit is strictly prohibited.
GB
52
CN
GR
FR
SP
PT
Positioning of the ignition and flame
sensing electrode
Figure 14
9912070100
Electronic board calibration
When the jumper or the switch is in the (g. 13a) position:
GPL operation of system with NATURAL gas
T-off 3-minute heating stand-by time
When the jumper or the switch is in the (g. 13b) position:
GPL
operation of system with LPG
T-off 10-seconds heating stand-by time
020521_0400020521_0300
Figure 13b
Figure 13a
NB Make sure that electrical power supply has been disconnected before making
settings.
Graph 1
0303_2403
Check of combustion parameters
The boiler has two connection points specically designed to allow technicians to
measure the combustion efciency after installation and ensure that the combustion
products do not constitute a health risk, as required by Italian Presidential Decree n.
412 of 26
th
August 1993.
One connection point is connected to the ue gas discharge circuit, and allows monitoring
of the quality of the combustion products and the combustion efciency.
The other is connected to the combustion air intake circuit, allowing checking of any
recycling of the combustion products in case of coaxial pipelines.
The following parameters can be measured at the connection point on the ue gas
circuit:
temperature of the combustion products;
oxygen (O2) or carbon dioxide (CO2) concentration;
carbon monoxide(CO) concentration.
The combustion air temperature must be measured at the connection point on the air
intake circuit, inserting the measurement probe to a depth of about 3 cm.
For natural draught boiler models, a hole must be made in the ue gas discharge pipe at
a distance from the boiler equal to twice the inside diameter of the pipe itself.
The following parameters can be measured through this hole:
temperature of the combustion products;
oxygen (O2) or carbon dioxide (CO2) concentration;
carbon monoxide (CO) concentration.
The combustion air temperature must be measured close to the point where the air
enters the boiler.
The hole, which must be made by the person in charge of operating the system when it
is commissioned, must be sealed in a way which ensures that the combustion product
discharge pipe is airtight during normal operation.
Output / pump head performances
This is a high static head pump t for installation on any type of single or double-pipe
heating systems. The air vent valve incorporated in the pump allows quick venting of
the heating system.
OUTPUT l/h
PUMP HEAD mH
2
O
53
GB
CN
GR
FR
SP
PT
Boiler schematic
heating domestic water gas domestic water heating
inlet outlet inlet return
Figure 15
2.24 FF
Key:
1 overheat thermostat
2 hydraulic pressure sensor
3 gas valve
4 gas train with injectors
5 ignition electrode
6 flue-water exchanger
7 DHW NTC sensor
8 flue adaptor
9 fan
10 negative pressure point
11
air pressure switch
12 positive pressure point
13 central heating NTC sensor
14 flame sensing electrode
15 main burner
16 expansion vessel
17 automatic air vent
18 pump and air separator
19 manometer
20 safety valve
21 automatic by-pass
22 DHW flow priority microswitch
23 boiler filling tap
24 boiler drain point
0605_0506
GB
54
CN
GR
FR
SP
PT
Boiler schematic
heating domestic water gas domestic water heating
inlet outlet inlet return
Figure 16
0208_2903
2.24 CF
Key:
1 boiler drain point
2 hydraulic pressure sensor
3 gas valve
4 gas train with injectors
5 ignition electrode
6 flue-water exchanger
7 DHW NTC sensor
8 flue gas hood
9 flue gas thermostat
10 central heating NTC sensor
11 flame sensing electrode
12 main burner
13 expansion vessel
14 automatic air vent
15 pump and air separator
16 manometer
17 safety valve
18 boiler filling tap
19 DHW flow priority microswitch
20 automatic by-pass
21 overheat thermostat
55
GB
CN
GR
FR
SP
PT
Illustrated wiring diagram
2.24 FF
0309_2301
CABLES COLOURS
C= light blue
M= brown
N= black
R
= red
G/V= yellow/green
B= white
Bl= blue
KE
Y
P1: Heating power regulation trimmer
P2: DHW potentiometer
P3: Central heating potentiometer
P4: S/W/OFF selector
JP1: MET/GPL gas change jumper
JP2: Heating in standby time 3’/10” jumper
FLAME SENSING
ELECTRODE
SAFETY THER-
MOSTAT
DHW NTC SEN-
SOR
DHW FLOW PRIORITY MICRO-
SWITCH
HYDRAULIC DIFFERENTIAL
PRESSURE MICROSWITCH
PUMP
AIR PRESSURE
SWITCH
IGNITION
ELECTRODE
CENTRAL HEATING
NTC SENSOR
FAN
ROOME THERMO-
STAT 230V
FEEDING POWER
GRID
FUSE
FEEDING TERMINAL BLOCK
GB
56
CN
GR
FR
SP
PT
Illustrated wiring diagram
2.24
CF
CABLES COLOURS
C= light blue
M= brown
N= black
R= red
G/V= yellow/green
B= white
Bl= blue
KEY
P1: Heating
power regulation trimmer
P2: DHW potentiometer
P3: Central heating potentiometer
P4: S/W/OFF selector
JP1: MET/GPL gas change jumper
JP2: Heating in standby time 3’/10” jumper
0309_2302
FLAME SENSING
ELECTRODE
SAFETY THERMO-
STAT
DHW NTC
SENSOR
DHW FLOW PRIORITY
MICROSWITCH
HYDRAULIC DIFFERENTIAL
PRESSURE MICROSWITCH
PUMP
FLUE GAS
THERMOSTAT
IGNITION ELECTRODE
CENTRAL HEATING
NTC SENSOR
ROOME THERMO-
STAT 230V
FEEDING POWER
GRID
FUS
E
FEEDING TERMINAL BLOCK
57
GB
CN
GR
FR
SP
PT
Technical data
2.24 Modell FF CF
Rated heat input kW 26,3 26,3
Reduced heat input kW 10,6 10,6
Rated heat output kW 24 24
kcal/h 20.600 20.600
Reduced heat output kW 9,3 9,3
kcal/h 8.000 8.000
Useful efciency according to 92/42/CEE directive
HH HH
Central heating system max. pressure bar 3 3
Expansion vessel capacity l 8 7
Expansion vessel pressure bar 0,5 0,5
DHW system max. pressure bar 8 8
DHW system min. dynamic pressure bar 0,2 0,2
DHW system min. output l/min 2,5 2,5
DHW production at ∆T=25 °C l/min 13,7 13,7
DHW production at ∆T=35 °C l/min 9,8 9,8
Specic output (*) l/min 11 11
Concentric ue duct diameter mm 60 -
Concentric air duct diameter mm 100 -
2-pipe ue duct diameter mm 80 -
2-pipe air duct diameter mm 80 -
Discharge pipe diameter mm - 120
Max. ue mass ow rate kg/s 0,020 0,021
Min. ue mass ow rate kg/s 0,017 0,018
Max. ue temperature °C 146 120
Min. ue temperature °C 106 86
Type of gas used G20 G20
G30-G31 G30-G31
Natural gas feeding pressure mbar 20 20
Butane gas feeding pressure mbar 28-30 28-30
Propane gas feeding pressure mbar 37 37
Power supply voltage V 230 230
Power supply frequency Hz 50 50
Rated power supply W 170 110
Net weight kg 33,5 29
Dimensions height mm 734 734
width mm 400 400
depth mm 317 317
Protection-limit against humidity and water leakages (**) IP X4D IP X4D
(*) according to EN 625
(**) according to EN 60529
58
CN
GB
Gr
Fr
SP
PT
Περιεµενα
δηγίες για τ ρήστη
δηγίες πριν απ την εγκατάσταση 59
δηγίες πριν απ τη θέση σε λειτυργία 59
Θέση τυ λέητα σε λειτυργία 59
Ρύθµιση θερµκρασίας δωµατίυ 60
Ρύθµιση θερµκρασία εστύ νερύ ικιακής ρήσης 60
Πλήρωση τυ λέητα 60
Σήσιµ τυ λέητα 60
Παρατεταµένη αρησία τυ συστήµατς Αντιπαγωτική πρστασία
(κύκλωµα θέρµανσης) 60
Αλλαγή αερίυ 60
Ενδείεις-Επέµαση συστηµάτων ασαλείας 60
δηγίες για τ σέρις 61
δηγίες για τν εγκαταστάτη
Γενικές πληρρίες 62
δηγίες πριν απ την εγκατάσταση 62
Σέδι για την εγκατάσταση τυ λέητα στν τί 62
∆ιαστάσεις λέητα 63
Εγκατάσταση αγωγών απαγωγής - αναρρησης 63
Ηλεκτρική σύνδεση 67
Σύνδεση θερµστάτη δωµατίυ 67
Σύνδεση ρλγιύ πργραµµατισµύ 67
Τρπς αλλαγής αερίυ 68
∆ιατάεις ελέγυ και ασαλείας 70
Ρυθµίσεις πυ πρέπει να εκτελεσθύν στην ηλεκτρνική πλακέτα 70
Τπθέτηση ηλεκτρδίυ ανάλεης και ανίνευσης λγας 70
Έλεγς παραµέτρων καύσης 71
Επιδσεις παρής εδυ / µανµετρικύ ύψυς στην πλάκα 71
Σηµατικ διάγραµµα λέητα 72-73
Εικνγραηµέν διάγραµµα συνδεσµλγίας 74-75
Τενικά αρακτηριστικά 76
Αγαπητέ Πελάτη,
είµαστε έαιι τι νές σας λέητας θα ικανπιήσει λες τις απαιτήσεις
σας.
Η αγρά ενς πρϊντς της CHAPPEE ικανπιεί τις πρσδκίες σας: καλή
λειτυργία, απλτητα και ευκλία στη ρήση.
Σας παρακαλύµε, να µη υλάετε αυτ τ υλλάδι ωρίς να τ διαάσετε:
περιέει ρήσιµες πληρρίες για τη σωστή και απδτική λειτυργία τυ
λέητά σας.
Τα υλικά της συσκευασίας (πλαστικές σακύλες, πλυστυρένι κλπ.) πρέπει να
υλάσσνται µακριά απ παιδιά, καθώς απτελύν πιθανή εστία κινδύνυ.
Η CHAPPEE δηλώνει τι τα εν λγω µντέλα έρυν σήµανση CE, σε
συµµρωση µε τις ασικές απαιτήσεις πυ διατυπώνυν ι ακλυθες
δηγίες:
- δηγία Αερίων 90/396/ΕΚ
- δηγία Απδσεων 92/42/ΕΚ
- δηγία Ηλεκτρµαγνητικής Συµαττητας 89/336/ΕΚ
- δηγία αµηλής Τάσης 73/23/ΕΚ
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51

CHAPPEE initia MASTER 2.24 CF Installers And Users Instructions

Type
Installers And Users Instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI