Siemens System 600 APOGEE Installation guide

Type
Installation guide

Siemens System 600 APOGEE is an open processor with Trane drivers that can connect the System 600 APOGEE to the Trane Tracer Summit BCU. It contains the main processor, memory, and communications circuitry. The APOGEE can be attached to the left mounting rail, the M-BUS rails, and the C-BUS slot of the MBC or RBC enclosure. It is FCC-approved for a maximum of four Controller Modules and/or Pre-APOGEE Open Processors, or a maximum of five APOGEE Open Processors.

Siemens System 600 APOGEE is an open processor with Trane drivers that can connect the System 600 APOGEE to the Trane Tracer Summit BCU. It contains the main processor, memory, and communications circuitry. The APOGEE can be attached to the left mounting rail, the M-BUS rails, and the C-BUS slot of the MBC or RBC enclosure. It is FCC-approved for a maximum of four Controller Modules and/or Pre-APOGEE Open Processors, or a maximum of five APOGEE Open Processors.

Installation Instructions
Document No. 565-939
Rev. 1, November, 1999
Open Processor with Trane Drivers
Siemens Building Technologies, Inc.
Page 1 of 4
PRODUCT DESCRIPTION
Each Open Processor (Figure 1) contains the main
processor, memory, and communications circuitry
for connecting the System 600 APOGEE to the
Trane Tracer Summit BCU.
Figure 1. Open Processor: Front View.
The Open Processor attaches to the left mounting
rail, the M-BUS rails, and the C-BUS slot of the MBC
or RBC enclosure.
N
NN
NO
OO
OT
TT
TE
EE
E:
::
:
An MBC or RBC enclosure is FCC-
approved for a maximum of four Controller
Modules and/or Pre-APOGEE Open
Processors, or a maximum of five
APOGEE Open Processors.
PRODUCT NUMBERS
565-363 Open Processor with Trane Driver
(APOGEE)
565-302 Open Processor with Trane Driver
(Pre-APOGEE)
538-670 Trunk Interface II, 115V
538-675 Trunk Interface II, 230V
545-710 Battery Replacement Kit. Refer to
Installation Instructions 545-408.
545-712 MMI Extension Cable. Refer to
Installation Instructions 545-407.
538-583 Grounding Wire.
EXPECTED INSTALLATION TIMES
7 minutes.
REQUIRED TOOLS AND MATERIALS
Flat-blade screwdriver (1/8" blade width)
Wire strippers
One 115V or 230V (depending on device)
receptacle to power the Trunk Interface II
Cabling and connectors (Figure 6)
CA
CACA
CAU
UU
UT
TT
TI
II
IO
OO
ON
NN
N:
::
:
Always wear an electro-static
discharge wrist strip and discharge
accumulated static before touching
field panel components.
PREREQUISITES
MBC or RBC enclosure mounted with at
least one open slot on the C-BUS and AC
power connected.
Backups made of the current database for
all Open Processors and other Controller
Modules in the enclosure.
Both systems installed and checked out by
certified representatives of the companies
that installed each system. These checkouts
must confirm that each system is operating
and ready to communicate with the other
system.
Building level network (BLN) cable, if used,
fed into the MBC or RBC enclosure. If
necessary, splice in a connector for the
Open Processor. (Connecting this cable is
done later during start-up.)
INSTRUCTIONS
Preparing to Install the Open Processor
1. Prepare the MBC or RBC enclosure for
shutdown by performing the following steps:
CA
CACA
CAU
UU
UT
TT
TI
II
IO
OO
ON
NN
N:
::
:
Do not install or remove an Open
Processor while the MBC or RBC
enclosure is powered up. Doing so may
damage the Open Processor or other
modules in the enclosure.
Document No. 565-939
Installation Instructions
Rev. 1, November, 1999
Page 2 of 4
Siemens Building Technologies, Inc.
a. Notify the appropriate building personnel
that you will be turning OFF power to the
enclosure, and tell them what equipment
will be affected.
b. Follow all shutdown procedures necessary
to prevent damage to any equipment or
harm to any personnel.
N
NN
NO
OO
OT
TT
TE
EE
E:
::
:
If the MBC or RBC enclosure already
houses one or more Controller
Modules and/or Open Processors,
make sure their batteries are good. If
any battery status LED is red when
the power is ON, replace the battery
before proceeding.
2. Turn OFF power to the MBC or RBC enclosure.
3. If you are installing the Open Processor in an
empty MBC or RBC enclosure, remove the
temporary cover (Figure 2) that is wrapped
around the mounting rails, M-BUS rails, and the
C-BUS. Save one connector for FLN 1 and one
for the BLN if it is used.
Figure 2. Temporary Cover.
4. Remove the C-BUS cover from the lowest
available slot and discard it.
5. Remove any M-BUS protective tape from the
M-BUS.
6. Remove the warning label from the Open
Processor to expose the C-BUS card (Figure 3).
Figure 3. Open Processor: Rear View.
Installing the Open Processor
N
NN
NO
OO
OT
TT
TE
EE
E:
::
:
The goal of this procedure is to place the
Open Processor’s C-BUS and M-BUS
connectors into their respective slots and
secure the module.
CA
CACA
CAU
UU
UT
TT
TI
II
IO
OO
ON
NN
N:
::
:
Improperly aligning and/or installing
the Open Processor may damage it.
1. On the right-hand side of the Open Processor,
locate the lower mounting guide (Figure 4).
2. Locate the round mounting rail on the far right
edge of the right-hand M-BUS rail (Figure 4).
3. Align the module’s lower mounting guide with
the lowest available slot next to the round
mounting rail (Figure 4).
4. Insert the lower and upper mounting guides into
the mounting slot and hook them into place
(Figure 4).
5. Push the left side of the Open Processor
forward so that its C-BUS card edge and
M-BUS connector mate with the C-BUS
connector and M-BUS rails (Figure 5). When
the Open Processor is seated properly, you will
hear a “click.”
6. If the Open Processor needs to be repositioned:
a. Locate the module’s latch (on the module’s
far left end). Release the latch by pulling it
toward you.
b. Swing the left end of the Open Processor
toward you to remove the module from its
C-BUS slot (Figure 5).
c. Pull on the Open Processor to remove its
mounting guides from the round mounting
rail (Figure 4).
d. Repeat Steps 2 through 5 above.
1. Turn ON power to the MBC or RBC enclosure.
2. If you changed the operating state of any
equipment, restore it to its previous state.
N
NN
NO
OO
OT
TT
TE
EE
E:
::
:
If you use the BLN that is mentioned in the
Prerequisites
section, do NOT plug the
connector attached to it into the Open
Processor’s BLN port. This will be done
during start-up.
The Open Processor installation is now complete.
Document No. 565-939
Installation Instructions
Rev. 1, November, 1999
Siemens Building Technologies, Inc.
Page 3 of 4
Figure 4. Attaching the Open Processor to the Mounting Guides.
Figure 5. Latching the Open Processor.
Document No. 565-939
Installation Instructions
Rev. 1, November 1999
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and
models as design improvements are introduced. © 1999 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
Landis & Staefa Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
Document No. 565-939.
Printed in the U.S.A.
Page 4 of 4
Connecting the Open Processor to the
Trane Tracer Summit BCU
Follow these steps to connect the Open Processor
to the Trane Tracer Summit BCU:
1. Turn OFF power to the MBC or RBC enclosure.
2. Following guidelines for P2 Trunk use in
installation instructions (P/N 538-663), install
the Trunk Interface II.
3. Make cable per diagram in Figure 6.
4. Connect the Open Processor to the Trane
Tracer Summit BCU using the guidelines in
Figure 6.
5. Plug in power supply for Trunk Interface II.
6. Turn ON power to the MBC or RBC enclosure.
FLN 1
POWER
BLN
OPEN PROCESSOR
S
-
+
S
-
+
RS-485 TRUNK CABLE
(MAX 4000' / 1219.2 m;
STANDARD 24 AWG LOW CAPACITANCE)
GROUND WIRE TO EARTH
(P/N 538-583)
POWER PACK
RS-232 CABLE
(MAX 50' / 15.24 m)
TRUNK INTERFACE II
GW0104R1
IF OPEN
PROCESSOR IS
LESS THAN
50 CABLE FEET
(15.24 m)
FROM BCU
PANEL,
PLACE TRUNK
INTERFACE II
IN MBC
ENCLOSURE
2
3
7
RS-232 PORT
(25-PIN FEMALE)
RS-232 PORT
(25-PIN MALE)*
TRANE
TRACER SUMMIT
BCU PANEL
TAPE BACK
SHIELD
*STANDARD
RS-232
25-PIN
PC PORT
MALE.
47832
Figure 6. Connecting the Open Processor to the
Trane System.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Siemens System 600 APOGEE Installation guide

Type
Installation guide

Siemens System 600 APOGEE is an open processor with Trane drivers that can connect the System 600 APOGEE to the Trane Tracer Summit BCU. It contains the main processor, memory, and communications circuitry. The APOGEE can be attached to the left mounting rail, the M-BUS rails, and the C-BUS slot of the MBC or RBC enclosure. It is FCC-approved for a maximum of four Controller Modules and/or Pre-APOGEE Open Processors, or a maximum of five APOGEE Open Processors.