The EMC CX3-20, a 1U storage processor enclosure, offers exceptional storage capacity and robust data protection for small and medium-sized businesses. Featuring a compact and versatile design, it's ideal for organizations seeking reliable and scalable storage solutions. With its advanced hardware architecture, the CX3-20 delivers exceptional performance, enabling you to manage and access your data efficiently.

The EMC CX3-20, a 1U storage processor enclosure, offers exceptional storage capacity and robust data protection for small and medium-sized businesses. Featuring a compact and versatile design, it's ideal for organizations seeking reliable and scalable storage solutions. With its advanced hardware architecture, the CX3-20 delivers exceptional performance, enabling you to manage and access your data efficiently.

1
This document explains how to install CX3-series hardware in cabinets
that conform to the National Electrical Manufacturer’s Association
(NEMA) standards for 19-inch cabinets (in which the left and right
mounting channels are 19 inches apart). It covers mounting hardware
for SPS, SPE3, and DAE3P components, and describes how to cable the
system to AC power and set up the back-end (disk I/O) bus. In most
cases, the illustrations and examples refer to standard cabinets that are
40U tall.
Topics are:
â—†Device placement requirements......................................................... 1
â—†Device height requirements................................................................ 5
â—†Power requirements............................................................................. 4
â—†Installing a 1U storage processor enclosure (SPE3) in a cabinet.... 8
â—†Installing a 1U SPS tray and SPS units in a cabinet....................... 13
â—†Installing a 3U disk enclosure (DAE3P) in a cabinet..................... 20
â—†Setting up an installed storage system............................................ 28
Note: Instructions for adding switches to a storage system are included in the
device-specific documentation that accompanies the switch.
Device placement requirements
This document provides the steps required to install rails and enclosures
in both EMC and non-EMC cabinets. Unless otherwise specified, the
illustrations depict the 40U-C cabinet.
EMC
Rails and Enclosures
(CX3-10 Class and CX3-20 Class Storage Systems)
Field Installation Guide
P/N 300-004-546
REV A03
July 20, 2007
2EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Device placement requirements
Figure 1 Typical cabinet front and rear views
Before attaching the mounting rails or trays in any cabinet, you must
decide where to put them. Where you install the devices depends on
the kinds of devices you will install and the height of each device.
Position in the cabinet
Devices with internal cooling fans or blowers that move air from
front to back (or vice versa) and not from beneath or above have no
special cooling requirements that direct placement in the cabinet. All
of the storage systems and enclosures mentioned in this document
have fans or blowers that move air from front to back.
EMC220
3
Fr
o
nt R
ea
r
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 3
Device placement requirements
In most cases, you should install devices starting at the bottom of the
cabinet. Installing bottom to top offers the advantages of stability and
convenient cable access from beneath.
We recommend the device placement configuration shown (from the
rear) in Figure 2.
Figure 2 Sample device placements with an SPE3
Note: Place the disk enclosure (DAE3P) that contains specially marked "array
software" disks 0-4 as close as possible to the CX3-series storage processor
enclosure (SPE3). In most cases, install that first enclosure (sometimes called
the DAE3P-OS, or vault) directly above the standby power supply (SPS).
Stack additional DAE3Ps directly above the DAE3P-OS.
EMC3477
!!
!!
!
EXPPRI
EXP
PRI
#
!
EXPPRI
EXP
PRI
#
A
B
SPE3
1U SPS
DAE3P-OS
4EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Power requirements
Review your plan to make sure all devices will fit in the cabinet. It is
also important to verify cabling lengths before installing any
enclosure.
Power requirements
Power distribution must support the number of outlets required for
the device and the device power rating.
Use the published technical specifications and device rating labels to
determine the current draw of each device in your cabinet and
calculate the total. Use the following values to calculate current draw
for CX3-series storage-system components.
Note: These are maximum ratings for a class family, to guide the
sizing of power distribution components at the rack level. Since model
configurations and drive types vary, they may not be appropriate to
estimate typical power consumption.
Note: For high availability, the left and right sides of any rack or cabinet must
receive power from separate branch feed circuits.
CX3-10//20
1000 W SPS
SPE3
(CX3-10)
SPE3
(CX3-20)
DAE3P
disk enclosure
0.2 A@ 100 V AC
0.1 A @ 200 V AC
2.4 A @ 100 V AC
1.5 A @ 200 V AC
3.3 A @ 100 V AC
1.9 A @ 200 V AC
4.4 A @ 100 V AC
2.2 A @ 200 V AC
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 5
SPE3, DAE3P, and SPS operating limits
SPE3, DAE3P, and SPS operating limits
The ambient temperature specification is measured at the front bezel
inlet. The site must have air conditioning of the correct size and
placement to maintain the specified ambient temperature range and
offset the heat dissipation listed below.
IMPORTANT: For systems mounted in a cabinet, the operating limits listed
above must not be exceeded inside the closed cabinet. Equipment mounted
directly above or below an SPE3 storage system must not restrict the
front-to-rear airflow of the storage system. The cooling airflow through the
storage system is approximately 64 cubic feet per minute (cfm). Cabinet
doors must not impede the front-to-rear airflow. The cabinet must exhaust air
at a rate that is equal to or greater than the sum of the exhaust rates of all the
equipment mounted in the cabinet. For example, in a cabinet containing one
SPE3 (64 cfm) and six DAE3Ps (55 cfm), the cabinet must exhaust at least
64+6x55 cfm, which equals 394 cfm.
Device height requirements
Device height requirements and cabinet mounting measurements are
based on NEMA units (U’s). See Table 1.
Requirement Description
Ambient temperature 10°C to 40°C (50°F to 104°F)
Temperature gradient 10°C/hr (18°F/hr)
Relative humidity 20% to 80% noncondensing
Elevation 2438 m (8,000 ft) at 40°C
3077 m (10,000 ft) at 37°C
Table 1 NEMA unit heights
Number of U’s Actual height
1U 1-3/4 inches
2U 3-1/2 inches
3U 5-1/4 inches
4U 7 inches
6EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Device height requirements
The predrilled holes in the cabinet channels are based on the U
measurement. The holes are predrilled at distances of 1/2 inch, 5/8
inch, 5/8 inch (totaling one U), then 1/2 inch, 5/8 inch, 5/8 inch
(another U), and so on. On EMC 40U and 40U-C cabinets, the 1U
increments are marked by a horizontal line or small hole in the
channel. See Figure 3 on page 7 on the next page.
Table 2 lists the vertical space requirements of typical rackmounted
devices.
Table 2 Height requirements of typical devices
Height
Number of
cabinet channel holes Typical device example
1U, 1-3/4 in, 45 mm 3 CX3-10, CX3-20 and
CX3-40 SPS, CX3- series
SPE3, some switches
2U, 3-1/2 in,90 mm 6 CX3-80 SPS,
some switches
3U, 5-1/4 in, 133 mm 9 EMC DAE2P, DAE3P
4U, 7 in, 178 mm 12 CX3-series SPE2
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 7
Device height requirements
Figure 3 U increments in a cabinet front channel
EMC2205
1
2
3
4
5
6
7
8
1U (1.75-in.)
Increment
8EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 1U storage processor enclosure (SPE3) in a cabinet
Installing a 1U storage processor enclosure (SPE3) in a cabinet
Follow the steps below to install a 1U SPE3 device in a standard 19"
NEMA cabinet.
Enclosure mounting kit
Before you start, be sure you have all the materials listed in Table 3.
Tools are not part of your purchased enclosure assembly.
Installing the adjustable rails
1. Locate and unpack the rail kit that accompanied your enclosure.
The front edge of each rail is stamped L or R for left and right
sides, when they face the cabinet front.
Table 3 Enclosure mounting kit materials
Component Use
2 adjustable rails (20.5-34 inches) Attach front to back on either side
between NEMA channels in a standard
19" cabinet
Ten (10) Phillips M5 12.7 mm screws Attach the rail mounting hardware in a
40U cabinet
2 latch brackets
Secure 1U bezel in 40U cabinets
1U bezel (front rack panel) with keys EMI shielding
EMC3429
(L)
(R)
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 9
Installing a 1U storage processor enclosure (SPE3) in a cabinet
2. From the front of the cabinet, insert the alignment pin on the right
mounting rail assembly into the middle hole of the selected 1U
space on a rear channel. Figure 4 shows the correct channel holes
for the alignment pins.
Figure 4 Aligning pins in a 1U section on the cabinet rear rails
1U
Alignment Pin
Here
EMC29
2
10 EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 1U storage processor enclosure (SPE3) in a cabinet
Refer to Figure 5 as you perform steps 3 through 6.
3. Pull the adjustable rail forward to the inner side of the front
channel (the surface facing the rear of the cabinet), and align the
three holes on the rail with those in the channel.
4. Secure the rail to the front channel using one of the provided
screws at the top hole of the rail. Leave the screw slightly loose to
allow for adjustment after you install the enclosure.
5. Repeat steps 2 through 4 on the left side, with the left rail.
6. From the rear of the cabinet, use two of the provided screws to
secure each rail to the rear channel. Tighten the screws.
Figure 5 Installing the adjustable mounting rails
EMC3430
Right rear
Screw (2)
Mounting rail Alignment pin
Left front
Screw (1)
Mounting rail
Alignment pin
Alignment pin
Adjustable rail
Front
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 11
Installing a 1U storage processor enclosure (SPE3) in a cabinet
Installing the SPE3 enclosure in the cabinet
WARNING
The enclosure is heavy and should be installed into a rack by two
people. To avoid personal injury and/or damage to the equipment, do
not attempt to lift and install the enclosure into a rack without a
mechanical lift and/or help from another person.
L’armoire étant lourde, sa mise en place sur une rampe nécessite deux
personnes. Afin de ne pas vous blesser et/ou endommager le matériel,
n’essayez pas de soulever et d’installer l’armoire sur une rampe sans
avoir recours à un relevage mécanique et/ou à l’aide d’une autre
personne.
Das Gehäuse ist schwer und sollte nur von zwei Personen in einem
Rack installiert werden. Zur Vermeidung von körperlichen
Verletzungen und/oder der Beschädigung des Gerätes, bitte das
Gehäuse nicht ohne die Hilfe einer zweiten Person anheben und
einbauen.
Il contenitore è pesante e dev'essere installato nel rack da due
persone. Per evitare danni personali e/o all’apparecchiatura, non
tentare di sollevare ed installare in un rack il contenitore senza un
sollevatore meccanico e/o l’aiuto di un’altra persona.
Debido a su considerable peso, la instalación del compartimento en
el bastidor deben realizarla siempre dos personas. Para evitar daños
personales o en el equipo, el compartimento no debe levantarse ni
instalarse en el bastidor sin la ayuda de un elevador mecánico o de
otra persona.
12 EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 1U storage processor enclosure (SPE3) in a cabinet
Follow these steps to install the enclosure on the rails in the cabinet:
1. With help from another person, lift the enclosure and, from the front
of the cabinet, slide the enclosure onto the rails as shown in
Figure 6.
Figure 6 Sliding an enclosure onto the mounting rails
When the enclosure slides to the back of the cabinet, the two
notches in the rear of the enclosure insert into the rear tabs on the
back corner of each rail. The tabs secure and support the rear of
the enclosure.
Note: If the chassis does not slide all the way into the cabinet, you may
need to further loosen the screws that hold the rear of the rails in place,
then adjust the rails to allow the tabs to fit into the notches.
2. Once the enclosure is completely seated into the rear tabs, tighten
the two screws (the top one on each rail) that secure the rails to
the front channels.
Front
Rear
EMC3431
Securing tabs
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 13
Installing a 1U SPS tray and SPS units in a cabinet
3. Secure the front of the enclosure and the mounting rail to the
front vertical channels of the cabinet using two M5 12.7 mm
screws (one per side), in the bottom holes as shown in Figure 6.
Note: A screw in the middle hole will secure the latch bracket mounted
on the front of the enclosure.
Installing the latch brackets and bezel
This section describes how to install latch brackets and the bezel they
support.
1. Use one screw to secure a latch bracket to each front channel. (The
brackets include small alignment bumps to correctly orient them
to the channel.) See Figure 7.
2. Press the bezel onto the latch brackets until it snaps into place. See
Figure 7.
Figure 7 Installing the latch bracket and bezel
Installing a 1U SPS tray and SPS units in a cabinet
This section explains how to install a 1U SPS (standby power supply)
tray in the cabinet. CX3-20 class systems require two 1000w 1U SPS
units in a single 1U tray; a second SPS unit is optional in CX3-10 class
systems.
EMC3450
Bezel
latch
bracket
Bezel
latch
bracket
14 EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 1U SPS tray and SPS units in a cabinet
SPS mounting kit The SPS mounting kit includes the components listed in Table 4.
.
Table 4 SPS mounting materials
Component Use
2 adjustable
(20.5-34 inches) rails
Attach front to back on either side
between NEMA channels in a 40U
cabinet
SPS B filler unit For configurations with a single SPS
unit, covers opening in back of tray
SPS tray - see Figure 10 on page 17 For one or two SPSs
Front fastener bracket
Secure SPS units to tray
M4 x 8-mm panhead screw, lock washer,
and flat washer assemblies 8 for back of tray
M4 x 10-mm flathead screws 6 for front of tray and fastener bracket
2 latch brackets
Secure 1U bezel in 40U cabinets
10 Phillips M5 x 16-mm panhead screws
(black) Attach the rail mounting hardware in a
40U cabinet
EMC3298
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 15
Installing a 1U SPS tray and SPS units in a cabinet
Removing the filler panels
In most cases, the front space into which you will install your
component is covered by a filler panel, which is attached to latch
brackets.
Remove any filler panel, then use a flat-blade screwdriver or similar
tool to pry off the latch brackets.
Installing the rails in the cabinet
This section describes how to mount the rails in the cabinet.
1. After you decide where in the cabinet you want to install the SPS
tray, find the unoccupied 1U section on the rear channels. We
suggest that you install the SPS tray immediately above the SPE3,
if possible (refer to the device placement examples beginning on
page 3).
2. From the front of the cabinet, insert the alignment pin on one
mounting rail assembly into the middle hole of the selected 1U
space on a rear channel. Figure 8 shows the correct channel holes
for the alignment pins.
Figure 8 Aligning pins in a 1U section on the cabinet rear rails
1U mounting tray bezel (see Figure 12 on page 19) 1 per tray
26-inch IEC power cord, straight C13 to C14 1 per SPS
(Select per cabinet PDU outlets.)
Table 4 SPS mounting materials (continued)
Component Use
1U
Alignment Pin
Here
EMC2922
16 EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 1U SPS tray and SPS units in a cabinet
Refer to Figure 9 on page 16 as you perform steps 3 and 4.
3. Extend the rail to the front cabinet channel. Align the holes of the
front rail flange to the inside of the channel, ensure that the rail is
level, and then install two M5 x 16-mm Phillips securing screws
in the top and bottom holes, as shown in Figure 9.
Note: Leave the screws slightly loose to allow for adjustment after you
install the tray. Do not insert a screw in the middle hole yet.
4. At the back of the cabinet, insert and tighten two M5 x16-mm
securing screws in the holes above and below the alignment pin,
as shown in Figure 9.
Figure 9 Installing the 1U SPS adjustable rails
5. Repeat steps 2 through 4 for the other rail assembly.
EMC3253
Adjustable rail Alignment pin
Alignment pin
Front
Left front
Screw (2)
Mounting rail
Right rear
Screw (2)
Mounting rail Alignment pin
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 17
Installing a 1U SPS tray and SPS units in a cabinet
Installing the SPS tray in the cabinet
This section describes how to install the tray in the rackmount
cabinet.
1. From the front of the cabinet, align the SPS tray with the channels
on the mounting rails. Position the tray as shown in Figure 10.
2. Slide the tray onto the mounting rails in the cabinet, until the
flanges of the tray are flush with the cabinet channels. See
Figure 10.
Figure 10 Inserting the SPS tray in the cabinet
3. Do not insert any new screws, but tighten the four securing
screws (two on each side - see Figure 9) that hold the mounting
rails to the channels.
You have installed an SPS tray. Continue to the next section to install
SPS units.
Installing the SPS units in an SPS tray
1. Remove the SPS units from their packaging.
2. Working from the front of the cabinet, slide the SPS units onto the
tray as shown in Figure 11.
EMC3252
Rear
18 EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 1U SPS tray and SPS units in a cabinet
Note: For systems with a single SPS unit, install the SPS in the left (from
the front) slot.
Figure 11 Inserting the SPS units into the SPS tray
Note: To eliminate potential bow caused by the weight of the SPS(s),
press up on the middle of the tray with one hand while you secure the
units to the tray.
3. Attach the front fastening bracket, and insert and tighten the
M4 x 10-mm flathead securing screws as shown in Figure 11.
4. Insert and tighten the M4 x 8-mm panhead securing screws that
secure the SPS units to the back of the tray, as shown in Figure 11.
Back
Front
EMC32
5
Screw (6)
Screw (8)
EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide 19
Installing a 1U SPS tray and SPS units in a cabinet
Installing latch brackets and bezel
This section describes how to install latch brackets and the bezel they
support.
1. Use one Phillips M5 x 16-mm screw to secure a latch bracket to
each front channel. (The brackets include small alignment bumps
to correctly orient them to the channel.) See Figure 12.
2. Press the bezel onto the latch brackets until it snaps into place. See
Figure 12.
Figure 12 Installing the latch bracket and bezel
EMC3250
Front
Rear
Latch
Bracket
Latch
Bracket
20 EMC Rails and Enclosures (CX3-10 Class and CX3-20 Class Storage Systems) Field Installation Guide
Installing a 3U disk enclosure (DAE3P) in a cabinet
Installing a 3U disk enclosure (DAE3P) in a cabinet
Follow the steps below to install a 3U DAE3P disk enclosure in a
standard 19" NEMA cabinet.
Enclosure mounting kit
Before you start, be sure you have all the materials listed in Table 5.
Tools are not part of your purchased enclosure assembly.
Table 5 Enclosure mounting kit materials
Component Use
2 adjustable rails (20.5-34 inches) Attach front to back on either side
between NEMA channels in a standard
19" cabinet
12 Phillips M5 12.7 mm screws Attach the rail mounting hardware in a
40U cabinet
3U bezel (front rack panel) with keys EMI shielding
(L)
(R)
EMC3248
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34

EMC CX3-20 Field Installation Manual

Type
Field Installation Manual
This manual is also suitable for

The EMC CX3-20, a 1U storage processor enclosure, offers exceptional storage capacity and robust data protection for small and medium-sized businesses. Featuring a compact and versatile design, it's ideal for organizations seeking reliable and scalable storage solutions. With its advanced hardware architecture, the CX3-20 delivers exceptional performance, enabling you to manage and access your data efficiently.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI