Eaton ULCAS380 Installation guide

Type
Installation guide

Eaton ULCAS380 is a sounder base compatible with Eaton Cooper Analogue Addressable Panels. It can be used with detector heads from Eaton Cooper, Menvier or JSB. The device uses a supervised, power limited SLC Circuit with a maximum wiring gauge of 12 AWG. It has an IP21C ingress protection rating and can operate in temperatures up to 37.8°C (100F) and humidity of 0-93%RH (Non Condensing). The Eaton ULCAS380 is compatible with the following detector heads: ULCAP320, ULCAH330, ULCAPT340, ULMAP320, ULMAH330, ULMAP340, ULFX320, ULFX330, ULFX340.

Eaton ULCAS380 is a sounder base compatible with Eaton Cooper Analogue Addressable Panels. It can be used with detector heads from Eaton Cooper, Menvier or JSB. The device uses a supervised, power limited SLC Circuit with a maximum wiring gauge of 12 AWG. It has an IP21C ingress protection rating and can operate in temperatures up to 37.8°C (100F) and humidity of 0-93%RH (Non Condensing). The Eaton ULCAS380 is compatible with the following detector heads: ULCAP320, ULCAH330, ULCAPT340, ULMAP320, ULMAH330, ULMAP340, ULFX320, ULFX330, ULFX340.

Sounder Base ULCAS380, ULMAS850, ULFXN538LBS Effective April 2019
Installation Instructions
Model No. Brand
ULCAS380 Eaton Cooper
ULMAS850 Eaton Menvier
ULFXN538LBS Eaton JSB
Installation
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram below.
3. Recommended Loop Cable Type: FIRETUF, FP200
1. Mounting Base
I. Knock-out the required fixing holes.
II. Fix to mounting surface using two suitable screws
If the base deforms on an uneven surface. Loosen the screws or
move to a more flat position.
When used with a detector, the installation and spacing shall be
in accordance with the requirements for smoke detectors (NFPA
72, Chapter 17).
When installed with the blank cover,the installation and spacing
shall be in accordance notification appliances
(NFPA 72, Chapter 18.)
2. Sounder Assembly
Clip sounder onto base. If sounder needs to be removed use a
small screwdriver to unclip.
3. Locking Tab (optional)
Fit the locking tab into the square
hole on the shoulder.
Finish assembly as stage 5.
Remove by inserting a suitable tool
(e.g. A thin screwdriver) into the hole
in the detector or cover, then rotate
detector or cover anti-clockwise.
4. Fitting Detector or Cover
5. Standard Connections (see diagram overleaf)
Warning: Do NOT use high voltage tester if ANY equipment is
connected to the system.
All connections are Power Limited.
When the base is used with the blank cover: Multiple tone
appliances which produce the three pulse temporal pattern for
the international evacuation signal [NFPA 72 (National Fire Alarm
Code)], shall be used for evacuation use only. The base must not
be used for evacuation when used with a detector head.
ote: N No addressing of the interface is required. See control panel
operation for details.
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
Installation Instructions
Effective April 2019
INSTALLATION INSTRUCTIONS 25-10822-B April 2019
Eaton
EMEA Headquarters
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu
TEL: +44 (0) 1302 321541
FAX: +44 (0) 1302 303220
© 2019 Eaton
All Rights Reserved
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
www.Eaton.com
Eaton Electrical Systems Ltd.
Wheatley Hall Road
Doncaster
DN2 4NB
TEL: +44 (0) 1302 303303
FAX: +44 (0) 1302 367155
50
60
70
80
Locking tab
release hole
S+
S-
F-
F+
Compatible Analogue
Addressable Panel
Loop StartLoop Finish
in
- +
3
E
4
1
2
- +
out
43
61-71
102
Sounder and Cover Sounder and Detector
ø
102ø
in
- +
3
E
4
1
2
- +
out
Do not use this
connection
Terminate the screen as a oating
joint to the rear of the base within the
cable termination box
Do not use this
connection
ULCAS380, ULMAS850, ULFXN538LBS
Sounder base Specification
Voltage 21-32Vdc
Current (Nominal) 388 μA
UL 464 Sound Output (dBA)
Settings Continuous Tone@3m Three Tone Temporal @3m
High 79.0 75.4
Medium 77.2 74.0
Low 71.7 71.3
Volume
(Ratings were obtained with the
blank cover ULCASC and do not
apply when used with a
detector head.)
Tone
Three Tone Temporal
Tone (mA)
Three Tone Temporal @3m
Low 13.24 13.68
Medium 13.52 13.60
High 13.96 13.92
Environmental
Max Ambient Temperature 37.8 °C (10 0F)
Humidity
(Non Condensing)
0-93%RH
Standards
Approved to UL464, UL521, UL268
Physical
Weight 206g
Ingress Protection Type A (IP21C)
Field Wiring SLC Circuit (input)
Wiring Gauge 12 Max AWG
Wiring Class Class A Style 7
Ground Fault Impedance 0.1 Ohm
Supervised, power limited Yes
This model is restricted for use
with the following UL Listed Panels Panel Compatibility
Cooper ULCF30002G, ULCF30004G, ULCF30002GP,
ULCF30004GP, ULCF30002GNC, ULCF30004GNC,
ULCF30002GPNC, ULCF30004GPNC, ULCF30002GRM,
ULCF30004GRM, ULCF30002GPRM, ULCF30004GPRM,
ULCF30002GNCRM, ULCF30004GNCRM,
ULCF30002GPNCRM, ULCF30004GPNCRM, ULR3000L2,
ULR3000L4, ULR3000L2NC, ULR3000L4NC
Menvier ULDF60002G, ULDF60004G, ULDF60002GNC,
ULDF60004GNC, ULDF60002GP,
ULDF60004GP,ULDF60002GPNC,
ULDF60004GPNC, ULDF60002RM, ULDF60004RM,
ULDF60002NCRM,ULDF60004NCRM,
ULDF60004NCRM, ULDF60002PRM, ULDF60004PRM,
ULDF60002PNCRM,ULDF60004PNCRM, ULR6000L2,
ULR6000L4, ULR6000L2NC, ULR6000L4NC
JSB ULFX60002G, ULFX60004G, ULFX60002GNC,
ULFX60004GNC, ULFX60002GP,
ULFX60004GP,ULFX60002GPNC,
ULFX60004GPNC, ULFX60002RM, ULFX60004RM,
ULFX60002NCRM,ULFX60004NCRM, ULFX60002PRM,
ULFX60004PRM, ULFX60002PNCRM,
ULFX60004PNCRM,ULFXR6000L2, ULFXR6000L4,
ULFXR6000L2NC, ULFXR6000L4NC
This model is suitable for use with
the following detector heads Detector Head Compatibility
Cooper ULCAP320, ULCAH330, ULCAPT340
Menvier ULMAP320, ULMAH330, ULMAP340
JSB ULFX320, ULFX330, ULFX340
Order Codes Product Brand
ULCAS380
Addressable Sounder Base Cooper
ULMAS850
Addressable Sounder Base Menvier
ULFXN538LBS
Addressable Sounder Base JSB
ULCASC
Lid for Sounder Base -
  • Page 1 1
  • Page 2 2

Eaton ULCAS380 Installation guide

Type
Installation guide

Eaton ULCAS380 is a sounder base compatible with Eaton Cooper Analogue Addressable Panels. It can be used with detector heads from Eaton Cooper, Menvier or JSB. The device uses a supervised, power limited SLC Circuit with a maximum wiring gauge of 12 AWG. It has an IP21C ingress protection rating and can operate in temperatures up to 37.8°C (100F) and humidity of 0-93%RH (Non Condensing). The Eaton ULCAS380 is compatible with the following detector heads: ULCAP320, ULCAH330, ULCAPT340, ULMAP320, ULMAH330, ULMAP340, ULFX320, ULFX330, ULFX340.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI