Bentone BG 400-2 LME22 512 VPS UV 60Hz User manual

Type
User manual
Providing sustainable energy solutions worldwide
178 035 74-7 CR00635  2023-07-05
Translation of the original instructions.
Installation- and maintenance instruction
BG 400-2 Biogas
LME22.232C2E
DMV-DLE 512
MVD 215/5
FRS 515
VPS 504
60Hz
2Bentone
example Beispielexempel
352011030141
Designation
Type
Model
Serial no.
Motor supply
Main supply
MADE IN SWEDEN BY
LIGHT OIL 35-90kW 1,25-6,0 cSt 7-14bar
BF 1 KS 76-24
BF 1
BF 1 KS 76-24
1234567
1~230V 1,0A 50Hz IP 20
Man.Year 2019
Cap. Min-Max
3
?
1
-sv
1. Manualer på övriga språk
2. www.bentone.com\
nedladdning eller scanna
QR-koden.
3. Skriv in brännarens
artikelnummer som nns på
din typskylt (se bild) och välj
ditt språk.
Detaljerad ecodesign
information kan laddas ner
på: www.bentone.com/
ecodesign.
-en
1. Manuals in other
languages
2. www.bentone.com\
download or scan QR-code.
3. Enter the burner`s article
number on your data plate
(see picture) and select
language.
Detailed ecodesign
information can be
downloaded at:
www.bentone.com/
ecodesign.
-da
1. Manualer på andre sprog
2. www.bentone.com\
download eller scan
QR-koden.
3. Indtast brænderens
artikelnummer, der ndes
på typeskiltet (se billede), og
vælg dit sprog.
Detaljerede oplysninger om
ecodesign kan downloades
på: www.bentone.com/
ecodesign.
-fr
1. Manuels dans d’autres
langues
2. www.bentone.com\
download ou scannez le
code QR.
3. Saisir le numéro d’article
du brûleur sur votre plaque
signalétique (consultez
l’illustration) et sélectionnez
la langue.
Des informations détaillées
sur l’écodesign peuvent être
téléchargées à l’adresse:
www.bentone.com/
ecodesign.
-de
1. Gebrauchsanweisungen
in anderen Sprachen
2. www.bentone.com\
download oder scannen Sie
den QR-Code.
3. Geben Sie die
Artikelnummer des Brenners
auf Ihrem Typenschild ein,
(siehe Bild) und wählen Sie
die Sprache aus.
Detaillierte Informationen
zum Ecodesign können unter
www.bentone.com/ecodesign
heruntergeladen werden.
2
3 Bentone
Table of contents
1. General Information ............................................................4
1.1 Delivery inspection........................................................................ 4
1.2 Safety ............................................................................................... 4
1.3 What to do if you smell gas ......................................................... 5
2. Technical data .......................................................................6
2.1 Dimensions BG 400-2 .................................................................. 6
2.2 Capacity range ............................................................................... 7
2.3 Gas categories, approved gases ................................................ 7
2.4 Technicalspecication ................................................................. 7
2.5 Workingeld .................................................................................. 8
2.6 Components ................................................................................... 9
2.7 Skeleton diagram 2-stage burner, Biogas ..............................10
2.8 Adjusting the gas train ...............................................................11
3. Electric equipment ............................................................. 12
3.1 Safety system .............................................................................. 12
3.2 Wiring diagram ............................................................................ 12
3.3 Function LME... ............................................................................ 13
3.4 Control program at faults; fault mode indicator LME .... .... 14
4. Installation ..........................................................................16
4.1 General instructions ................................................................... 16
4.2 Instructions .................................................................................. 16
4.3 Inspection and maintenance .................................................... 16
4.4 Preparation for assembly ......................................................... 16
4.5 Gas supply .................................................................................... 16
4.6 Electric connection ..................................................................... 16
5. Mounting ............................................................................17
5.1 Gas nozzle.....................................................................................18
5.2 De-aerating ...................................................................................19
5.3 Tightness control ........................................................................19
5.4 Calculationofgasow .............................................................. 20
6. Settings ...............................................................................21
6.1 Brake plate adjustment .............................................................21
6.2 Control of burner head ..............................................................21
6.3 Startup ........................................................................................... 21
6.4 Control of combustion .............................................................. 21
6.5 Settingtheairpressureswitch ................................................ 22
6.6 Settingthegaspressureswitchmin ....................................... 23
6.7 Settings Damper motor, 2-stage ............................................. 24
7. Double Solenoid Valve DMV-DLE ......................................25
7.1 Technical data .............................................................................. 25
7.2 DMV-DLE 512-520/11 ................................................................. 26
7.3 DMV-DLE 525/11 ......................................................................... 26
8. Gas solenoid valve MVD 210/5 / MVD 215/5 ...................28
9. Gas pressure regulator .....................................................30
10. Leakage control VPS 504 .................................................. 32
10.1 Technical data .............................................................................. 32
10.2 Program sequence ..................................................................... 32
10.3 Electrical connection ................................................................. 33
11. Service .................................................................................34
11.1 Burner Service Schedule, Gas .................................................. 34
11.2 Component replacement intervals ..........................................34
11.3 Combustion device ..................................................................... 35
11.4 Air damper ................................................................................... 36
11.5 Replacement, Damper motor air ............................................. 37
11.6 Fan ................................................................................................. 38
11.7 Replacement of electrical components .................................. 39
11.8 Vibrations ......................................................................................40
11.9 Controlofamemonitoringandionizationcurrent ........... 41
12. Handing over of the installation ......................................43
13. Troubleshooting ................................................................. 44
14. Service- and inspection protocol .....................................46
4Bentone
172 515 01-2  2021-10-05
1. General Information
The burner may only be used for its intended purpose in accordance with the
product’s technical data.
We reserve the right to make design changes and cannot be held liable for any
misprints or typographical errors.
Modifying the design or using accessories or components that have not been
approved by Enertech in writing is strictly prohibited.
This Installation and Maintenance manual:
is to be regarded as part of the burner and must always be kept near
the installation site.
must be read prior to installation.
is intended for use by authorised personnel.
1.1 Delivery inspection
Make sure everything is delivered and the goods have not been
damaged during transit. Transport damage should be reported to the
shipping company.
If something is wrong with a delivery, report it to the supplier.
1.2 Safety
- before installation:
Installation and work on the burner and associated system
components may only be carried out by persons who have undergone
relevant training.
The product is packaged to prevent damage from occurring when
handled – Handle the product with care! Lifting equipment must be
used to lift larger packages.
The products must be transported/stored on a level surface in a dry
environment, max. 80% relative humidity, no condensation.
Temperature -20 to +60 °C.
- installation:
The burner must be installed in accordance with local regulations for
re safety, electrical safety, and fuel distribution.
The premises must comply with local regulations pertaining to use of
the burner and must have adequate air supply.
The installation site must be free of chemicals.
Fire extinguisher with Class BE recommended.
Make sure when installing the burner that there is enough space to
service the burner.
The electrical installation must be professionally carried out in
accordance with current mains electricity regulations and in a
professional manner.
Make sure that the burner is suitable for the application (see Technical
Data).
All components must be installed without being bent, twisted or
subjected to mechanical or thermal forces that affect components.
5 Bentone
Care must be taken by the installer to ensure that no electrical cables
or fuel lines are pinched or otherwise damaged during installation or
service.
Sharp edges can occur on, for example: ame tube, fan wheel and air
damper.
The gas outlet from the pressure regulator must be congured in
accordance with applicable regulations and lead to a safe area.
- before rst start:
The burner must not be put into operation without proper safety and
protection devices.
Permitted ambient temperature during operation -10 to +60 °C. Max.
80% relative humidity, no condensation.
The surface temperature of the burner’s components may exceed
60 °C.
Handle with caution – the burner has moving parts, and there is risk
of crushing injuries.
Seal inspections must be performed during installation and servicing
to prevent leakage.
Fitting and installation work has been completed and approved.
Electrical installation has been correctly performed.
Flue gas ducts and combustion air ducts are not blocked.
All actuators and control and safety devices are in working order and
correctly set.
If the boiler is equipped with an access hatch, this must be equipped
with a hatch opening switch connected to the burner’s safety system.
When in operation, the burner’s noise level can exceed 85 dBA – use
hearing protection!
- operation:
Carry out all stipulated settings, service and inspection work within
the set time.
1.3 What to do if you smell gas
Turn off the fuel supply.
Turn off the device and remove the boiler from operation.
Open windows and doors.
Prevent open ames or sparking, e.g. do not turn lights on or off, do
not use any electrical appliances or mobile phones.
Evacuate the building.
Notify the installer or gas supplier of the problem so that it can be
rectied.
6Bentone
2. Technical data
The burner is intended for:
Operation in installations according to EN 303 and EN 676.
Fuels:
Natural gas H, E, L, LL.
LPG, Butane and Propane.
Dry biogas max 0.1 Vol% H2S and min 50% CH4.
2.1 Dimensions BG 400-2
172 535 44-2  2023-07-05
Length of
ame tube
Flame tube
measure A
Flame tube
measure B
Flame tube
measure C
172 155 ø140 ø110
272 255 ø140 ø110
* The above dimensions are max. measurements. Depending on the components used, the measurements may vary.
** Min. recommended distance to oor.
K L M
12 ø175-240 ø145 (***115)
D E F G H I J
100 410 250 *410 192 *506 **200
K
L
M
***Dimensions when installing ame tube from the inside of the boiler.
2.1.1 Measurements for connection to the boiler
I
øC
A D
H
F
E
øB
G
**J
160303-622
7 Bentone
2.3 Gas categories, approved gases
Components are approved for dry biogas with a maximum content of 0.1% H2S.
2.2 Capacity range
BG 400-2
G20  61 - 325 6.5 34.4 200
G25  61 - 310 7.5 38.1 200
G30  75 - 340 2.3 10.5 200
G31  75 - 350 3.1 14.3 200
    61 - 250 10.2 41.7 200
160303-627-2
Capacity
kW
Gas quantity
at min. power
Nm3/h
Gas quantity
at max. power
Nm3/h
Max.
connection
pressure mbar
Min
connection
pressure mbar
See data plate.
Biogas
Gas quantity and capacity vary according to grade of gas and connection pressure.
Category Country of destination Supply pressure
II2R3R AT, BE, BG, CH, CY, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HR, HU, IE,
IS, IT, LT, LU, LV, MK, MT, NL, NO, PL, PT, RO, RS, SE, SI, SK, TR 20 mbar
II2H3B/P AT, CH, CY, DK, FI, LT, RO, SE, SK 20 mbar
II2H3P GB, IE 20 mbar
II2L3B/P RO 20 mbar
II2E3B/P PL 20 mbar
I2E(R)B BE 20 mbar
I3P BE 20 mbar
II2EK3B/P NL 20 mbar
160302-223-4
2.4 Technical specication
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be reduced by equipping the burner with
silencer. Installation must be done so it does not prevent air supply to the
burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
BG 400-2
Main supply 230V, 1~, 2.2A, 60Hz, IP20
Max fuse rating 6.3A
NOX-class 2 G20, G25 / 3 G30, G31
Noise level 89dBA
8Bentone
!Do not exceed working
eld.
2.5 Working eld
Biogas
-1
0
1
2
3
4
5
6
7
8
50 100 150 200 250 300 350
mbar
kW
G20 61-325 kW
G25 61-310 kW
160302-579-2
-1
0
1
2
3
4
5
6
7
50 100 150 200 250
mbar
kW
61-250 kW
160303-619
-1
0
1
2
3
4
5
6
7
8
50 100 150 200 250 300 350
mbar
kW
G30 75-340 kW
G31 75-350 kW
160302-788
Natural gas, LPG, Butane and Propane
9 Bentone
2.6 Components
1. Switch 0-I
2. Switch I-II
3. Cover, inspection glass
4. Reset button
5. Air pressure switch
6. Damper motor
7. Nozzle control
8. Flame tube
9. Gas valve
10. Connection, gas ttings
11. Air damper
12. Air intake
13. Gas pressure switch, Min.
14. Burner control
15. Fan wheel
16. Electrical connection
17. Motor
18. Ignition electrode
19. Transformer
20. Ionization electrode
21. Nozzle
22. Brake plate
23. Indication lamp, Stage I
24. Indication lamp, Stage II
13
14
17
18
21
20
19
12
22
7
160303-626
16
3
5
6
10
11
9
8
160303-625
1 2
4
23 24
15
10 Bentone
172 515 72-2
2.7 Skeleton diagram 2-stage burner, Biogas
Gas train
1. Ball valve
2. Filter
3. Pressure regulator
4. Pressure outlet
5. Gas valve
6. Leakage control (VPS)
7. Safety valve on-off
8. Gas pressure switch
Pe Pressure before valve
Pa Pressure between valves
Adjusting points:
a. Main ow restrictor stage 2
(max load)
b. Gas pressure adjustment
c. Main ow restrictor stage 1
(min load)
d. Hydraulic brake stage 1 to 2
8
5 6 73
Pe Pa
21
4
a bd
c
11 Bentone
2.8 Adjusting the gas train
The burner is test run with propane before delivery.
The safety valve (7) must be fully open during operation. At initial setting, the
adjusting screw (c) must have lifted the valve for stage 1 by 1-2 turns.
On start-up, safety valve (7) and valve on double solenoid valve (5) open, gas
ows through the valve for stage 1.
When the burner has started on stage 1, proceed to stage 2 and start adjusting
this stage rst. When stage 2 is complete, adjust stage 1.
Adjustment of stage 2 is done with adjusting screw (a) on the double solenoid
valve (5) which regulates the opening of the valve controlling the gas for
stage 2. The burner is now receiving gas for maximum load, adjust the power
on stage 2 to the desired load and set the air damper for stage 2 and nozzle
assembly for a good combustion.
The power is adjusted for stage 2 by adjusting the opening of valve 1 with the
adjusting screw (a) and the gas pressure is adjusted on the pressure regulator
screw (b). The air damper and nozzle assembly shall also be adjusted to obtain
the correct air volume and good combustion.
Adjustment of stage 1 on the burner is done when stage 2 is complete, adjust
the stage 1 valve on the double solenoid valve (5) using the adjusting screw (c).
If this is screwed in, the gas ow to the burner is increased by lifting the valve.
This valve is always open and this opening is what gives the min-load. Adjust
the air damper for stage 1 for good combustion.
12 Bentone
3. Electric equipment
3.1 Safety system
The safety system (safety switch for hatches, doors, water level, pressure,
temperature and other safety devices) must be installed in the safety circuit in
accordance with current regulations for the system.
The cables of the safety system must be separated so that the outgoing signal
is not placed in the same cable as the incoming signal.
3.2 Wiring diagram
172 615 31-2  2022-11-28
E106020
Bn Brown
Bu Blue
Gn Green
Ye Yellow
Gn/Ye Green/Yellow
Bk Black
Gy Grey
Rd Red
Wh White
Og Orange
Vt Violet
13 Bentone
3.2.1 Components
A1 Burner control
A3 Leakage control, VPS 504
F1 Operating fuse
H1 Lamp, low capacity
H2 Lamp, high capacity
H3 Alarm signal 230V
M1 Motor
M2 Damper motor
P1 Time meter, total operating
time
P2 Time meter, high capacity,
total operating time
Q1 Signal amplier AGQ
R1 UV-Detector
S1 Operating switch
S2 Operating switch, stage 2
S3 Control thermostat
S4 Temperature limiter
S5 Micro switch for hinged door
S6 Control thermostat, stage 2
S7 Main switch
S8 Air pressure switch
S9 Gas pressure switch
T1 Ignition transformer
X1 Connection terminal board
X2 Earth terminal
X3 Plug-in contact, burner
X4 Plug-in contact, boiler
X5 Plug-in contact, stage 2,
burner
X6 Plug-in contact, stage 2, boiler
Y1 Gas solenoid valve 1
Y2 Gas solenoid valve 2
Y3 Safety solenoid valve
3.3 Function LME...
1. Operating switch ON-Thermostat ON-Gas pressure switch ON
A check that the air pressure switch does not indicate fan pressure is
carried out.
2. Burner motor starts
A check that the air pressure switch indicates sucient fan pressure is
carried out.
3. The ignition spark is created
4. The gas solenoid valve is open
The gas is ignited. The ionisation electrode now indicates a ame.
5. The safety time expires
The ignition spark ceases. The safety period ceases. If the spark is missing
or it disappears after this time limit, the gas burner control is blocked.
6. Operating position
7. Stop
The operation of the burner can now be stopped with the control switch or
thermostat.
If the gas burner control is blocked
Red light in the gas burner control is lit. The burner is restarted by pushing
the reset button.
3.3.1 Technical data
!Mains connection and
fuse in accordance with
local regulations.
LME22.232C2E
3 s
20 s
2.5 s
< 3 s
< 1 s
< 1 s
5 µA
20 µA
160303-325
Preiginition time
Prepurge time
Postignition time
Safety lockout time
Reset time after lockout
Reaction time on  ame failure
Min. ionisation current at  ame
Max. ionisation current
14 Bentone
Light period
(waiting period 10 s) Blinking code Pause Blinking codePress the
reset button > 3 s
3.4 Control program at faults; fault mode
indicator LME ....
3.4.1 Colour codes
3.4.2 Diagnosing alarm causes
After alarm disconnection, the red alarm signal light is lit continuously.
The diagnosing of the alarm cause can be read according to the following
sequence:
3.4.3 Limiting of starting repetitions
LME 11... has a function with start repetition if the ame is not created at start
or disappears during operation.. LME 11... allows max. three repetitions during
continuous starting cycle.
Table colour codes for multi-coloured signal light (LED)
Status Colour codes Colours
Waiting period «tw», other waiting periods ○………………… O
Ignition phase, ignition controlled ●○●○●○●○●○● Blinking yellow
Normal operation □………………… Green
Operation, poor ame signal □○□○□○□○□○ Blinking green
Illegal ame signal during start-up □▲□▲□▲□▲□▲ Green-Red
Undervoltage ●▲●▲●▲●▲●▲ Yellow-Red
Fault, alarm ▲………………… Red
Blinking code for fault codes ▲○ ▲○ ▲○ ▲○ Blinking red
Interface diagnostics ▲▲▲▲▲▲▲▲ Red icking
…… Continuous
Off
Red
Yellow
Green
15 Bentone
3.4.4 Alarm code table
Red blinking code on
signal lamp (LED)
Possible causes
Blinking 2 x
••
No ame creation at End of “TSA
defective or fouled ame monitoring.
defective or fouled fuel valves.
poor burner setting.
defective ring device.
Blinking 3 x
•••
“LP” defective
No air pressure switch signal after “t10”.
“LP” is welded in open position.
Blinking 4 x
••••
Illegal ame signal during start-up.
Blinking 5 x
•••••
Time out “LP”
“LP” is welded in open position.
Blinking 6 x
••••••
Free
Blinking 7 x
•••••••
Too many ame disappearances during operation.
poor burner setting.
defective or fouled fuel valves.
defective or fouled ame monitoring.
Blinking 8 x
••••••••
Free
Blinking 9 x
•••••••••
Free
Blinking 10 x
••••••••••
Connection fault or internal fault, outgoing contacts or
other faults.
Blinking 14 x
••••••••••••••
CPI contact not closed.
During the diagnosing of the alarm cause, the control outputs are voltage-
free.
The burner is disconnected.
Exception, alarm signal «AL» at board 10.
Reconnection of the burner happens after resetting only.
Press the reset button 0.5...3 s.
3.4.5 Interface diagnostics
To change to interface mode, press and hold the reset button longer than 3 s.
To go back to the normal position, press and hold the reset button longer than
3 s. If the gas burner control is in the alarm position, it is reset by pressing the
reset button 0.5...3 s.
16 Bentone
172 535 09-2
4. Installation
4.1 General instructions
Installation must be carried out in accordance with current regulations and
instructions.
The supplier/installer of the facility is obliged to familiarize himself with
all regulations so that the installation meets the requirements of the local
authorities.
Installation, assembly and settings must be performed to obtain the best
possible function. Only gas intended for the gas burner may be used.
4.2 Instructions
It is the installer’s responsibility to instruct the user in detail in the functions of
the gas burner and the entire system.
4.3 Inspection and maintenance
The system must be maintained at the interval specied in the service
schedule. If the burner is in a dirty environment, service should be done at
more frequent intervals.
4.4 Preparation for assembly
Check that the burner’s dimensions and capacity range match the current
boiler. The power information on the type plate refers to the burner model’s
min. and max. effect.
4.5 Gas supply
In order to obtain good operational safety, it is important that the installation
of the gas distribution system is carried out correctly, considering the
following:
Check that the burner is approved for the gas quality of the
installation.
Check that the burner gas components are approved for the specied
gas pressure, see type plate.
Installation must be carried out in accordance with current standards.
Pipe lines should be assembled so that service can easily be
performed on the boiler and burner.
Pipe lines should be assembled so that any contaminants do not come
into contact with the gas components.
4.6 Electric connection
Before work on the electrical connection, the current must be
disconnected so that the installation is isolated.
Connection must be done in accordance with the applicable
regulations.
Connection must conform to the wiring diagram.
!If any electrical connection other than that recommended
by Enertech is used, there is a risk of property damage and
personal injury.
17 Bentone
172 515 06-2  2022-11-28
!Check for leaks in the gas line.
5. Mounting
The burner is mounted on the boiler according to the hole pattern on the
xing ange.
1. Remove the gas valve from the burner.
2. Remove fan housing by loosening nut (A), swing out fan housing.
Disconnect ionisation and ignition cables from the electrodes.
Remove nut (B) on hinged ange and lift fan housing off.
3. Install the xing ange and the supplied gasket on the boiler. If
new mounting holes need to be drilled, use the xing ange as a
template and fasten with M8-M12 screws.
4. Check that the electrodes are correctly set, see chapter Gas
nozzle.
5. Mount the fan housing on the xing ange and fasten with nut
(B).
6. Connect the ionisation and ignition cables.
7. Fit the gas valve.
8. Connect the gas with the ball valve provided. Ensure that the pre-
screwing, ball valve and tubings are done in such a way that the
burner and boiler hatch can be easily used for servicing.
9. Connect the supply cable, operating and safety circuits.
B
A
18 Bentone
5.1 Gas nozzle
Check that the ignition and ionization electrodes are correctly set before
mounting on the boiler.
Natural gasPropan
Biogas (UV detector)
2.5
8.0
172 515 08-2  2022-11-28
19 Bentone
5.2 De-aerating
De-aerating the gas line by closing the tap to the gas connection and
unscrewing the screw on the measuring nipple for the connection pressure.
Connect a plastic hose, open the tap and drain the gas in a safe place. When
the de-aerating is completed, be sure to ret the screw on the measuring
nipple.
5.3 Tightness control
When checking for leakage, the solenoid valve must be closed. A pressure
gauge is connected to the measuring nipple ”Pa”, see picture. The test
pressure in the system must not be higher than max. connection pressure,
see data plate. If leaks are found during measurement, locate the source
using soapy water or leak detection spray. After sealing: check the tightness
of the gas xture again.
!Check the gas tightness.
Pa
20 Bentone
5.4 Calculation of gas ow
Formula symbol Description Example values
VNStandard gas volume [Nm3/h]
Gas volume at normal condition 15 °C 1013 mbar
-
QBoiler output [kW] 230 kW
HiLower caloric value of gas [kWh/m3]
Natural gas under normal conditions 15 °C 1013 mbar, EN 676
9.45 kWh/m3
ηBoiler eciency (e. g. 90%) 0.9
f Conversion factor (pressure and temperature compensation) -
tGas Gas temperature at gas meter [°C] 15 °C
PBaro Barometric air pressure [mbar] 945 mbar
PGas Pressure of gas at the gas meter [mbar] 20 mbar
VOperating volume [m3/h] -
VG Gas ow measured at the gas meter [m3] 0.75 m3
TMeasuring time for consumed gas quantity [s] 90 s
VN=
Q
VN =
230 kW
=27.0 m3/h
η · Hi0.9 · 9.45 kW/m3
Calculate standard volume using the following formula:
f=
273
x
PBaro + PGas
f=
273
·
945 + 20
= 0.90
273 + tGas 1013 273 + 15 1013
Calculate conversion factor using the following formula:
V=VNV =
27.0 m3/h = 30.0 m3/h
f0.90
Calculate gas volume using the following formula:
V=
3600 · VGV =
3600 · 0.75 m3
= 30.0 m3/h
T90 sek
Determine operating volume with the following formula:
Gas quality kWh/Nm3MJ/Nm3
Natural gas G20 9.5 34.02
Natural gas G25 8.2 29.25
Caloric value of the gas
172 515 07-2
Height above
sea level [m]
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
PBaro [mbar] 1013 1001 989 977 966 954 943 932 921 910 899 888 877
Lower caloric value Hi at normal conditions 15 °C and 1013 mbar, EN 676.
For exact caloric value of the gas, contact the gas distributor.
Gas quality kWh/Nm3MJ/Nm3
Butan G30 32.25 116.09
Propan G31 24.44 88.00
Biogas 6.0 21.60
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Bentone BG 400-2 LME22 512 VPS UV 60Hz User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI