OTDELAY - Output Transfer Delay to Emergency
This option causes the IIS Inverter System to delay the transfer from normal operation (AC utility power) to emergency
operation (battery power) and vice versa. When power is lost, the IIS Inverter System will take 3 seconds (factory default)
to apply battery-supplied power to the emergency circuit. This is useful in some xture applications where sensing
controls need to detect the loss in utility power to default to full light output in emergency mode. The transfer delay is
factory set at 3 seconds but may be eld adjusted by an IIS Inverter Technician to 1-8 seconds.
Available on IIS Single Phase, IISC, IIS3P, and IISCN3P models.
PM(A or B)REG(#) - Five-Year Preventative Maintenance Plan
Ensure your IIS Inverter System operates at peak performance through its operating lifespan with regular preventative
maintenance performed by a qualied IIS Inverter Technician. IOTA’s network of factory serviced technicians and factory
trained and authorized service centers will travel to the job site to perform critical maintenance tasks on your IIS Inverter
System on an annual (option PMA5REG#) or bi-annual (option PMB5REG#) basis. See iotaengineering.com for more
details on what is included in the IIS Central Inverter preventative maintenance plan. Available in the continental U.S.
only. Requires factory startup (see FSREG#) to be ordered.
Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IISM, IIS3P and IIS3P EXT models.
RAP - Remote Summary Alarm Panel
Provides a box (4" x 4" x 2 ¼") containing a red alarm light and an audible alarm
with a silence switch that will activate on any alarm condition. See individual
product user manuals for alarm details. The Remote Summary Alarm Panel
may be installed up to 1000 feet from the Inverter.
Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IISM, IIS3P, IIS3P EXT, and IISCN3P models.
RMP - Remote Meter Panel
Outts the IIS Inverter System with an additional detached
panel and keypad that provides greater exibility in monitoring
and programming the system from a remote location (up to
150 feet away from the inverter). This option allows users to
remotely view status, alarm, and test data about the IIS Inverter
System and remotely program system and test parameters.
Standard Remote Meter Panel mounting distance is 100 feet
but it may be extended up to 150 feet from the IIS Inverter. The
Remote Meter Panel is an addition to the standard display panel
attached to the Inverter cabinet.
Available on IIS Single Phase, IISM, IIS3P, and IISCN3P models.
RS232 - RS232 Serial Port
This option equips IISM models with an RS232 Diagnostic Interface
designed to remotely monitor system parameters, events, and
automatic test data. The user can use the RS232 interface to command
the system to perform a life safety test and review all system, event and
test parameters. Access is provided via a DB9 connector and transmits
at a 9600 baud rate. Note: an RS232 port may be oered as standard
on other models; consult specication sheets.
Available on IISM models.
O
R
P
RS-232 Serial Port
(on IIS Inverter) DB9 Connector
(provided)
ENTER ESCAPE
Remote Meter
Panel
150 feet (max)
Standard Panel
(included, shown on
IIS Single Phase model)
Remote Summary
Alarm Panel