Trane CO2 Sensing Kit User manual

Type
User manual

Trane CO2 Sensing Kit helps improve indoor air quality by monitoring and controlling carbon dioxide levels. Ideal for use in commercial buildings, schools, and other large spaces, the kit includes a wall-mount or duct-mount CO2 sensor that communicates with the Symbio™ 700 controls to adjust fresh air intake. Installation is simple, with clear instructions and mounting hardware included. The kit also features a "CO2 Kit Has Been Installed" label for easy identification.

Trane CO2 Sensing Kit helps improve indoor air quality by monitoring and controlling carbon dioxide levels. Ideal for use in commercial buildings, schools, and other large spaces, the kit includes a wall-mount or duct-mount CO2 sensor that communicates with the Symbio™ 700 controls to adjust fresh air intake. Installation is simple, with clear instructions and mounting hardware included. The kit also features a "CO2 Kit Has Been Installed" label for easy identification.

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation,
starting up, and servicing of heating, ventilating, and air-conditioning equipment
can be hazardous and requires specific knowledge and training. Improperly
installed, adjusted or altered equipment by an unqualified person could result in
death or serious injury. When working on the equipment, observe all precautions
in the literature and on the tags, stickers, and labels that are attached to the
equipment.
132
4 5 6
©2022
Installation Instructions
CO2 Sensing Kit
6 to 25 Ton Packaged Units with Symbio™ 700
Controls
Model Number: Used With:
FIACO2K001* Precedent™ with wall mount sensor
FIACO2K002** Precedent™ with duct mount CO2 sensor
Warnings, Cautions, and Notices
Read this manual thoroughly before operating or servicing this unit. Safety
advisories appear throughout this manual as required. Your personal safety and
the proper operation of this machine depend upon the strict observance of these
precautions.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect the
ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs)
and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all
refrigerants containing these compounds have the same potential impact to the
environment. Trane advocates the responsible handling of all refrigerants-
including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the USA,
the Federal Clean Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the equipment
that is used in these service procedures. In addition, some states or
municipalities may have additional requirements that must also be adhered to for
responsible management of refrigerants. Know the applicable laws and follow
them.
The three types of advisories are defined as follows:
WARNING Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
CAUTION Indicates a potentially hazardous situation which, if
not avoided, could result in minor or moderate injury.
It could also be used to alert against unsafe practices.
NOTICE Indicates a situation that could result in equipment or
property-damage only accidents.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring
MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE
required for the work being undertaken (Examples; cut resistant
gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing). ALWAYS refer to
appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of
Classification and Labeling of Chemicals) guidelines for information on
allowable personal exposure levels, proper respiratory protection and
handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians
MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-
specific requirements for arc flash protection, PRIOR to servicing the unit.
NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH
CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE
PROPERLY RATED FOR INTENDED VOLTAGE.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes to
its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective
owners.
General
Note: An economizer must be installed and functional before attempting to install
a CO2 sensing kit.
These sensors detect and control the carbon dioxide level in the conditioned
space by measuring CO2 concentration, comparing it with a user-adjustable set
point and sending a corresponding control signal to the economizer module.
This causes the economizer damper to be positioned so that sufficient fresh air
is introduced into the conditioned space to reduce and maintain the CO2
concentration to a minimum level as selected by the user.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Trane personnel must follow the company’s Environmental, Health and
Safety (EHS) policies when performing work such as hot work, electrical, fall
protection, lockout/tagout, refrigerant handling, etc. Where local
regulations are more stringent than these policies, those regulations
supersede these policies.
Non-Trane personnel should always follow local regulations.
Inspection
1. Unpack all components of the kit.
2. Check carefully for shipping damage. If any damage is found, report it
immediately, and file a claim against the transportation company.
3. Visually inspect the components for shipping damage as soon as possible
after delivery, before it is stored. Concealed damage must be reported within
15 days.
4. If concealed damage is discovered, stop unpacking the shipment.
5. Do not remove damaged material from the receiving location. Take photos of
the damage, if possible. The owner must provide reasonable evidence that
the damage did not occur after delivery.
6. Notify the carrier’s terminal of damage immediately by phone and by mail.
Request an immediate joint inspection of the damage by the carrier and the
consignee.
Note: Do not attempt to repair any damaged parts until the parts are inspected
by the carrier’s representative.
Parts List
CO2 Sensor:
FIACO2K001*
One (1) CO2 Demand-Controlled Ventilation Wall-Sensor (4190 4100) with
instructions and mounting hardware.
FIACO2K002*
•One (1) CO
2 Demand-Controlled Ventilation Duct -Sensor (4190 4101) with
instructions and mounting hardware.
One (1) “CO2 Kit Has Been Installed” Label
Installation
1. Apply provided CO2 and ventilation override wiring diagram label next to the
main unit wiring diagram label, located on compressor access panel.
2. Apply “CO2 kit Has Been Installed” label next to the main unit wiring diagram
label.
3. Install CO2 sensor in conditioned space or return air duct according to
instructions packed with the sensor.
4. Make field wiring connections to Symbio™ 700 UC J22 pins 1-3. Refer to main
unit schematic sheet 3 and in this guide.
5. Route low voltage external field wiring along with and secure to existing low
voltage zone sensor or thermostat wiring.
6. Replace any access panels removed for kit installation.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all
motor start/run capacitors before servicing. Follow proper lockout/ tagout
procedures to ensure the power cannot be inadvertently energized. Verify with a
CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
CO2 Sensor Operation for Symbio™ 700 with Economizer
Demand Control Ventilation (DCV)
DCV eliminates over-ventilating the space by allowing the fresh air damper to close further than non-CO2 sensing systems, which reduces power consumption. DCV
adjusts the fresh air damper between a DCV Minimum Position and Design Minimum Position. DCV Minimum Position equals non-CO2 sensing systems minimum
damper position - 10%, or more, down to 0% open.
When the CO2 level is greater than or equal to the DCV Minimum CO2 setpoint the supply fan is energized and the fresh air damper modulates between the DCV
Minimum Position Setpoint and the Design Minimum Setpoint, increasing the amount of outdoor air flow and reducing the CO2 level in the space. The damper will only
open up to the Design Minimum Position Setpoint. If the CO2 level drops below the DCV Minimum CO2 Setpoint - 50ppm the fresh air damper will drive to the DCV
Minimum Position. If CO2 level rises above the Building CO2 setpoint the fresh air damper will open to the Design Minimum Position setpoint.
DCV Setup, Damper Position and CO2 Setpoint
Before beginning, turn the fan ON and conduct the Minimum Position Setpoint procedure used WITHOUT CO2 to obtain and record visually the Minimum Position Setpoint
setting and/or the corresponding DC voltage settings for the min and max required to meet ASHRAE standards.
August 2022 ACC-SVN248A-EN
7
©2022
Trane and American Standard have a policy of continuous product and product data improvement and reserve the
right to change design and specifications without notice. We are committed to using environmentally conscious print
practices.
Trane and American Standard create comfortable, energy efficient indoor environments for commercial
and residential applications. For more information, please visit trane.com or americanstandardair.com.
CONDUCTOR NAME CONDUCTOR BASE COLOR CONDUCTOR TRACER COLOR
1BLACK
2RED
3 BLUE
4 ORANGE
5 YELLOW
6BROWN
7 RED BLACK
8 BLUE BLACK
9 ORANGE BLACK
10 YELLOW BLACK
11 BROWN BLACK
12 BLACK RED
13 BLUE RED
14 ORANGE RED
15 YELLOW RED
16 BROWN RED
17 BLACK BLUE
18 RED BLUE
19 ORANGE BLUE
20 YELLOW BLUE
21 BROWN BLUE
22 BLACK ORANGE
23 RED ORANGE
24 BLUE ORANGE
25 YELLOW ORANGE
26 BROWN ORANGE
LEGEND
REF DES DESCRIPTION LINE NO
DAT SENSOR - DISCHARGE AIR 122
FOS SWITCH - FROSTAT 124
LPC1 SWITCH - LOW PRESSURE 1 156
OAS SENSOR - OUTDOOR AIR 122
UC MODULE - UNIT CONTROLLER 143
PPM19
PPM177
PPM150
J6
J7
BK
R
BK
BL
Y
BK
R
BL
O
Y
BR
R/BK
BL/BK
O/BK
Y/BK
BR/BK
BK/R
PPM116
J5
P4
P3
J3
OBL BK R BL O BK R BK R BL O
IMC-1
BK
R
BL
O
BK
R
BL
BL
R
BK
IMC-1
BK
R
BL
O
PPF150
PPM50
PPF132
PPM32
BK
BK
R
R
BL
BL
O
O
Y
Y
BR
BR
J14
J15
J21
PPF117
BK
BK
R
R
BL
BL
BK
BK
R
R
BL
BL
O
O
BK
BK
R
R
BL
BL
J4
J1
P6
PPF116
BK
BK
R
R
BL
BL
O
O
Y
Y
BR
BR
PPM117
BK
R
DAT
OAS
LPC1
FOS
SYMBIO 700
MODBUS +
MODBUS -
COMMON
COMMON
24 VAC OUT
IMC+
IMC-
24 VAC IN
COMMON
COMMON
COMMON
24 VAC OUT
24VAC OUT
PHASE MONITOR IN
CONTROL VOLTAGE IN
INDOOR FAN RUN
INDOOR FAN HI SPEED
24 VAC IN
COMMON
CONDENSER FAN1
COMMON
CONTROL 24 VAC IN
CONTROL 24 VAC OUT
CIRCUIT 1 PROVING IN
COMPRESSOR 1 24 VAC IN
COMPRESSOR 1 RUN
COMPRESSOR 1 UNLOADER/CCH
CONTROL VOLTAGE IN
CONTROL VOLTAGE OUT
CONTROL 2 PROVING IN
COMPRESSOR 2 24 VAC IN
COMPRESSOR 2 RUN
COMPRESSOR 2 UNLOADER/CCH
CONTROL 24 VAC IN
CONTROL 24 VAC OUT
CIRCUIT 3 PROVING IN
COMPRESSOR 3 24 VAC IN
COMPRESSOR 3 RUN
COMPRESSOR 3 UNLOADER/CCH
SOV1 OUT
COMMON
SOV2 OUT
COMMON
COMMON
ECM CONDENSER FAN CONTROL
DISCHARGE AIR TEMP
OUTDOOR AIRTEMP
COIL TEMP 1
COIL TEMP 2
COIL TEMP 3
CIRCUIT 1 DISABLE
CIRCUIT 2 DISABLE
CIRCUIT 3 DISABLE
DEMAND LIMIT/SHED
24 VAC OUT
24 VDC OUT
COMMON
SPACE HUMIDITY
COMMON
CO2 IN
24 VDC OUT
24 VAC OUT
LOCAL OCCUPANCY
24 VAC OUT
EMERGENCY STOP
ACNET IN+
ACNET IN-
ACNET OUT+
ACNET OUT-
ZONE TEMP
COMMON
COOLING SET POINT
UNIT MODE
HEATING SET POINT
COMMON
24 VAC OUT
24 VAC OUT
T-STAT Y1
T-STAT W1/0
T-STAT G/VAV CHANGEOVER
T-STAT W2
T-STAT Y2
T-STATX2
T-STAT PULLDOWN-T
T-STAT GND
24 VAC OUT
COMMON
IMC+
IMC-
24 VAC OUT
COMMON
IMC+
IMC-
24 VAC OUT
COMMON
IMC+
IMC-
CONTROL VOLTAGE IN
TRACER TU
ETHERNET
HOST PORT
CONDENSER FAN2
COMMON
CONDENSER FAN3
COMMON
ETH
USB-B
USB-A
P1
WHITE
P2
WHITE
P3
WHITE
P4
WHITE
J3
WHITE
J4
WHITE
J5
GREEN
J6
WHITE
P5
BLACK
P14
PINK
P15
LT BLUE
P15
PURPLE
P17
YELLOW
P18
GRAY
P19
RED
P20
BROWN
P21
GREEN
J16
GREEN
P6
WHITE
P7
BLACK
P8
RED
P9
WHITE
P10
BLUE
P11
WHITE
P12
BLACK
J17
GREEN
J18
GREEN
J19
GREEN
J20
GREEN
J21
GREEN
J22
GREEN
J23
GREEN
BK
BK
R
R
Y
Y
BR
BR
BL
BL
O
OEXPANSION MODULE
SHEET 4
AB-J18
MODBUS-1
SHEET 2
-H
THERMOSTAT CO2 SENSOR
OPTIONAL REMOTE SENSOR
ZONE SENSOR
TO LINE 72
(UC)
TO LINE 210 TO LINE 484
SHEET 9
XM30/XM32
TO LINE 49
SHEET 1
PPM72
TO LINE 250
SHEET 5
IOM-J5
TO LINE 72
SHEET 2
MODBUS-1
TO LINE 224
SHEET 4
AB-J17
SHEET 1
TO LINE 49
PPM72
TO LINE 224
SHEET 4
AB-J17
TO LINE 224
SHEET 4
AB-J17
TO LINE 224
SHEET 4
AB-J17
BUILDING
AUTOMATION
SYSTEM
OPTIONAL LCI
MODULE
TO SHUT DOWN UNIT FOR EMERGENCY STOP, CONNECT FIELD SUPPLIED CONTROL
DEVICE ACROSS PINS 1 & 2. UNIT STOPS WHEN SWITCH CLOSES.
DISCHARGE AIR TEMPERATURE SENSOR (DAT)
STANDARD ON UNITS WITH SZVAV & MZVAV.
EXTENSION HARNESS NOT PRESENT ON 15-25T UNITS.
1
2
1
2
J19
1
2
1
2
1234123 123
1
2
PPF19
1
2
123456
123456
12
PPF32
12
PPF77
12
12
PPF50
12
1
2
1
2
3
4
5
6
J8
1
2
3
4
5
6
J9
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
12341212341234
1
2
3
4
1
2
3
4
PPM77
12
PPF177
1212
12
PPM132
12
12
12
123 123123456789121234567121234
1234
1234567
123456789 123
1234567
1
2
31
3
2
123 1234 1234 1234 1234 12 12 123 1234
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
1
2
1234 12 1234567 12 123456789 123 123
J22 Connector
ACC-SVN248A-EN 29 Aug 2022
(NEW)
  • Page 1 1
  • Page 2 2

Trane CO2 Sensing Kit User manual

Type
User manual

Trane CO2 Sensing Kit helps improve indoor air quality by monitoring and controlling carbon dioxide levels. Ideal for use in commercial buildings, schools, and other large spaces, the kit includes a wall-mount or duct-mount CO2 sensor that communicates with the Symbio™ 700 controls to adjust fresh air intake. Installation is simple, with clear instructions and mounting hardware included. The kit also features a "CO2 Kit Has Been Installed" label for easy identification.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI