IMI TA MC15-230 User manual

Type
User manual

IMI TA MC15-230 is an electrical linear actuator compatible with BR216MZ and BR316MZ two-way/ three-way valves. It's suitable for three-point and two-point controllers in zone post-treatment devices for heating, ventilation, and air conditioning systems. The device offers precise positioning with a stroke range of 9mm and a positioning time of 22s/mm, driven by a motor with a nominal power consumption of 2.8VA. It features manual adjustment with a socket for a 4mm hexagon key, simplifying maintenance.

IMI TA MC15-230 is an electrical linear actuator compatible with BR216MZ and BR316MZ two-way/ three-way valves. It's suitable for three-point and two-point controllers in zone post-treatment devices for heating, ventilation, and air conditioning systems. The device offers precise positioning with a stroke range of 9mm and a positioning time of 22s/mm, driven by a motor with a nominal power consumption of 2.8VA. It features manual adjustment with a socket for a 4mm hexagon key, simplifying maintenance.

IMI Hydronic Engineering International SA
Lake Geneva Business Park
Route de Crassier 19
CH 1262 Eysins
Operating manual 3.09-TA.025-01-EN
MC15/230
Issue 2021-11-30
Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen
voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Zmeny vyhradené - Změny vyhrazeny - Zmiany zastrzeżone - Возможны
изменения - A változtatások jogát fenntartjuk - ؍⮉ᵚ㓿䙊⸕㘼᭩ࣘⲴᵳ࣋
Product Description
MC15/230 Electrical Linear Actuator
for BR216MZ and BR316MZ two-way/three-way valves
Application
Electrical linear actuator for 3-point and 2-point controllers in zone
post-treatment devices for heating, ventilation and air conditioning
systems.
Content Page
Important Information on Product Safety ...............................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Dimensions..........................................................................................................................................................4
Connection...........................................................................................................................................................4
Valve Installation..................................................................................................................................................5
Mounting and commissioning the linear actuator ................................................................................................6
Removing the linear actuator...............................................................................................................................8
Manual adjustment ..............................................................................................................................................9
Initialization and adjustment to the valve stroke ................................................................................................10
Page 2 / 10
Product DescriptionMC15/230
Operating manual 3.09-TA.025-01-EN Issue 2021-11-30
Important Information on Product Safety
Safety instructions
This document contains information on installing and commissioning the product “MC15/230”. Each
person who carries out work on this product must have read and understood this document. If you
have any questions that are not resolved by this document, you can obtain further information from
the supplier or manufacturer.
If the product is not used in accordance with this document, the protection provided could be
impaired.
The applicable regulations must be observed when installing and using the devices. Within the EU,
these include regulations regarding occupational safety and accident prevention as well as those
from the VDE (German Association for Electrical, Electronic & Information Technologies). If the
device is used outside of the EU, it is the responsibility of the plant engineer or operator to comply
with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers based on their technical training, knowledge
and experience, as well as their knowledge of the applicable regulations.
Symbol meanings
WARNING
Indicates a hazard of medium risk which can result in death or serious bodily injury if not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if not avoided.
!CAUTION
Indicates a hazard which can result in material damage or malfunctions if not avoided.
NOTE
Indicates additional information that can simplify working with the product.
Notes on disposal
In accordance with the applicable laws and directives of the European Union countries, the product
should not be disposed of with household waste. This ensures environmental protection and
sustainable recycling or raw materials.
Commercial users should contact their supplier and observe the conditions of the purchase
agreement. This device may not be disposed of together with other commercial waste.
The local and currently applicable laws must be observed.
Page 3 / 10
Operating manual 3.09-TA.025-01-EN
MC15/230Product Description
Issue 2021-11-30
Item
Technical Data
MC15/230 Electrical linear actuator for BR216MZ and BR316MZ two-way/
three-way valves
Nominal voltage AC 230 V ±10%; 50/60 Hz
Power consumption Dimensioning: 4.4 VA
Nominal: 2.8 VA
Switch-on current Max. 10 A for a short time
Control Three-point signal (open/stop/close) or two-point signal (open/close)
Connection Built-in cable: 1.5 m, 3 x 0.75 mm2
Motor switch-off Actuator spindle: extending = load-dependent, retracting = load-dependent
Actuating noise <28 dB
Positioning stroke 9 mm max.
Positioning time 22 s/mm
Positioning force 150 N (nominal)
Position indicator Stroke range scale
Manual adjustment Only when disconnected from the power supply
Socket for hexagon key on the actuator cover,
Key socket 4 mm
Permissible medium
temperature in the valve
0..120 °C
Ambient temperature 0..50°C
Ambient humidity During operation: 0..85% r.h., non-condensing
Out of operation: 0..85% r.h., non-condensing
Overvoltage category III
Level of contamination 2
Degree of protection IP40
Protection class II in accordance with EN 60730
Installation position Anywhere from vertical to horizontal
Maintenance Maintenance-free
Weight 242 g
Page 4 / 10
Product DescriptionMC15/230
Operating manual 3.09-TA.025-01-EN Issue 2021-11-30
Dimensions
Connection
!CAUTION
You require a 1 A pre-fuse to operate the electrical linear actuator.
!CAUTION
Peak loads of up to 10 A may occur when switching on the actuator. Ensure suitability of switching
components (e.g. controller connection) to ensure proper functioning and to avoid malfunctions and
damage.
NOTE
The actuation direction can be changed by switching the supply lines to terminals 2 and 3 on the
actuator.
M30x1,5 DIN 13
86,5
80
60
51
48,5
- Three-point control - Two-point control
GY
230 V AC
BU BN
0 V AC
M
123
MC15/230
M
123
GY
230 V AC
BU BN
0 V AC
MC15/230-HR
Page 5 / 10
Operating manual 3.09-TA.025-01-EN
MC15/230Product Description
Issue 2021-11-30
Valve Installation
The pipeline system and the interior of the fitting must be free of foreign objects. In the event of
contaminated media, dirt collectors are to be inserted upstream of the valves with fine screens,
mesh width 0.25 mm.
There must be no tension between the valve and the pipeline connection.
To avoid eddy formations in the valve body, the valve should be installed in a straight section of
the pipe. A distance of 10 times the nominal diameter is recommended between the valve flange
and manifold or other similar parts.
The installation location is to be selected so that the ambient temperature at the linear actuator is
kept between 0 °C and +50°C.
When carrying out installation, the permissible maximum pressure difference p and the specified
direction of flow must be observed.
The three-way valves are to be used as mixing valves. Observe the specified direction of flow.
Once the valve is installed, make sure the ball in the valve seating can be moved easily by pushing
in the valve stem.
For safety reasons, do not suspend the linear actuators from under the valve.
Observe the direction of flow arrow on the valve body. Inverting the direction of flow impairs control
behavior.
M
M
M
Page 6 / 10
Product DescriptionMC15/230
Operating manual 3.09-TA.025-01-EN Issue 2021-11-30
Mounting and commissioning the linear actuator
WARNING
Contact with live parts of electrical domestic installation can cause death due to electric shock.
Mounting/removal may only be carried out when power is switched off.
CAUTION
Installation and commissioning work may only be carried out by qualified technicians.
If the valve is installed in the system, make sure that no differential pressure builds up in the valve
body before beginning work. If necessary, close the gate valve and turn off pumps. After the pipeline
has cooled off, the actuator can be installed.
Be sure to comply with VDE guidelines and local wiring regulations. The device is connected
according to the legally binding system circuit diagram.
!CAUTION
Do not operate the MC15/230 Small Actuator electrically without a valve.

1 2 3 4
Page 7 / 10
Operating manual 3.09-TA.025-01-EN
MC15/230Product Description
Issue 2021-11-30
Place the linear actuator on the threaded connection of the valve and tighten hand-tight using the
union nut.
Establish the electrical connection.
When the power supply is switched on for the first time, an automatic initialization run takes place.
The actuator first travels to the upper end position and then to the lower end position. The valve
is then adapted.
The linear actuator does not respond to the control signal until the initialization run is complete.
After mounting and commissioning work is complete, the automatic coupling must be protected
with the dust cover (see Fig. 8).
!CAUTION
After recommissioning or a manual adjustment, an initialization run must be triggered manually. This
is done by flipping the DIP switch before switching on the power supply (see Fig. 6).
1 2 3
5 6
Klick
7
180°
8
Page 8 / 10
Product DescriptionMC15/230
Operating manual 3.09-TA.025-01-EN Issue 2021-11-30
Removing the linear actuator
CAUTION
Before beginning to remove the unit, make sure that no differential pressure builds up in the valve
body before beginning work. If necessary, close the gate valve and turn off pumps.
After the pipeline has cooled off, you can begin removing the linear actuator.
!CAUTION
Before beginning to remove the unit, put the actuator in the middle position.
Move the linear actuator to the center position using a control signal.
Disconnect the linear actuator from the mains power supply. Then disconnect all electrical
connections.
Loosen the union nut.
Turn the dust cover far enough so that you can press the safety button.
Press the safety button on the automatic coupling all the way in and hold it (see Fig. 6).
Remove the linear actuator from the valve.
50%
1 2 3 4
180°
5 6 7
Page 9 / 10
Operating manual 3.09-TA.025-01-EN
MC15/230Product Description
Issue 2021-11-30
Manual adjustment
!CAUTION
Manual adjustment may only be performed when the actuator is installed.
The linear actuator must be disconnected from the mains power supply
for manual operation.
A hexagon key (key socket 4 mm) can be used to move the actuator
into any position.
!CAUTION
If you manually adjust until the slip clutch responds, turn the hexagon key half a turn in the opposite
direction after the manually set stroke position has been reached.
NOTE
An initialization run must be performed after a manual adjustment, see Reinitialization section on p.10
Page 10 / 10
Product DescriptionMC15/230
Operating manual 3.09-TA.025-01-EN Issue 2021-11-30
Initialization and adjustment to the valve stroke
WARNING
Contact with live components of the building’s electrical system can cause death due to electric
shock.
The actuator must be disconnected from the power supply before you remove the terminal cover and
flip the switch.
Reinitialization
The valve stroke must be reinitialized whenever the unit is remounted
or adjusted manually.
Disconnect the linear actuator from the power supply and remove
the terminal cover.
Change the switch setting (1).
Reattach the terminal cover and reconnect the power supply.
The linear actuator performs an initialization run.
NOTE
A valve stroke initialization is also performed when a valve end position is reached during normal
operation.
1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

IMI TA MC15-230 User manual

Type
User manual

IMI TA MC15-230 is an electrical linear actuator compatible with BR216MZ and BR316MZ two-way/ three-way valves. It's suitable for three-point and two-point controllers in zone post-treatment devices for heating, ventilation, and air conditioning systems. The device offers precise positioning with a stroke range of 9mm and a positioning time of 22s/mm, driven by a motor with a nominal power consumption of 2.8VA. It features manual adjustment with a socket for a 4mm hexagon key, simplifying maintenance.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI