Heating Cable Installation
This section provides instructions for installing
the heating cables in pavement or slabs. Read
and follow these instructions to ensure that the
ElectroMelt system performs reliably and as
intended.
3.1 Protect the Heating Cable
On many projects there is a delay between
installation of the heating cable and placement
of the concrete. If there is any delay at all,
take the following precautions to protect the
installation until concrete can be poured:
• Prevent traffic from crossing the area where
the heating cable is installed.
• Install temporary end seals such as vinyl
electrical tape, heat shrink tubing, or other
suitable materials on all exposed heating cable
ends to prevent water entry. All temporary end
seals must be removed before installation.
• Mechanically protect the heating cable so that it
cannot be damaged by being walked on, run over,
painted, sandblasted, welded, cut, or otherwise
cut, abraded, burned, or contaminated.
3.2 Heating Cable Installation
1. Locate Structural Features
Elevate the reinforcement from the ground,
measure and mark the designed heating
cable spacing on the reinforcement and
mark the location of all pavement joints. The
reinforcement should be elevated from the
ground so that the heating cable attached to
it will be 1 1/2 to 2 inches (4to 6 cm) from the
surface of the finished concrete. For paver
applications, concrete should be 2 inches (6
cm) thick to allow 1 1/2 inches (4cm) between
heating cable and surface of concrete. Note
the planned location of structures such as
flagpoles, rail posts, benches or parking meters.
These are typically installed after concrete
cures and their installation requires cutting