FläktGroup ILOX 86PLUS Installation and Maintenance Manual

Category
Split-system air conditioners
Type
Installation and Maintenance Manual
OPERATION, INSTALLATION AND MAINTENANCE MANUAL
AIR HANDLING UNIT
ILOX 86PLUS
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
2
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
Thank you for purchasing the ILOXair air handling unit. We have been
developing our products over the years with the aim of making them more
user-friendly. This user guide has also been written with this in mind. However,
if you feel that an aspect of the guide or the product needs to be improved, we
would be glad to hear from you. Our contact information can be found on web-
site
www.flaktgroup.com
.
More useful information and help, such as the following, is available on our
website
www.flaktgroup.com
:
Instructions and guides
Service call. Please have access to the unit’s product label (location on the
control box)
Ordering original filters
SAFETY
We recommend that you follow these instructions strictly. This way
you will ensure reliable operation of your equipment for many years to
come.
WARNINGS AND NOTES
This manual contains clearly marked warnings which are intended for
your personal safety.
CONTENT
Safety ................................................................................................................................... 2
OPERATION & MAINTENANCE (FOR THE USER)
Main components ........................................................................................................... 3
Electrical data, Control equipment .......................................................................... 4
Basic operation ...............................................................................................................5
Plus Touch panel.............................................................................................................5
Temperature control ......................................................................................................6
Additional control equipment .....................................................................................6
Maintenance ..................................................................................................................... 7
Condensation, water inside the unit .......................................................................8
Overheating protection, Temperature alarms, other alarms ........................8
Maintenance schedule, Fan speed settings .......................................................9
INSTALLATION (FOR INSTALLER AND SERVICE PERSONNEL)
Dimensions and weight .............................................................................................10
Duct connection, Insulation of the ducts .............................................................11
Installation options and duct definitions ..............................................................11
Mounting example ........................................................................................................12
Site of installation .........................................................................................................12
Installing the condensate removal pipe .............................................................. 12
Mounting option, wall ..................................................................................................13
Mounting option, ceiling .............................................................................................13
Electrical installation ................................................................................................... 14
External connection box ............................................................................................ 14
Internal connections .................................................................................................... 14
Connection diagrams .................................................................................................. 15
Cable entry ......................................................................................................................16
Physical connections for external control ..........................................................16
CO
2
Control ...................................................................................................................... 16
Humidity Control ............................................................................................................ 16
Emergency stop ............................................................................................................16
Set-up menus - only for installer ...........................................................................17
Removing the unit from the ceiling .......................................................................19
Declaration of conformity ......................................................................................... 20
Warning! Indicates the presence of a hazard which could
result in personal injury.
!
Note! Alerts the reader of important facts and conditions.
Warning! The device can be used by children from 8 years upwards and people (including children) with reduced
physical, sensory or mental capa bilities, or lack of experience and knowledge if they have received guidance or
information on how to use the device safely and understand the risks that can occur. Children should not play
with the appliance. Cleaning and maintenance is not carried out by children without supervision.
!
Warning! Installation, adjustment and commissioning that is described in this manual must be carried out by
competent, authorised personnel.
!
Warning! Use protective gloves during installation, service and maintanance.
!
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
3
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
HEAT EXCHANGER
The unit has a counterflow heat exchanger made of aluminium and
it has a temperature efficiency of up to 80%. An automatic defrosting
function, Termo ice is standard.
Air flow, l/s 20 30 40 50 60
Temperature efficiency,% 77.2 77.2 77.2 77.3 77.4
The table above shows the unit temperature efficiency in % at a given
air flow according to EN 308 conditions.
POST HEATER, ELECTRICAL
The 1.2 kW electrical post heater is used to heat the supply air tem-
perature when the counter flow heat exchanger is not able to recover
enough energy. It is also used when the defrosting function Termo ice
is active.
FILTERS
The unit is fitted with a ISO Coarse pre-filter and a ISO ePM1 55% filter
on the supply side and a ISO Coarse filter on the extract side.
PACKAGING
The unit is delivered in a cardboard box with styrofoam padding. Re-
cycle the cardboard to the carton waste and the padding material to
plastic or energy waste. The printed material in the package can be
recycled to the paper waste.
All of the printed material can be downloaded from our website
www.flaktgroup.com
.
OPERATION & MAINTENANCE (FOR THE
USER)
MAIN COMPONENTS, LEFT HAND VERSION
CASING
The outer and inner casing are made of white coated galvanised steel
(RAL9016) with an intermediate layer of 20 mm polyester fiber insula-
tion. Corrosion class C3 and leakage class A1 external, A2 internal (EN
13141-7).
FANS
The fans are driven by independently controllable energy-efficient EC
motors with stepless speed control.
MAIN COMPONENTS
1. Counterflow heat exchanger
2. Extract air fan (behind the heat exchanger)
3. Supply air fan (behind the heat exchanger)
4. Post heater (behind the heat exchanger)
5. Control equipment
6. Supply air prefilter, (G3) ISO Coarse
7. Supply air fine filter, (F7) ISO ePM1 55%
8. Extract air filter, (G3) ISO Coarse
9. Power switch
10. By-pass damper (automatic)
11. Reset button, thermal overload for electrical post heater
Condensate drainage, see under Dimensions and weight.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
4
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
ELECTRICAL DATA
Voltage: 230V, 1 phase 50 Hz.
Postheater Electrical heater
Fan Power (w)
2 x 117
Post heater (w)
1200
Total Power (W)
1460
Current (A)
6.3
ELECTRICAL DATA, CONTROL EQUIPMENT
TERMO ICE – AUTOMATIC DEFROSTING
The Termo Ice function ensures an optimal annual efficiency and a
better indoor climate. The unit uses temperature sensors to detect if
there is frost forming in the heat exchanger and starts defrosting on
demand.
When Termo ice is activated the by-pass damper opens and the
outdoor air is directed directly to the post heater by-passing the heat
exchanger. The supply air fan stays in operation during defrosting. The
warm extract air defrosts the heat exchanger.
COOLING RECOVERY
During summertime, if the extract air is cooler than the outdoor air, the
by-pass damper will close. The heat exchanger then recovers cooling
from the extract air. This primarily applies if there is some form of
cooling device in the house. When the extract air is warmer than the
outdoor air the by-pass damper will again be opened.
HUMIDITY
Optional humidity sensor for extract air. The unit can be controlled to
maintain the humidity below certain level via the Plus Touch panel.
CO2
Optional carbon dioxide sensor for extract air. The unit can be control-
led to maintain the carbon dioxide level below a certain level via the
Plus Touch panel.
MODBUS RTU
The unit has a Modbus RTU interface as standard. The unit can be con-
trolled via the Modbus in terface.
ALARMS
The unit has built-in alarms for filter change and sensor errors.
SEC CLASS
SEC class A+ is fulfilled in a cold climate zone
(Nordic countries). Units configured for demand
control CO
2
will achieve SEC class A in an average
climate zone (Central Europe). ECO design directive 1254/2014.
CONTROL EQUIPMENT
The unit is equipped with an electronic control system, Plus control-
ler. The Plus controller handles fan speeds, the by-pass damper and
electrical post heater. The air handling unit is supplied with a 1.25 me-
ter cable and a plug in connector for the main supply. Control connec-
tions are made in the connection box outside the unit. The connection
box has connectors for Modbus connections, cooker hoods, Mosaik
switch and Plus Touch control panel. Any additional sensors are con-
nected directly to the PCB in the control box.
FAN CONTROL
Depending on the controller used, up to four operating modes can be
selected (see accessories):
AWAY is used when nobody is at home for a longer period e.g. vaca-
tion.
NORMAL is used for normal ventilation air flow.
BOOST is used when there is a need for a higher ventilation air flow (it
will automatically revert after 60 minutes).
MAXIMUM generates full fan speed.
The fan speeds can be adjusted independently of each other on every
operating mode.
TEMPERATURE CONTROL
The Plus controller controls the by-pass damper and the electrical post
heater to maintain the supply air temperature at set point. The electri-
cal post heater is activated when the energy recovery from the heat
exchanger is insufficient.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
5
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
Fan speed:
1/4 for Away
2/4 for Home
3/4 for Boost
4/4 for Maximum
Active alarms Active function
Menu
Automatic operation
Away
Boost
ON/OFF
The Plus Touch panel basic view.
BASIC OPERATION
The basic functions of the air handling unit can be controlled from the
following:
Plus Touch Panel Cooker hood Mosaik
MOSAIK CONTROL
Mosaik is standard light switch sized controller with three operating
modes. The right switch controls whether the unit is in away mode or
normal operation and the left switch controls home or boost operating
mode when right switch is in normal mode.
COOKER HOOD CONTROL
The air handling unit’s operating modes can be controlled with a coo-
ker hood. Compatible Iloxair cooker hoods can also indicate and reset
the unit’s alarms. For more detailed information please read the cooker
hood manual. Using Iloxair cooker hoods is strongly recommended for
ensuring the compability.
PLUS TOUCH PANEL
Home
Boost
Home
Away
OFF
Boost
Away
Automatic
Home
PLUS TOUCH PANEL
With the Plus Touch panel it is possible to change for example fan
speeds, temperature set point, date and time.
TEMPERATURE SET POINT
It is possible to change the temperature set point and to read the tem-
perature of the different temperature sensors via the Plus Touch panel.
The temperature sensors are located inside the unit. This means that
they do not precisely reflect the actual outdoor or indoor air tempera-
tures.
WEEKLY SCHEDULES
The unit can be set to operate according to user-defined weekly sche-
dules. A setup wizard guides you through the basic set-up. It is pos-
sible to edit the schedule for each day afterwards.
ALARMS
The Plus Touch panel shows alarms for example filter change and
sensor errors. For more information regarding alarms see separate
parts in this document.
FAN OPERATING MODES
All four operating modes can be selected via the Plus Touch panel:
Away is used when nobody is at home for a longer period e.g.
vacation.
Home is used for normal ventilation air flow.
Boost, there are several variants:
Boost is used when there is a need for a higher ventilation air flow.
Boost 60 minutes sets the unit into BOOST mode for 60 minutes.
Fireplace timer 15 minutes is used when the user wants to light a fire.
Maximum generates full fan speed.
Note! If a separate Away/Normal control switch is used, the switch
must be in the normal position to allow changes via the touch panel.
Home
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
6
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
ADDITIONAL CONTROL EQUIPMENT
HOME/AWAY SWITCH
The Home/Away switch allows you to reduce
the ventilation rate. To enable control from an
Plus touch panel or other additional control
equipment connected to the unit, the switch
must be in the Home position.
FIREPLACE OR BOOST SWITCH
The switch may be used either as a fireplace
switch or a regular boost switch. When used as
a fireplace switch it changes the pressure con-
ditions in order to make it easier to light a fire.
When in use, the fireplace switch overrides any
other switches.
CO2 SWITCH
The CO
2
switch measures the carbon dioxide
level in the room and boosts ventilation if the
set point level is exceeded. When the CO
2
level
drops below the set point the fans return to their
previous speed.
HUMIDITY SWITCH
The humidity switch boosts ventilation when
the relative humidity in the room exceeds the
set point. During the cold season, the set point
should be set to approximately 50%. During the
warm season, the set point should be higher,
approximately 70%. If the set point is correct
then the humidity switch boosts the ventilation
when using the shower or sauna. The normal ventilation rate is resu-
med after approximately 1–2 hours. During certain conditions the humi-
dity level may be so high that unit will stay in boost mode. In order to
prevent this raise the humidity set point.
3-SPEED OR 4-SPEED SWITCH
Easy to use switch for choosing between
three or four different operating modes.
TEMPERATURE CONTROL, ELECTRICAL HEATER
Temperature set point.
The supply air temperature set point is adjustable via the knob on the
front edge of the electrical box inside the unit. The temperature set
point can be adjusted between 12 and 26°C, recommended set points
being between 17°C and 20°C. It is also possible to set the tempe-
rature set point via the Plus touch panel (accessory). The electrical
post heater will not be activated unless the outdoor air temperature is
below the post heater activation temperature default being 8°C. Please
note that the temperature set point is not be mistaken to be the gene-
ral indoor temperature. The general indoor temperature is to be hand-
led by the heating system.
TEMPERATURE CONTROL
During cold periods the by-pass damper closes and the cold outdoor
air is led through the counter flow heat exchanger (winter mode). The
supply air will then be heated from the warm extract air. If the outdoor
air is cold and the heat energy recovered from the extract air is not
enough to achieve the supply air temperature set point the post heater
will activate in order to maintain the supply air temperature. During
warm periods when the heat recovery from the extract air is not
needed the by-pass damper opens and the outdoor air is led past the
heat exchanger directly into the supply air fan (summer mode).
Summer mode Winter mode
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
7
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
MAINTENANCE
GENERAL
Filters, fans and the counter flow heat exchanger are very important
for the function and economy of the unit. It is therefore important that
these are kept clean and in good condition. We recommend a general
check of these parts during filter replacement, every 6 months. For sa-
fety reasons, general caution should be observed during maintenance
of the unit. It is recommended to use protective gloves.
FILTER ALARM AND REPLACEMENT OF FILTERS
The filters for the extract and supply air should normally be replaced
twice a year. In areas where there is a lot of airborne particles such as
in cities it may be necessary to change the filters more often. The Plus
controller is set to remind the user to change the filter every 6 months.
It is possible to change the interval when using Plus touch panel.
Follow the instructions below to change the filters:
1. Open the hatch door.
2. Disconnect the power by using the power switch on the electrical
box.
3. Remove the used supply air filters (ISO Coarse pre-filter and ISO
ePM1 55% filter) from the console.
4. Remove the used extract air ISO Coarse filter.
5. Insert the new supply air filters (ISO Coarse pre-filter and ISO ePM1
55% filter) and extract air filter (ISO Coarse filter).
6. Turn on the power switch and close the hatch door.
7. (If equipped with accessory Plus Touch panel, reset the filter alarm.)
Warning! When replacing dirty filters, use of a face mask is
recommended (lowest class, FFP2).
!
Note! Only use filters recommended by FläktGroup at exchange. If
incorrectly selected filters are installed, there is a risk that perfor-
mance and air quality will not be achieved. FläktGroup disclaims
warranty liability if incorrect filters are installed upon replacement.
CLEANING THE FANS
The fans should be checked every two years. The fans should be
cleaned if there is dirt on the impellers. Note that the fans are not be
cleaned with water or other fluids. The fans are only to be cleaned with
a vacuum cleaner or a brush. It is strongly recommended to let an
educated professional maintenance the fans.
Before cleaning the fans, heat exchanger etc, the unit should always have the power
disconnected.
1. The heat exchanger is removed from the unit
2. Remove the screws for the cover plates of the fans.
3. Disconnect the electrical contacts and remove the fans from the
unit.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
8
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
OVERHEATING PROTECTION, TEMPERATURE
ALARMS, OTHER ALARMS
POST HEATER ELECTRICAL
The unit has an overheating protection device that switches off the
electrical post heater if the temperature is too high. If the overheating
protection has triggered, the user needs to manually reset this. See
figure below:
Overheating protection
reset button
When the overheating protection has been triggered remove the plastic cover and
press the reset button on the front edge of the electrical box inside the unit.
Note! If the overheating protection device has been triggered it is
important to find the overall cause of the problem.
TEMPERATURE ALARM
The unit automatically identifies temperature sensor errors. In the
event of an error, arrange a service visit.
CONDENSATION, WATER INSIDE THE UNIT
When the unit is running, moisture from the extract air may condensa-
te in the heat exchanger. This applies mainly during autumn and winter.
The amount of moisture condensated from the extract air depends
on moisture production in the house such as cooking and showering.
Typically in newly built houses the construction materials emit their
excess moisture during the first years. In the bottom of the unit there
is a drainage for removal of the condensate. It is important to regularly
check the function of drainage to prevent clogging. After the summer
the water in the water trap may have evaporated. This can result in a
gurgling noise. Remedy this by pouring water into the drain hole inside
the unit to fill the water trap.
The chromed ball-fitted water trap allows for a silent and reliable the disposal of
condensate.
The heat exchanger is cleaned with either a vacuum cleaner or by showering it with
water.
Note! Acetone or a similar solvent must not be used. The heat ex-
changer is not to be soaked in water etc. Do not use sharp objects.
Make sure that the heat exchanger is completely dry before rein-
stalling.
CLEANING THE HEAT EXCHANGER
Check that the surface of the heat exchange is not covered in dust.
Clean by either using a vacuum cleaner, compressed air or by
showering the heat exchanger with water. If this is not sufficient, apply
a grease-dissolving fluid such as dish soap and wash the heat ex-
changer.
4. Detach the impeller from the fan by removing the four screws.
5. Clean the fan and impeller with a brush.
6. Reinstall the cleaned fan in reverse order.
The heat exchanger is pulled out of the unit. When reinstalling make sure that all the
gaskets are in the right possition and fully intact.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
9
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
MAINTENANCE SCHEDULE, FAN SPEED SETTINGS
MAINTENANCE SCHEDULE
Date of purchase of the unit: ............./.........../20.........
Fill in the record starting from the season of the year following the
purchase.
Period Replace the filters,
clean the unit
Vacuum the
exhaust air filter Check unit operation Clean the
heat exchanger
Check/clean the
fans
Year 1, spring x x
Year 1, autumn x x
Year 1, winter x
Year 2, spring x x x
Year 2, autumn x x
Year 2, winter x
Year 3, spring x x (x) (x)
Year 3, autumn x x
Year 3, winter x
Year 4, spring x x x
Year 4, autumn x x
Year 4, winter x
Year 5, spring x x (x) x
Year 5, autumn x x
Year 5, winter x
Year 6, spring x x x
Year 6, autumn x x
Year 6, winter x
Replacing the filters and cleaning the unit: Replace the filters according
to the instructions, vacuum the unit inside and wipe with a damp cloth
if necessary. Clean the water trap at the same time.
Note! Depending on the situation it may be necessary to change
the filters more often than indicated in this manual. In that case, the
other maintenance actions should also be performed at more frequ-
ent intervals.
Checking the operation of the unit: Listen to the fan sounds (do they
both work, is the sound balanced, are there noises that may indicate
bearing faults?). Inspect the condition of the unit visually.
Cleaning the heat exchanger: Clean the heat exchanger according to
the instructions. Perform the inspection every spring and clean if dirty
or every 1–2 years.
Checking/cleaning the fans: Perform the inspection every two years
and clean if dirty or every 4-5 years. The cleaning is strongly recom-
mended to be performed by a professional to ensure that the fans’
balance pads do not become dislodged.
Note! The ventilation ducts should be cleaned by a professional
every 5–7 years or according to the local regulations.
FAN SPEED SETTINGS
To find out about the fan speed settings, check the set-up record or
contact the person who performed the set-up. We recommend that
you write down the settings here for future reference.
Fan speed setting Supply fan Extract fan
Speed 1 V V
Speed 2 V V
Speed 3 V V
Speed 4 V V
Supply difference adjustment V V
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
10
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
INSTALLATION (FOR INSTALLER AND SERVICE PERSONNEL)
DIMENSIONS AND WEIGHT
DUCT CONNECTIONS
1 = outdoor air (Ø125)
2 = supply air (2x Ø125)
3 = extract air (2x Ø125)
4 = exhaust air (Ø125)
K = condensate outlet (½” female thread) at the bottom
Weight: 50 kg
MODEL L (LEFT)
Outdoor air left, supply air right
MODEL R (RIGHT)
Outdoor air right, supply air left
515
598
130
130
168
85.5
570
140 142 145
4
2
2
1
3
2 3
K
84
84
221
K
2
130
84
84
85.5
140142145
4
2
1
3
23
221
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
11
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
DUCT CONNECTION, INSULATION OF THE DUCTS
Note! During installation, the instructions relating to the unit and
duct insulation must be adhered to without deviation. Otherwise
there is a risk of condensation and moisture resulting in a major
damage.
DUCT CONNECTION
Exhaust air from the unit should only be connected to a ventilation duct
intended for the purpose. Connection should not be made to a chimney
or a smoke or gas duct. If the unit is being used in premises with for
example an open fireplace or heating stove with a chimney or smoke
or gas duct, an adequate supply air flow must be provided. A kitchen
duct must be provided in accordance with applicable regulations.
INSULATION OF DUCTS
In order to the unit working as intended the duct system should be
installed in a professional manner in accordance with local regula-
tions and following the ventilation plans made by a professional. This
includes installation of the ducts through external walls containing
insulation and vapour barriers, external roofs and joists. If this is not
done in professional manner there is a risk for condensation, resulting
in possible damage to the unit, duct system or the structure itself due
to moisture. In the case of replacing older units, it is also necessary
to ensure the quality of the ducts and duct insulation. Supply air ducts
and extract air ducts are filled with warm air. If those ducts are placed
in unheated spaces they must be insulated. The insulation should be
applied externally and have a wind-proof surface layer. Outdoor air
ducts and exhaust air ducts are filled with cold air. If those ducts are
placed inside the building’s vapour barrier they must be insulated and
have a diffusion-proof (moisture-proof) surface layer. Given the high
degree of heat recovery achieved by unit the exhaust air also gets very
cold and must be thermally insulated.It is also important that the wall/
ceiling which the unit will be mounted on is well insulated.
SILOX
EV
O
EXT
EXH
DUCT DEFINITIONS
O = Outdoor air
S = Supply air
EXH = Exhaust air
EXT = Extract air
EV = Extract air valve
INSTALLATION OPTIONS AND DUCT DEFINITIONS
If the unit is not installed immediately after delivery it should be stored
in a protected place under cover and in its original packaging. It is
recommended using some machinery while moving and lifting the unit.
Use protective gloves during the installation.
INSTALLATION OPTIONS
The unit shall be placed according to the ventilation plans made by
a professional. If there is no specific ventilation plans then the unit
should be installed according to one of the following options. The unit
is intended for indoors installation in a warm space and can be wall
mounted or ceiling mounted.
Warning! In order to prevent personal injury: The unit must
be connected to the ducts before the power plug is connec-
ted.
!
Warning! The unit must always be connected to a protective
earth socket.
!
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
12
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
MOUNTING EXAMPLE
Caution! To avoid the risk of moisture damage to the roof
and roof insulation, the outdoor air duct should not be instal-
led horizontally inside the roof insulation. Outdoor air duct
should be insulated with 100 mm mineral wool mat with a
moisture-proof surface layer in cold spaces.
The exhaust air duct from the unit should
preferably run straight to the roof, without any
horizontal runs inside the roof insulation.
The outdoor and exhaust
air duct must be insulated
with 100 mm mineral wool
mat with a moisture-proof
surface layer in cold spaces.
If cooker hood is connected
to the unit, EI30 insulation
should be used.
The condensate pipe must run into a floor drain, not directly into
the sewer. The water seal height of the water trap must be at
least 100 mm. There must be no more than one water trap and
no horizontal runs in the condensate pipe.
NB! If the unit is equipped with
a cooling coil, the supply air
duct must be insulated, e.g.
with Armaflex, or with insulation
covered with an airtight vapour
barrier.
The outdoor and exhaust air ducts must be
insulated with 100 mm mineral wool mat with a
moisture-proof surface layer in warm spaces.
The extract and supply
air ducts do not need any
insulation in warm spaces.
The extract and supply air
ducts must be insulated with
100 mm mineral wool mat
and preferably inside the
loose wool in cold spaces.
Installation example.
SITE OF INSTALLATION
The air handling unit should be installed in a heated space. Ambient
temperature should be above +10 °C. The ILOX 86Plus can be either
wall mounted with the accessory mounting bracket or ceiling mounted
with the accessory ceiling mounting frame.
INSTALLING THE CONDENSATE REMOVAL PIPE
At the bottom of the unit, there is an outlet (1/2“ internal thread) for
condensate removal. Fit a pipe or a rigid hose with an inner diameter
of at least 12 mm between the condensate outlet and a floor drain or
the waste connector of a wash basin. The condensate removal pipe
should not run directly into the sewer. A water trap has to be instal-
led in the condensate removal pipe. Make sure that the condensate
removal pipe is always leaning towards the floor drain or wash basin.
The condensate removal pipe should always be installed in warm con-
ditions. If the condensate removal pipe can not be installed in warm
conditions, a heating cable should be installed in order to prevent fre-
ezing. Make sure to fill up the water trap.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
13
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
MOUNTING OPTION, WALL
The wall mounting bracket (accessory) should be attached securely
into a wall, preferably onto a brick, light weight concrete or concrete
wall. If the mounting surface is a drywall or similar material, the wall
must be strengthened with additional wall frame or a plywood board.
1. Check both vertical and horizontal alignment with a spirit level.
2. Remove the two bottom rear mounting screws.
3. Lift the bottom edge of the unit onto the lower parts of the mounting
brackets.
4. Move the unit slightly upwards, keeping it against the wall, until the
mounting projections in the upper part of the bracket are guided into
the openings of the unit.
5. Lower the unit onto the bracket.
6. Fasten the bottom corners onto the brackets using the screws re-
moved earlier.
Note! Installing the unit on a bedroom boundary wall with the wall
mounting bracket should be avoided due to the transmission of
sound; using the ceiling mounting frame is recommended.
MOUNTING OPTION, CEILING
1. Secure the ceiling bracket (accessory) in the ceiling structure using
four 8 mm threaded rods.
2. The bracket should be installed with the mounting hooks pointing
downwards and the ducts as the figure shows. The figure shows
outlets for a right-handed unit (Model R).
3. Flange nuts should be fitted above the frame, and a conical rubber,
washer and locking nut should be fitted underneath the frame.
4. Pre-tighten the locking nut manually approximately two turns (the
rubber should shorten about 2 mm).
5. Cut off the threaded rods, leaving the ends of the rods above the
lower edge of the frame.
6. Put the power cord and the external connection box through the lar-
ge opening in the mounting frame.
7. Lift the unit to the ceiling mounting frame so that the mounting
hooks fit to the corresponding slots on top of the unit. Use some
force upward from the bottom of the unit until the unit locks to the
mounting frame with clicking sounds. Double check that the unit is
secured tightly.
Note! The bottom of the frame should be installed no more than 10
-20 mm above the finished ceiling surface or possible crown mol-
ding, so that the unit door can still open.
Dimensions of the ceiling-mounting frame (model R ducting).
130
130
168
168
17.5 85.5 15
570
511
140
40
568
598
142 145
4
2
2
1
3
2 3
Locations for threaded rods
1
2
371
520
595
60
523
Wallmounting with wall rails.
The figure below shows the duct outlets for Model (R).
1. Outdoor air for the unit
2. Supply air from the unit to the house
3. Extract air for the unit
4. Exhaust air
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
14
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
8 mm threaded rod
8 mm flange nut
Rubber damper
Washer
8 mm nut
Threaded rod attachment.
Warning! When using a ceiling mounting frame, it is especi-
ally important to make sure that the unit is properly secured
to the ceiling mounting frame. When the unit engages the
frame, you should hear a clear “click” on both sides of the
ceiling mounting frame.
!
Connecting the accessory control equipment to the external connection box.
ELECTRICAL INSTALLATION
The air handling unit is equipped with a plug connector, which can be
plugged directly into a wall socket that has an earth connector. The
wall socket should be installed inside the building’s moisture barrier
to a place where it can be unplugged with ease. Electrical installation
and connections for the unit must be made by a qualified electrician.
The unit is equipped with a service switch for switching off the power.
When installing accessories or other electrical connections, power
should be switched off by disconnecting the plug from the socket. The
unit is equipped with an external connection box for connecting some
of the basic accessories of the unit.
EXTERNAL CONNECTION BOX
An external connection box is used to make the most common control
connections to the unit. The external connection box is mounted above
the unit or in the ceiling, next to the service hatch. It is strongly re-
commended to install the external connection box inside the building’s
moisture barrier.
INTERNAL CONNECTIONS
The PCB in the unit’s control box is used to make the physical connec-
tions required for external control and to connect any of the following:
internal carbon dioxide transmitter, carbon dioxide switch, internal
humidity transmitter, humidity switch, emergency stop switch, Home/
Away switch and fireplace boost switch.
Note! Extra length must be allowed for the cables, so that the inside
of the electrical box can be pulled out sufficiently for installation.
Plus Touch panel
Mosaik switch
Modbus in
Cable with plug 86Plus
Modbus out
Hood control from Basic, Seili, Design,
Basic-E, Slide-E, Rosala, Satava
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
15
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
CONNECTION DIAGRAMS
9
10
11
15
16
17
18
23
24
25
26
27
28
GND
1 2 3 4 5 6 7 8
19
20
21
22
12
13
14
5
6
7
8
1
2
3
4
33
32
31
30
37
36
35
34
40
39
38
43
42
41
46
45
44
24V
T2 T3 T4 T5 T6 T7
Led no
24VDC
0-10V
GND
24VDC
GND
GND
L
N
L
N
L
N
PE
PE
T1
55 N
54 Actuator 230V 10W
53 N
52 Pump control 230V 100W
51
50
Transformer 24V
Prog. connector
USB
R
switch
Humidity
2x2x0,5
NOMAK
+0,5
transmitter
Humidity
2x2x0,5
NOMAK
+0,5
24V
0-10V
GND
474849
1wt
2or
1or
1wt 1or2or2or 1or
R
switch
CO²
2x2x0,5
NOMAK
+0,5
transmitter
CO²
2x2x0,5
NOMAK
+0,5
24V
0-10V
GND
1wt 1or2or2or 1or
1wt
2or
1or
or
or
home
away
Home/Away
switch
1wt 1or
2x2x0,5
NOMAK
+0,5
1or
1wt Home/Away
AHU e-stop
CO2
Humidity
24V
0-10V
GND
1
2
3
4
1or
2or
Fireplace impulse
switch
2or 1or
NOMAK
2x2x0,5
+0,5
loop
Forced mode
1
2
3
4
5
6
7
8
9
9
10
Home
Boost
Maximum
Ctrl. voltage 24VDC
Ctrl. panel GND
Ctrl. panel B
Ctrl. panel A
Ctrl. panel 24VDC
Modbus A
Modbus A
Modbus B
10 Modbus B
1
2
3
4
5
6
7
8
9
10
box is included in the delivery
L
br
N
bl
-
B
+
5
A
B
A
dooHdooH
-
+
yl/g
1
2
3
4
L
N
NL
L
Hood
Plug
NL
Plug
A01 CAV032A01 CAV032
Control by cooker hood
11 Modbus PE
1or
1wt
2or
2wt
2x2x0,5
NOMAK
+0,5
1or
2or
2wt
1wt
2x2x0,5
NOMAK
+0,5
Mechanical hoods
manual damper
Ilox Basic
Ilox Seili
Ilox Design
Ilox Design center
Electronic hoods
manual damper
Ilox Basic-E
Ilox Slide-E
Electronic hoods
electric damper
Ilox Rosala
Ilox Satava
Status data 2-4
Status data comm.
Status data 1
Common
Alarm A
Alarm B
PE 1rd 1bl PE 1rd 1bl
in out
1or 1wt 2or
1 2 3 4
2wt 1wt 2wt 2or
5 6 7 8
1or
External terminal box
Installation on top of the machine or
in the ceiling by the service hatch
2x(2+1)x0,5+0,5
JAMAK
Device cable of the external terminal
B
Modbus A
5
7
8
6
9
10
wt
g
bk
bl
19
20
21
22
RJ12
Startup panel connector on
the side of the electric box
MODBUS
1or 1va
2x2x0,5
NOMAK
+0,5
AHU
emergency-stop
1wt
1or
Control voltage can be taken from connectors 34 and 37
(external 24VDC voltage to be supplied)
AHU e-stop circuit opto-isolated
1or
1wt
Daisy chain to next
Iloxair AHU unit 30
31
potential free
contact
L
L
speed selector switch
illustrated from behind
Mosaik
1or 2or 1wt
1or 2or 1wt
4 2 1
NOMAK
2x2x0,5
+0,5
1. speed control, away
2. speed control, home
3. speed control, boost
4. speed control, max
status data speed 2-4
status data common
status data 1
alarm common
alarm A
alarm B
8x2x0,5
NOMAK
+0,5
Control from BMS
Physical connection points
23
24
25
9
10
11
5
6
7
8
1
2
3
4
touch panel
Optima
1or 2or 2wt 1wt
+A+ B- -
1or 2or 2wt
8 7 6 5
1wt
NOMAK
2x2x0,5
+0,5
2wt 2or 1or
2x2x0,5
+0,5
1wt 2or 2wt
1 2 3
12
34
56
78
NOMAK
1or
4
1wt
speed selector
switch
lzer M220
CONTROL
BY SWITCH
CONTROL
BY PANEL
1wt
2wt
2or
1or
1wt 2wt 2or
5 6 7 8
1or
1wt
2or
2wt
3or
1or
3wt
4or
4wt
5or
5wt
6or
24V control
1or
3or
2wt
2or
1wt
3wt
4or
4wt
5or
5wt
6or
6wt
37
38
39
6wt
GND
0-10V
-
+
Control by signal voltage 0-10V
0-10V (-)
0-10V (+)
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
16
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
An emergency stop circuit for a number of air handling units with the control voltage
taken from the PCB.
AHU emergency
stop switch
1or 1wh
NOMAK
2×2×0.5
+0.5
NOMAK
2×2×0.5
+0.5
AHU emergency stop circuit opto-isolated
(requires an external 24 VDC supply)
The control voltage can be taken from
terminals 34 and 37.
AHU 1
37
GND
34
24 VDC
36
36
33
32
31
30
37
GND
34
24 VDC
36
36
33
32
31
30
AHU 2
AHU
emergency stop
1or
1or
1or
1va
1wh
1wh
AHU
emergency stop
PHYSICAL CONNECTIONS FOR EXTERNAL CONTROL
The unit can be controlled via physical controls such as the HOME/
AWAY switch. These types of controls override the Plus Touch panel
controls.
More detailed connection instructions are available in the electrical
connections diagram.
CO2 CONTROL
The unit can be controlled to maintain carbon dioxide below a certain
level by adjusting the operation mode. It is possible to use a inter-
nal CO
2
transmitter or a CO
2
switch. See the connection diagram for
electrical connections.
HUMIDITY CONTROL
The unit can be controlled to maintain the humidity below a certain
level by adjusting the operation mode. It is possible to use a internal
humidity transmitter or a humidity switch. See the connection diagram
for electrical connections.
EMERGENCY STOP
An emergency switch can be used to stop the unit. This connection is
opto-isolated and requires an external control voltage of 24 VDC. If ne-
cessary, the control voltage can be taken from terminals 37 (GND) and
34 (24 VDC) on the control board.
CABLE ENTRY
There is a cable gland on top of the unit to allow for internal connec-
tions. Inside the unit, the cable is routed to the electrical box through
the glands at the back of the box.
Top view over cable entry.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
17
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
PCB user interface
Control knob Programming
button
Eight LEDs 1-8
Fan speed voltage settings.
SET-UP MENUS - ONLY FOR INSTALLER
The menu of the PCB user interface.
1 2 3 4 5 6 7 8
1st press
2nd press
3rd press
4th press
5th press
6th press
7th press
8th press
9th press
10th press
Speed 1 (Away)
Speed 2 (Home)
Speed 3 (Boost)
Speed 4 (Maximum)
Supply fan correction
Max. speed limit for defrosting
2)
Post heater activation temp.
1)
Modbus communication speed
Modbus ID address
Speed 1
1) Outdoor temperature setting, see page 17. 2) See page 18.
The unit can be set up using one of the following options:
PLUS TOUCH PANEL
If the unit is not connected to an PLUS Touch panel, it is possible to
use a service panel. Connect the service panel to the appropriate
port on the front cover of the control box. When the PLUS Touch panel
has started up, go to the menu (in the upper left corner) Settings
Down arrow Maintenance Settings Menu 4569 OK Guided
Installation START. This commissioning wizard guides you through the
fan speed settings and supply air temperature setpoint. More settings
are available in the maintenance settings menu. Press and hold an
item for pop-up help. To select an item, press it briefly.
PCB USER INTERFACE
On the electrical box there is a control knob, eight LED:s and a pro-
gramming button, all of which are connected to the PCB. To switch
from one set-up parameter to the next, press the button briefly. To
view the value of the current parameter, press and hold the button. To
change the value of the parameter:
1. Hold the button pressed down for 5 seconds
2. The value begins to flash
3. Keep the button pressed down
4. Rotate the control knob to change the value
5. Release the button, the selected value is confirmed
6. Wait for 10 seconds in order to leave the set-up mode
12 3 4 5 6 7 8
+8 +6 +4 +2 0–2 –4 –6
Reheating set point (limit value).
POST HEATER ACTIVATION TEMPERATURE:
It is possible to set a temperature limit when the electrical post heater
is allowed to be active. In case the outdoor temperature is higher than
the selected value the post heater will not activate even if the supply
air temperature setpoint is not reached. In order to access this para-
meter press the button 7 times and select the activation temperature.
Please see picture Reheating set point (limit value) how the LED’s corres-
pond to the temperatures.
Note! It is possible to set the activation temperature even higher
with PLUS Touch screen or service panel.
Note! In case the temperature limit is set too low there is a risk of
draft or condensation in case the heat recovery is not able to provi-
de enough thermal energy to the supply air.
10V
9,5V
9,0V
8,5V
8,0V
7,5V
7,0V
6,5V
6,0V
5,5V
5,0V
4,5V
4,0V
3,5V
3,0V
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
18
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
Temperature settings for electric reheating.
26°C
25°C
24°C
23°C
22°C
21°C
20°C
19°C
18°C
17°C
16°C
15°C
14°C
13°C
12°C
0°C
It is possible to change the supply air temperature setpoint when the
unit is not in set-up mode (to leave the set-up mode do not press the
programing button for 10 s). This is done by rotating the control knob.
Alternatively, use the PLUS touch control panel and go to Settings
Temperature. The default is 17 °C.
FAN SPEED MODE
When the unit is not in set-mode or temperature setpoint mode the
LED:s on the front of the electrical box indicates the fan speed mode of
the unit.
LED 1 = Away
LED 2 = Normal
LED 3 = Boost
LED 4 = Maximum
LED 5 = Fireplace
LED 6 = Defrost mode
ADJUSTING THE SUPPLY AIR TEMPERATURE SETPOINT
POST HEATER, ELECTRICAL
SUPPLY FAN CONTROL VALUE CORRECTION
In order to achieve accurate supply and extract air flows you might
have to adjust the supply fan speed with Supply fan voltage correction
function. With this function it is possible to set the supply fan control
voltage from -1,2 V lower up to +1,2 V higher compared to the exhaust
fan.
1. Press the button until LED’s from 5 to 8 light up (5th press).
2. Press and the button and rotate the control knob change the value
(see picture below).
3. Release the button and the selected value is confirmed.
Note! This set value correction applies to all fan speeds!
DEFROSTING MAXIMUM SPEED LIMITATION:
It is possible to change the defrosting maximum speed limit. In order
to access this parameter press the button 6 times and select the con-
trol value as in the fan speed value settings.
Note! It is not possible to exceed this selected value during defros-
ting in any way!
0 V
-0.2 V
-0.4 V
-0.6 V
-0.8 V
-1.0 V
-1.2 V
+0.2 V
+0.4 V
+0.6 V
+0.8 V
+1.0 V
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
19
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
REMOVING THE UNIT FROM THE CEILING
Note! The example relates to the ILOX 129, but the ILOX 86 is remo-
ved in the same way.
1. Remove the front panel from the front of the frame by taking out the
2 screws. Then push the front panel upwards to re move it.
2. Support the ventilation unit from underneath so that it does not fall
when the rails are released.
4. The ceiling mount rails slide in the ceiling mount frame, as in the
image, and release the ventilation unit.
3. Release the mounting from the ceiling mount frame by pushing
back the ceiling mount rail that is visible through the holes in the
front of the frame. This should be done on both sides of the frame.
Air Handling Unit ILOX 86Plus - Operation, installation and maintenance manual
20
FläktGroup FG_DC10084GB_20201027_R0 Specifications are subject to alteration without notice
DECLARATION OF CONFORMITY
ENCLOSURE II A
FläktGroup Finland Oy
Postal Address Street Address Telephone Telefax Reg. no:
FläktGroup Finland Oy Logistiikkakeskus Nat +358 20 44 23 000 Nat +358 20 44 23 011 2495875-8
KALEVANTIE 39 Rydönnotko 1 Reg. office:
20520 TURKU, FINLAND 20360 Turku, FINLAND Turku
FG_DC_10371GB_ILOX 59PLUS_ILOX89PLUS_ILOX129PLUS_ ILOX199PLUS_DOC_20190920_R0
Declaration of Conformity
In accordance with:
EU Directive for Machinery, 2006/42/EC
EU EMC Directive, 2014/30/EU
EU Directive for Energy related Products ErP 2009/125/EC
EU RoHS Directive, 2011/65/EU
Manufacturer FläktGroup Poland Sp. z o.o
Ul. Poludniowa 2, Oltarzew
05-850 Ozarów Mazowiecki
Herewith declares that:
Product Type: Ventilation unit
Manufacturer: FläktGroup
Commercial name: ILOX 59PLUS
ILOX 86PLUS
ILOX 89PLUS
ILOX 129PLUS
ILOX 199PLUS
The machine is designed and manufactured in accordance with the following standards, in relevant parts.
EN ISO 12100 Safety of machinery – General principles for design- Risk assessment and risk reduction
EN 60204-1 Safety of machinery; electrical equipment of machines; general requirements
EN 60335-1 Household and similar electrical appliances - Safety - Part 1: General requirements
EN 60335-2-40,31 Household and similar electrical appliances - Safety - Part 2: Particular requirements
EN 61000-6-1 Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity for
residential, commercial and light-industrial environments
EN 61000-6-3 Emission standard for residential, commercial and light-industrial environments.
EN 50106 Safety of household and similar electrical appliances - Particular rules for routine tests
referring to appliances under the scope of EN 60335-1
EN 62233 Measurement methods for electromagnetic fields of household appliances and similar
apparatus with regard to human exposure
EN 50581:2012 Technical documentation for the assessment of electrical and electronic products with
respect to the restriction of hazardous sustances
A risk analysis has been made according to requirements of the Directive for Machinery.
Authorized To prepare technical documentation:
Ann-Sofie Andersson
Design- R&D
FläktGroup Sweden AB
Fläktgatan 1
551 84 Jönköping
The declaration applies only to the installation made according to FläkGroup instructions and assuming no
changes made to the unit.
Varsova 2020-05-20
Mariusz Zakrzewski, Operational Director, FläktGroup Poland Sp, Varsova
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

FläktGroup ILOX 86PLUS Installation and Maintenance Manual

Category
Split-system air conditioners
Type
Installation and Maintenance Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI