www.pulsar.pl AWZ05121
F fuse
F1÷F5 fuse
T 315A/250V
F 500mA/ 250V
M
echanical specifications (tab. 4).
Enclosure dimensions 170 x 180 x 88 (175 x 185 x 80+8) (WxHxD)
Fixing 145 x 174 x Φ 6 WxH
Net/gross weight 1,6/1,7 kg
Enclosure colour Steel plate DC01 0,7mm thick, colour RAL9003
Closing Cheese head screw (at the front)
Connectors Mains power 230V AC: Φ0,63-2,05 (AWG 22-12)
DC outputs: Φ0,51- 2,05 (AWG 24-12)
TAMPER output: wires 25cm
Notes The enclosure does not adjoin the assembly surface so that cables can be
led.
Convectional cooling
Operation safety (tab.5).
Protection class PN-EN 60950-1:2007 I (first)
Degree of Protection PN-EN 60529: 2002 (U) IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000V AC min.
1500V AC min.
500V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V DC
Operating specifications (tab.6).
Operating temperature -10ºC...+40ºC
Storage temperature -20ºC...+60ºC
Relative humidity 20%...90%, without condensation
Vibrations during operation unacceptable
Impulse waves during operation unacceptable
Direct insolation unacceptable
Vibrations and impulse waves during transport PN-83/T-42106
2. Installation
2.1Requirements.
The stabilized PSU is to be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC interference and low-voltage installations. The unit
should be mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative
humidity (RH=90% maximum, without condensation) and temperature from -10°C to +40°C. The PSU shall wor k in
a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure.
Before mounting the PSU module, perform a load balance. During normal operation, total
current drawn by the receivers cannot exceed
I=1A (P=12W max.). The change of the original
fuse value is acceptable unless all power outputs are in use and Pmax is exceeded.
As the PSU is designed for a continuous operation and is not equipped with a power-switch,
therefore an appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user
shall be informed about the method of unplugging (usually through assigning an appropriate fuse in the fuse-box).
The electrical system shall follow valid standards and regulations.
2.2 Installation procedure.
1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off.
2. Mount the PSU in a selected location and connect the wires.
3. Remove the mains fuse that protects the primal circuit.