  • Hello! I am an AI chatbot trained to assist you with the Danfoss Heat exchanger XGM032 Service guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
© Danfoss | 2016.10
VU.JQ.C1.02 | 1
ENGLISH
XGM032 www.danfoss.com Page 2
DEUTSCH
XGM032 www.waerme.danfoss.com Seite 3
ITALIANO
XGM032 www.danfoss.com Pagina 4
FRANÇAIS
XGM032 www.danfoss.fr Page 5
ROMÂNĂ
XGM032 www.danfoss.com Pagină 6
POLSKI
XGM032 www.heating.danfoss.pl Strona 7
РУССКИЙ
XGM032 www.danfoss.com Страница 8
XGM032
Service Guide
2 | © Danfoss | 2016.10
VU.JQ.C1.02
XGM032
Defining thickness of the plate by reading the plate code. In one of the angles of the plate you
can find code of the plate (one digit + one letter). First digit means thickness of plate. 3 means
0,3 mm, 4 means 0,4 mm. Letter means type of plate (H, M or L). If the marking is not present at
any of angles – plate is 0,3 mm thick.
Defining type of the plate. If the plate doesn’t have marking in the corner, you can check type of
the plate on the label of the HEX. Type of plate is described in the naming. Example: XGM032H-1-30.
Letter H shows, that plate pack type is H. Plate type can be H, M or L.
To service the hex, please order correct plate type, using codes below:
079B0419 PLATES 4H. 0,4 XGM032H 1.4404 I-P 10
079B0418 PLATES 4H. 0,4 XGM032L 1.4404 I-P 10
079B0417 PLATES 4H. 0,4 XGM032M 1.4404 I-P 10
Calculation of A dimension. N is number of plates
Only 0.3 mm plates. A=2,3*n
Only 0.4 mm plates. A= 2,4*n
Mix of 0.3 mm + 0.4 mm plates A=2,3*n0.3 mm plates+2,4*n0,4 mm plates
Measuring A dimension. A dimension is length of assembled and tightened plate pack of heat plates.
A dimension does not include plate with connections (if the HEX has it). Please see photo below.
1. Define the plate thickens
2. Define plate type
3. Order replacement plates of the type you need
4. Replace plates with new ones
5. Assemble the HEX, strictly following instruction manual and A dimension.
Please follow the steps below in order to service XGM032 HEX properly.
Plate thickness
Plate type
A dimension
ENGLISH
© Danfoss | 2016.10 | 3
VU.JQ.C1.02
XGM032
DEUTSCH
4 | © Danfoss | 2016.10
VU.JQ.C1.02
XGM032
ITALIANO
© Danfoss | 2016.10 | 5
VU.JQ.C1.02
XGM032
FRANÇAIS
6 | © Danfoss | 2016.10
VU.JQ.C1.02
XGM032
ROMÂNĂ
© Danfoss | 2016.10 | 7
VU.JQ.C1.02
XGM032
POLSKI
© Danfoss | 2016.10 | 8
VU.JQ.C1.02
XGM032
РУССКИЙ
/