VLT AQUA Drive FC 202

Danfoss VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, VLT HVAC Drive FC 102, VLT® Mains Shield Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss VLT AQUA Drive FC 202 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MI.38.M1.02 - VLT
®
is a Danfoss Registered Trademark 1
This instruction sheet is for the installation of a mains shield for the
VLT series drives frames D1, D2 and E1. This kit can be installed in
IP21/NEMA 1 or IP54/NEMA 12 enclosures on D1, D2 frames manu-
factured after week 29 of 2005 and all E1 frames. It is not possible
to install in the IP00/Chassis versions as these have included as
standard a metal cover. These shields satisfy VBG-4 requirements.
Ordering numbers
Frames D1 and D2: 176F0799
Frame E1: 176F1851
INSTRUCTIONS
INSTALLATION OF MAINS SHIELD FOR VLT DRIVES
Required Tools
Socket wrench with 07mm to
17mm sockets
T30 Torx Driver
Torque Requirements
M6—35 in-lbs (4.0 N-M)
M8—85 in-lbs (9.8 N-M)
M10—170 in-lbs(19.6 N-M)
IP21 Frame D2 VLT
Mains Shield kit parts
Lexan® cover with
access holes for
test probes and
two mounting
brackets (E1 mains
shield consists of
two pieces )
Install mounting
brackets on the
input plate using
existing studs
and nuts
IP21 Frame D2 VLT
with mains shield
installed
Install mains
shield using
4 M6 torx
screws
1/1