milleteknik 350-122 Owner's manual

Type
Owner's manual

The milleteknik 350-122 Redundancy Panel 1U is a rack-mounted unit for power control of Milleteknik's Power supply 24V 15A 1U or battery backups. It has three inputs, allowing up to three power supplies to be connected. If two of the three power supplies fail, the third and final functioning power supply will cover the system. Redundancy Panel 1U alarms when any of the power sources fail or in case of load fuse faults.

The milleteknik 350-122 Redundancy Panel 1U is a rack-mounted unit for power control of Milleteknik's Power supply 24V 15A 1U or battery backups. It has three inputs, allowing up to three power supplies to be connected. If two of the three power supplies fail, the third and final functioning power supply will cover the system. Redundancy Panel 1U alarms when any of the power sources fail or in case of load fuse faults.

Redundancy Panel 1U
Strömstyrning av Power supply 24V 15A
SV
EN
350-122
Publiceringsdatum 2023-03-09
Innehållsförteckning
1. Om ........................................................................................................................................... 3
2. Komponentöversikt ..................................................................................................................... 4
3. Kapsling .................................................................................................................................... 5
3.1. Montering i 19" rack ......................................................................................................... 5
3.2. Montering ....................................................................................................................... 5
4. Inkoppling .................................................................................................................................. 5
5. Koppla ihop med Power supply 24BV 15A 1U .............................................................................. 6
5.1. Input 3 ............................................................................................................................ 6
6. Anslut last ................................................................................................................................. 7
6.1. Larmfunktioner ................................................................................................................ 7
7. Anslut larm ................................................................................................................................ 7
8. Driftsättning ............................................................................................................................... 8
9. Panelförklaring ........................................................................................................................... 8
10. Regelverk och certifieringar ...................................................................................................... 8
10.1. Krav som produkten uppfyller ......................................................................................... 8
11. Tekniska data ........................................................................................................................... 8
12. Tekniska data kapsling .............................................................................................................. 9
12.1. Tekniska data 1U ........................................................................................................... 9
13. Garanti, support, tillverkningsland och ursprungsland ................................................................. 9
13.1. Garanti ......................................................................................................................... 9
13.2. Tillverkningsland ........................................................................................................... 9
13.3. Tillverkare ..................................................................................................................... 9
14. Produktens livslängd, miljöpåverkan och återvinning ................................................................ 10
15. Om detta dokument ................................................................................................................ 10
16. Adress och kontaktuppgifter .................................................................................................... 10
1. OM
Redundancy Panel 1U är en rackmonterad enhet för strömstyrning av Power supply 24V 15A 1UE eller
batteribackuper från Milleteknik. Redundancy Panel 1U har tre (3) ingångar vilket innebär att det är
möjligt att ansluta upp till tre (3) nätaggregat (Power supply 24V 15A 1U). Om två av tre nätaggregaten
(Power supply 24V 15A 1U) / batteribackuper slutar att fungera som strömkälla till systemet täcker det
tredje och sista fungerande nätaggregatet. Redundancy Panel 1U larmar för om någon av strömkällor-
na slutar att fungera eller vid lastsäkringsfel.
Användningsområde: Där behov av redundans i 24 V strömförsörjning finns.
3
SV
LÄS DETTA FÖRST!
Om det är möjligt, lämna 100 mm fritt utrymme.
Systemet är avsett för bruk i kontrollerad inomhusmiljö.
Endast personer med behörighet bör installera och underhålla systemet.
Det är installatörens ansvar att systemet är lämpad för avsett bruk.
Dokument som medföljer systemet skall förvaras i det eller i dess omedelbara närhet.
Ventilation skall ej övertäckas. Nätspänning bör vara bortkopplad under installation.
Alla uppgifter med reservation för ändringar.
Vid installation av denna produkt erkänner och accepterar installatören denna produkts
begränsningar som de är beskrivna i denna manual.
2. KOMPONENTÖVERSIKT
Figur 1. Framsida
Nr Förklaring
1 Indikeringsdiod för last och anslutna Power supply 24V 15A 1U
2 Lastsäkringar
Figur 2. Baksida
4
SV
Nr Förklaring
1 Dubblerat summalarm, NO/COM/NC+NO/COM/NC. Summalarm: larm vid bortfall av spänning från nätaggregat (Power
supply 24V 15A 1U) ett, två och tre (beroende på vilka som är inkopplade), utlöst lastsäkring 1, 2 och 3, (beroende på
vilka som är anslutna).
2.1-2.4 Last in 1-4, -- / ++
3.1-3.3 Inkoppling av Power supply 24V 15A 1U
3. KAPSLING
3.1. Montering i 19" rack
Enheten skall monteras i 19” rack. Konsol skruvas fast i rack med M6 skruv och korgmutter, minst en på
varje sida. Använd lämplig skruv och mutter för rack. Skruv och mutter ingår ej.
Nr Förklaring
1 Enhenten skruvas fast i 19" rack.
3.2. Montering
4. INKOPPLING
Redundancy Panel 1HE drivs av påkopplade nätaggregat (Power supply 24V 15A 1U. Anslut 24 V last
på Last 1-4.
5
SV
5. KOPPLA IHOP MED POWER SUPPLY 24BV 15A 1U
Tabell 1. Koppla ihop Redundancy panel 1U med Power supply 24V 15A 1U
Nr Förklaring
1 Koppla in första Power supply 24V 15A 1U på Input 1.
2 Koppla in andra Power supply 24V 15A 1U på Input 2.
3 Koppla in tredje Power supply 24V 15A 1U på Input 3. Se input 3 [6]I
5.1. Input 3
VIKTIGT
Detta avsnitt gäller endast om tre Power supply 24V 15A 1U skall användas med
Redundancy panel 1U.
Skall tre Power supply 24V 15A 1U användas skall bygel på Input 3 avlägsnas.
Skall två Power supply 24V 15A 1U användas tillsammans med Redunandcy panel 1U skall jumper,
(röd cirkel) vara monterad (sitter monterad från fabrik). Skall tre Power supply 24V 15A 1U skall jumper,
(röd cirkel) ej vara monterad.
Skruva av locket och justera bygel.
6
SV
Skruva av locket och justera bygel.
Tag bort jumper vid användning av tre Power supply 24V 15A 1U.
VARNING
Enheten får ej vara spänningssatt vid bygling.
6. ANSLUT LAST
24 V last ansluts visa snabbkontakt. [4]
6.1. Larmfunktioner
Dubblerat summalarm: Larm vid bortfall av spänning från nätaggregat efter lastsäkring.
7. ANSLUT LARM
Larm ansluts på baksidan. NO/CO/NC. Använd valfri anslutning, larmen är dubblerade.
Summalarm: larm vid bortfall av spänning från nätaggregat ett, två och tre (beroende på vilka som är
inkopplade), utlöst lastsäkring 1, 2 ,3 och 4, (beroende på vilka som är anslutna).
7
SV
8. DRIFTSÄTTNING
Efter inkoppling skall uppstart ske i följande steg:
1. Koppla till nätaggregat (bör ej vara spänningssatta vid installation) och last.
2. Kontrollera att säkring(ar) på framsida är på ON.
3. Spänningssätt elnät.
4. Enheten fungerar normalt då indikeringsdiod lyser med fast grönt sken.
9. PANELFÖRKLARING
Tabell 2.
LED för Status Förklaring
Alarm Släckt Normaldrift.
Alarm Rött Larm för PSU Error / fel på eller utlös lastsäkring.
PSU 1-3 Grön Normaldrift- Power supply 24V 15A 1U är inkopplat.
PSU 1-3 Släckt Fel på Power supply 24V 15A 1U.
Load 1-4 Grön Normaldrift.
Load 1-4 Släckt Lastsäkring har löst ut.
10. REGELVERK OCH CERTIFIERINGAR
10.1. Krav som produkten uppfyller
EMC: EMC Direktivet 2014/30EU
El: Lågspänningsdirektivet: 2014/35/EU
CE: CE direktivet enligt:765/2008
11. TEKNISKA DATA
Tabell 3. Kretskort Redundans 19R2
Info Förklaring
Artikelbenämning Kretskort Redundans 19R2
Strömförsörjning Produkten drivs av påkopplade nätaggregat (Power supply 24V 15A 1U).
Lastutgångar Fyra stycken, --/++
Ingångar Tre stycken, -- / ++ snabbkontakt.
8
SV
Info Förklaring
Larm Dubbla summalarm: larm vid bortfall av spänning från nätaggregat ett, två och tre (beroende på vilka som är
inkopplade), utlöst lastsäkring 1, 2 och 3, (beroende på vilka som är anslutna).
Säkringar (last). Automatsäkringar 10 A
12. TEKNISKA DATA KAPSLING
12.1. Tekniska data 1U
Info Förklaring
Namn 1U
Kapslingsklass IP 20
Mått Höjd: 44 mm, bredd: 244 mm, djup: 280 mm.
Höjdenheter 1
Montering 19" rack
Omgivningstemperatur +5 °C - +40 °C. För bästa batterilivslängd: +15 °C till +25 °C.
Omgivning Miljöklass 1, inomhus. 20% ~ 90% relativ fuktighet
Material Pulverlackerad plåt
Färg Svart
Kabelgenomföringar, antal 8
13. GARANTI, SUPPORT, TILLVERKNINGSLAND OCH
URSPRUNGSLAND
13.1. Garanti
Produkten har två års garanti, från inköpsdatum (om inget annat avtalats). Kostnadsfri support under
garantitiden nås på suppor[email protected] eller telefon, 031-34 00 230. Ersättning för res- och eller
arbetstid i samband med lokalisering av fel, installerande av reparerad eller utbytt vara ingår ej i
garantin. Kontakta Milleteknik för mer information. Milleteknik ger support under produktens livslängd,
dock som längst 10 år efter inköpsdatum. Byte till likvärdig produkt kan förekomma om Milleteknik
bedömer att reparation inte är möjlig. Kostnader för support tillkommer efter det att garantitiden har gått
ut.
13.2. Tillverkningsland
Sverige
13.3. Tillverkare
Designad och producerad av Milleteknik AB
9
SV
14. PRODUKTENS LIVSLÄNGD, MILJÖPÅVERKAN OCH
ÅTERVINNING
Produkten är designad och konstruerad för lång livslängd vilket minskar miljöpåverkan. Produktens
livslängd (förutom slitagedelar) är beroende på, bland annat miljöfaktorer, främst omgivningstemperatur,
oförutsedd belastning på komponenter som blixtnedslag, yttre åverkan, handhavandefel, med flera.
Produkter återvinns genom att lämnas till närmaste återvinningsstation eller sändas åter till tillverkare.
Kontakta din distributör för mer information. Kostnader som uppkommer i samband med återvinning
ersätts ej.
15. OM DETTA DOKUMENT
Dokumentets artikelnummer: 350-122
Detta dokument kan ändras utan föregående meddelande.
Alla uppgifter publiceras med reservation för tryckfel.
16. ADRESS OCH KONTAKTUPPGIFTER
Milleteknik AB
Ögärdesvägen 8 B
433 30 Partille
Sverige
031-340 02 30
www.milleteknik.se
10
SV
Table of Contents
1. About ...................................................................................................................................... 11
2. Component overview ................................................................................................................ 12
3. Enclosures .............................................................................................................................. 13
3.1. Installation in 19" rack .................................................................................................... 13
3.2. Mounting ...................................................................................................................... 13
4. Connection .............................................................................................................................. 13
5. Connect with Power supply 24BV 15A 1U .................................................................................. 14
5.1. Input 3 .......................................................................................................................... 14
6. Connect load ........................................................................................................................... 15
6.1. Alarm functions ............................................................................................................. 15
7. Connect alarm ......................................................................................................................... 15
8. Commissioning ........................................................................................................................ 16
9. Panel explanation ..................................................................................................................... 16
10. Regulations and certifications ................................................................................................. 16
10.1. Requirements that the product meets ........................................................................... 16
11. Technical data ........................................................................................................................ 16
12. Technical data enclosures ....................................................................................................... 17
12.1. Technical data 1U ........................................................................................................ 17
13. Warranty, support, country of manufacture and country of origin ................................................ 17
13.1. Warranty ..................................................................................................................... 17
13.2. Country of manufacture ............................................................................................... 17
13.3. Designed and produced by: Milleteknik AB .................................................................... 17
14. Product life cycle, environmental impact and recycling .............................................................. 18
15. About this document ............................................................................................................... 18
16. Address and contact details .................................................................................................... 18
1. ABOUT
Redundancy Panel 1U is a rack-mounted unit for power control of Power supply 24V 15A 1UE or battery
backups from Milleteknik. Redundancy Panel 1U has three (3) inputs, which means that it is possible to
connect up to three (3) power supplies (Power supply 24V 15A 1U). If two of the three power supplies
(Power supply 24V 15A 1U) / battery backups stop working as a power source for the system, the third
and last functioning power supply covers. Redundancy Panel 1U alerts if one of the power sources
stops working or in the event of a load fuse failure.
Area of use: Where there is a need for redundancy in the 24 V power supply.
11
EN
READ THIS FIRST!
If possible, leave 100 mm of free space.
The system is intended for use in a controlled indoor environment.
Only authorized persons should install and maintain the system.
It is the installer's responsibility to ensure that the system is suitable for its intended
use.
Documents accompanying the system must be kept in or in its immediate vicinity.
Ventilation should not be covered. Mains voltage should be disconnected during instal-
lation.
All information subject to change.
Upon installation of this product, the installer acknowledges and accepts the limitations
of this product as described in this manual.
2. COMPONENT OVERVIEW
Figure 1. Front
No Explanation
1 LED for load and connected Power supply 24V 15A 1U
2 Load fuses
Figure 2. Back
12
EN
No Explanation
1 Double sum alarm, NO/COM/NC+NO/COM/NC. Sum alarm: alarm in case of loss of voltage from power supply (Power
supply 24V 15A 1U) one, two and three (depending on which are connected), tripped load fuse 1, 2 and 3, (depending
on which are connected).
2.1-2.4 Load 1-4, -- / ++
3.1-3.3 Connection of Power supply 24V 15A 1U
3. ENCLOSURES
3.1. Installation in 19" rack
The unit must be mounted in a 19" rack. Bracket is screwed into rack with M6 screw and basket nut, at
least one on each side. Use the appropriate screw and nut for the rack. Screw and nut not included.
No . Explanation
1 The unit is screwed into a 19" rack.
3.2. Mounting
4. CONNECTION
Redundancy Panel 1HE is powered by connected power supplies (Power supply 24V 15A 1U. Connect
24 V load to Load 1-4.
13
EN
5. CONNECT WITH POWER SUPPLY 24BV 15A 1U
Table 1. Connect Redundancy panel 1U with Power supply 24V 15A 1U
No Explanation
1 Connect the first Power supply 24V 15A 1U to Input 1.
2 Connect the other Power supply 24V 15A 1U to Input 2.
3 Connect the third Power supply 24V 15A 1U to Input 3. See input 3 [14]IN
5.1. Input 3
IMPORTANT
This section only applies if three Power supply 24V 15A 1U are to be used with
Redundancy panel 1U.
If three Power supplies 24V 15A 1U are to be used, the jumper on Input 3 must be removed.
If two Power supply 24V 15A 1U are to be used together with the Redunandcy panel 1U, the jumper
(red circle) must be fitted (it is fitted from the factory). Should three Power supply 24V 15A 1U jumper,
(red circle) should not be mounted.
Unscrew the cover and adjust the bracket.
14
EN
Unscrew the cover and adjust the bracket.
Remove jumper when using three Power supply 24V 15A 1U.
WARNING
The unit must not be energized when bridging.
6. CONNECT LOAD
24 V load is connected show quick contact. [12]
6.1. Alarm functions
Double total alarm: Alarm in the event of loss of voltage from the power supply after load protection.
7. CONNECT ALARM
Alarm is connected on the back. NO/CO/NC. Use any connection, the alarms are duplicated.
Total alarm: alarm in the event of loss of voltage from power supplies one, two and three (depending on
which are connected), tripped load fuse 1, 2, 3 and 4, (depending on which are connected).
15
EN
8. COMMISSIONING
After connection, startup must take place in the following steps:
1. Connect power supply (should not be live during installation) and load.
2. Check that the fuse(s) on the front is ON.
3. Voltage set mains.
4. The device works normally when the indicator diode lights up with a solid green light.
9. PANEL EXPLANATION
Table 2.
Led for Status Explanation
Alarm Turned off Normal operation.
Alarm RED Alarm for PSU Error / fault on or triggered load fuse.
PSUs 1-3 Green Normal operation - Power supply 24V 15A 1U is connected.
PSUs 1-3 Turned off Error on Power supply 24V 15A 1U.
Loads 1-4 Green Normal operation.
Loads 1-4 Turned off Load fuse has tripped.
10. REGULATIONS AND CERTIFICATIONS
10.1. Requirements that the product meets
EMC: EMC Directive 2014 / 30EU
Electricity: Low voltage directive: 2014/35 / EU
EN 60950-1
CE: CE directive according to: 765/2008
11. TECHNICAL DATA
Table 3. Circuit board Redundancy 19R2
Info Explanation
Article name Circuit board Redundancy 19R2
Power supply The product is powered by connected power supplies (Power supply 24V 15A 1U).
Load outputs Four pieces, --/++
Entrances Three pieces, -- / ++ quick connector.
16
EN
Info Explanation
Alarm Double total alarm: alarm in case of loss of voltage from power supplies one, two and three (depending on which
are connected), tripped load fuse 1, 2 and 3, (depending on which are connected).
Fuses (load). Automatic fuses 10 A
12. TECHNICAL DATA ENCLOSURES
12.1. Technical data 1U
Info Explanation
Name 1U
Enclosure class IP 20
Measure Height: 44 mm, width: 244 mm, depth: 280 mm.
Height units 1
Mounting 19 "rack
Ambient temperature + 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C.
Environment Environmental class 1, indoors. 20% ~ 90% relative humidity
Material Powder coated sheet metal
Color Black
Cable glands, number 8
13. WARRANTY, SUPPORT, COUNTRY OF MANUFAC-
TURE AND COUNTRY OF ORIGIN
13.1. Warranty
The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support
during the warranty period can be reached at suppor[email protected] or telephone, +46 31-34 00 230.
Compensation for travel and / or working hours in connection with locating faults, installing repaired or
replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik pro-
vides support during the product's lifetime, however, no later than 10 years after the date of purchase.
Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support
costs may (at Milleteknik's discretion) occour after the warranty period has expired.
13.2. Country of manufacture
Country of manufacture / country of origin is Sweden. For more information, contact your seller.
13.3. Designed and produced by: Milleteknik AB
Designed and produced by Milleteknik AB
17
EN
14. PRODUCT LIFE CYCLE, ENVIRONMENTAL IMPACT
AND RECYCLING
The product is designed and constructed for a long service life, which reduces the environmental
impact. The product's service life depends on, among other things, environmental factors, mainly ambi-
ent temperature, unforeseen load on components such as lightning strikes, external damage, handling
errors, and more. Products are recycled by being handed over to the nearest recycling station or sent
back to the manufacturer. Contact your distributor for more information. Costs that arise in connection
with recycling are not reimbursed.
15. ABOUT THIS DOCUMENT
Article number of the document:
This document is subject to change without prior notice.
All information is published with reservation for printing errors.
16. ADDRESS AND CONTACT DETAILS
Milleteknik AB
Ögärdesvägen 8 B
S-433 30 Partille
Sweden
+46 31 340 02 30
www.milleteknik.se
18
EN
This page is intentionally left blank.
This page is intentionally left blank.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

milleteknik 350-122 Owner's manual

Type
Owner's manual

The milleteknik 350-122 Redundancy Panel 1U is a rack-mounted unit for power control of Milleteknik's Power supply 24V 15A 1U or battery backups. It has three inputs, allowing up to three power supplies to be connected. If two of the three power supplies fail, the third and final functioning power supply will cover the system. Redundancy Panel 1U alarms when any of the power sources fail or in case of load fuse faults.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages