Haier MRV II AV26NMVERA Startup Manual

Category
Split-system air conditioners
Type
Startup Manual
MRV II
Aug. 2008
START UP GUIDE
R410A HEAT PUMP 50HZ
SYJS-005-08REV.0
AV08NMVERA
AV10NMVERA
AV12NMVERA
AV14NMVERA
AV16NMVERA
AV18NMVERA
AV20NMVERA
AV22NMVERA
AV24NMVERA
AV26NMVERA
AV28NMVERA
AV28NMVERA
AV30NMVERA
AV32NMVERA
AV34NMVERA
AV36NMVERA
AV38NMVERA
AV40NMVERA
AV42NMVERA
AV44NMVERA
AV46NMVERA
AV48NMVERA
GRUPAd.o.o.
CONTENTS
1. Lineup of MRVII system
1.1 Indoor/outdoor models
1.2 External appearance
2. Wiring work
2.1 Confirm the power cables' connection of each indoor unit
2.2 Confirm the communication wires' connection of each indoor unit
2.3 Confirm the wired controller wires connection of each indoor unit
2.4 Confirm the wiring connections when in central control
2.5 Confirm the central controller setting
2.6 Confirm the power cables' connection of each outdoor
2.7 Confirm the P, Q connection and the communication among outdoors A,
B, C connection
2.8 Confirm the indoor control type
2.9 Confirm the indoor communication address when in central control: SW03
on indoor PCB
2.10 Confirm the indoor central control address when in central control: SW02
on indoor PCB
2.11 Confirm the indoor group control address when in group control: SW01
on indoor PCB
2.12 Confirm the outdoor pipe length switch on outdoor PCB
2.13 Confirm the outdoor capacity over match switch setting on outdoor PCB
2.14 Confirm the outdoor unit address: the master unit must be No. 1
2.15 Confirm the outdoor units searching when multi units in combination
2.16 Confirm the outdoor capacity
2.17 Rotary switch function
3. Indoor unit control
3.1 Indoor PCB
3.2 Wired controller
3.3 Infrared controller
4. Outdoor control
5. Dip switch setting when out of factory
6. Wiring of indoor and outdoor
3
3
4
6
7
8
9
11
12
13
13
14
14
15
16
17
17
18
18
19
20
25
25
26
29
35
38
39
GRUPAd.o.o.
03
1.1 Indoor/outdoor models
Indoor units
Type
Model
4-way cassette type
PB-700IB
AB*MCERA
AB*MEERA
092 122 162
182
242
282 302
382 482
Low ESP duct type
AD*MLERA
072
092
122 162
182
242
Med ESP duct type AD*MMERA
182
242
302
382 482
High ESP duct type AD*MHERA
182
242 282
Convertible type
182
242
382 482162
Wall mounted type
AS*MC/AERA
072
092
122 162
182
282
302 382
Console type
AF*MAERA
072
092
122
Outdoor units
Type
AV*MVERA
Model
10HP
10N
12HP
12N
14HP
14N
16HP
16N
18HP
18N
20HP
20N
22HP
22N
24HP
24N
8HP
08N
28HP
28N
30HP
30N
482
092
122
Type
AV*MVERA
Model
34HP
34N
36HP
36N
38HP
38N
40HP
40N
42HP
42N
44HP
44N
46HP
46N
48HP
48N
32HP
32N
722 962
AB*MCERA
182
242
282 302
382 482
4-way cassette type
PB-950JB
4-way cassette type
PB-950IB
1. Lineup of MRVII system
182
AC*MC/FERA
242
GRUPAd.o.o.
04
AV08NMVERA
1.2 External appearance
Outdoor
AV16NMVERA
AV18/20NMVERA
AV22/24/26NMVERA
AV28/30/32NMVERA AV34/36NMVERA
AV38/40/42NMVERA AV44/46/48NMVERA
AV10NMVERA AV14NMVERAAV12NMVERA
GRUPAd.o.o.
05
4-WAY CASSETTE TYPE / PB-700IB
Indoor
AB092MCERA
AB122MCERA
AB162MCERA
AB182MEERA
AB242MEERA
AB282MEERA
AB302MEERA
AB382MEERA
AB482MEERA
4-WAY CASSETTE TYPE / PB-950IB
LOW ESP DUCT TYPE
AD072MLERA
AD092MLERA
AD122MLERA
AD162MLERA
AD182MLERA
AD242MLERA
AD182MMERA
AD242MMERA
AD282MMERA
MED ESP DUCT TYPE
AD302MMERA
AD382MMERA
AD482MMERA
HIGH ESP DUCT TYPE
AD182MHERA
AD242MHERA
AD282MHERA
AD302MHERA
AD382MHERA
AD482MHERA
CONSOLE TYPE
AC092MCERA
AC122MCERA
AC162MCERA
AC182MCERA
AC242MCERA
CONVERTIBLE TYPE
AC382MFERA
AC482MFERA
HRV(heat reclaimed ventilation)
ERV0150ANN
ERV0200ANN
ERV0260ANN
ERV0350ANN
ERV0800ANN
ERV1000ANN
ERV1200ANN
ERV1500ANN
WALL MOUNTED TYPE
AB182MCERA
AB242MCERA
AB282MCERA
AB302MCERA
AB382MCERA
AB482MCERA
4-WAY CASSETTE TYPE / PB-950JB
AD722MHERA
AD962MHERA
AF072MAERA
AF092MAERA
AF122MAERA
AF182MAERA
AS072MCERA
AS092MCERA
AS122MCERA
AS162MCERA
AS182MCERA
AS242MAERA
GRUPAd.o.o.
06
2. Wiring work
GRUPAd.o.o.
07
2.1 Confirm the power cables' connection of each indoor unit
Make sure the position and the connection of live wire (L) and neutral wire (N) correct.
electric control box of indoor
except for wall mounted unit
electric control box of wall
mounted unit
GRUPAd.o.o.
08
2.2 Confirm the communication wires' connection of each indoor unit
Make sure the position and the connection of P, Q cables correct.
Confirm P cables of all indoors are the same color, so Q cables do.
electric control box of indoor
except for wall mounted unit
electric control box of wall
mounted unit
GRUPAd.o.o.
09
2.3 Confirm the wired controller wires connection of each indoor unit
Master control type: connect all wires A, B, C.
Slave control type: only connect wires B and C.
1 2 3
1 2 3 1 2 3
1 2 3
1 2 3
Indoor 16Indoor 15Indoor NIndoor 2Indoor 1
Wired controller Wired controller Wired controller Wired controller Wired controller
(master unit)
A B C
Wired controller
Control wiring of
wired controller,
polar.
CN22 on indoor PCB
Note: When in group control type, the slave unit can not use individual wired controller.
GRUPAd.o.o.
10
2.3 Confirm the wired controller wires connection of each indoor unit
Make sure the position of SW1 and SW20-1 on wired controller
Old type wired controller is SW20-1; new type wired controller is SW1.
Note: 1. D1, D2 are the diode, if the two terminals are disconnected, the state is "1"; if the two terminals
are connected with a jumper, the state is "0".
2. Only when two controllers control one indoor unit, one of wired controllers can be set as slave controller,
and set SW20-[1] as ON, the others keep the state when out of factory, set SW20-[1] as OFF.
3. The old type: there are resistors of J03 and J06 beside the dip switch.
old
J02
J06
J07
J03
selection item
state
function description
changeover of
controller type
0
1
0
1
0
1
0
1
selection of room
temp. sensor
auto restart
selection of room
temp. display
set as simple controller
set as standard controller
use room temp. sensor on wired controller
not use room temp. sensor on wired controller
without auto restart
with auto restart
display room temp.
not display room temp.
new
D9
D12
D15
D14
old
SW20-[1]
SW20-[2]
D1
D2
selection item
state
function description
changeover of
master/slave controller
ON
OFF
0
1
0
1
shorten time function
compulsory defrost
set as slave controller
set as master controller
indoor shorting time
without shorten time
send to compulsory defrost signal
normal operation
ON
OFF
C or F
F
C
new
SW[1]
SW[2]
JP8
JP7
GRUPAd.o.o.
11
2.4 Confirm the wiring connection when in central control
Condition 1: ICR01+IGU04
indoor electric control box
ICR01
IGU04
P, Q
L N
220~
B-B
B-A
Condition 2: ICR01 only
indoor electric control box
ICR01
L N
220~
P, Q
GRUPAd.o.o.
12
2.5 Confirm the central controller setting
O N
1 23 4
Dip switch setting meaning:
The first bit: central bus line selection, 0: indoor bus line; 1: central bus line
The second bit: master/slave central controller selection, 0: master central controller; 1: slave central
controller
The third, fourth bit: control range, 00: 1~64, 01: 65~128, 10: 129~192, 11: 193~256. Every central
controller only can control 64 units, and every unit can include max. 16 indoors, but the central controller
only displays the master indoor state.
00: 1~64 01: 65~128
10: 129~192 11: 193~256
position 1
0: ON
1: OFF
indoor bus line
central bus line
2
master controller
slave controller
3 4
For example:
Select central bus line, master central controller, control range is 00, so the dip switch is 1 0 0 0.
Select indoor bus line, master central controller, control range is 00, so the dip switch is 0 0 0 0.
Note: Indoor address number more than 64 will not display on the first group, and the address number
less than 65 will not display on the second group.
GRUPAd.o.o.
13
2.6 Confirm the power cables' connection of each outdoor
Fix the cables firmly and keep the cables color corresponding.
2.7 Confirm the P, Q connection and the communication among outdoors A, B, C
connection
outdoor electric control box
outdoor electric control box
Only P,Q of master outdoor unit are connected to the indoor unit. Pay attention to the color of P, Q in
accordance.
Keep the color of A, B, C accordant.
GRUPAd.o.o.
14
2.8 Confirm the indoor control type
N. Wired control/remote control selection: SW08-6
SW08-6
1
0
wired control type
remote control type
function
Control method Wired control master unit Wired control slave unit Remote control unit
Socket
/jumper
CN23 short connected disconnected disconnected
CN30 short connected short connected disconnected
CN21 blank blank to remote receiver
SW08-[6] ON ON OFF
signal terminal block A,B,C to B,C to A,B,C not
wired controller wired controller to wired controller
2.9 Confirm the indoor communication address when in central control: SW03 on
indoor PCB
SW03 on indoor PCB
1: ON
0: OFF
GRUPAd.o.o.
15
C. Indoor communication address
SW03 description
[1] [2] [3] [4] [5] [6] [7] [8]
__- 000000central control address=1
__- 000001central control address=2
---- ----
__- 111110central control address=63
__- 111111central control address=64
- 0
set central control address by wired controller
- 1 Forbidden to set address by wired controller
0
1
set address automatically
set address by hand
There are three kinds of address setting method for indoor units: automatical address setting, manual
address setting, wired controller setting. Any one of them can set the address and wired controller setting
type has the highest priority.
2.10 Confirm the indoor central control address when in central control: SW02 on
indoor PCB
SW02 on indoor PCB
1: ON
0: OFF
GRUPAd.o.o.
16
B. Indoor address setting when in central control by central controller: SW02 (only on the master unit).
SW02 description
[1] [2] [3] [4] [5] [6] [7] [8]
__0000000central control address=1
__0000001central control address=2
---- ----
__1111110central control address=127
__1111111central control address=128
0
set central control address by wired controller
1 Forbidden to set address by wired controller
2.11 Confirm the indoor group control address when in group control: SW01 on indoor
PCB
SW01 on indoor PCB
1: ON
0: OFF
SW01
Description
[1] [2] [3] [4] [5] [6] [7] [8]
0
0
--
1
1
0
0
--
1
1
0
0
--
0
1
0
1
--
1
1
--
--
--
--
--
wired controller address=1
wired controller address=2
--
wired controller address=15
wired controller address=16
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
GRUPAd.o.o.
17
2.12 Confirm the outdoor pipe length switch on outdoor PCB
SW4-1
piping length selection
SW4-1 SW4-2
medium piping length, cooling suction pressure:8.01kgf/cm
2
,
heating discharging pressure:28.0kgf/cm
2
00
01
10
11
SW4-2
description
medium piping length
long piping length, cooling suction pressure:7.51kgf/cm
2
,
heating discharging pressure:30.0kgf/cm
2
short piping length, cooling suction pressure:8.53kgf/cm
2
,
heating discharging pressure:26.0kgf/cm
2
1: ON
0: OFF
SW4-1, SW4-2
2.13 Confirm the outdoor capacity over match switch setting on outdoor PCB
0
1
SW4-4
over-match capacity
setting
allowable
forbidden
1: ON
0: OFF
SW4-4
GRUPAd.o.o.
18
2.14 Confirm the outdoor unit address: the master unit must be No. 1.
SW4-6
outdoor unit No.
SW4-7 SW4-8
1
2
3
4
5
6
7
8
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
SW4 - 6, 7, 8 used to set outdoor unit No. and outdoor unit No. lock
1: ON
0: OFF
SW4-6,7,8
SW4-5
2.15 Confirm the outdoor units searching when multi units in combination
SW4-5
0
1
searching outdoor
after being electrified
begin to search outdoor
stop searching outdoor and lock the outdoor quantity
GRUPAd.o.o.
19
2.16 Confirm the outdoor capacity
SW2-1 SW2-2 SW2-3
8HP
10HP
12HP
14HP
16HP
20HP
22HP
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
SW2: 8-bit dip switch
outdoor capacity
18HP
GRUPAd.o.o.
20
2.17 Rotary switch function
SW10
0-15
control description
LED2, LED3, LED4 display air inelt temp. -2 degree displays -02
LED2, LED3, LED4 display air inelt temp. -2 degree displays -02
LED2, LED3, LED4 display valve open angle
LED3, LED4, display indoor capacity, 1.5HP displays 1.5
display indoor failure code; no failure, display 0
LED3, LED4, indoor available, display 1111; indoor unavailable, display ----
function
indoor communication checking
indoor abnormal
indoor capacity
air inlet temp.
indoor gas pipe temp.
indoor EEV open angle
SW11
3
4
5
6
7
8
9
SW9
0
1
2
3
address
1-16
17-32
33-48
49-64
indoor liquid pipe temp.
LED2, LED3, LED4 display air inelt temp. -2 degree displays -02
10-15
pre-set
2.17.1 Check indoor parameters by rotary switch
SW9 SW10
SW11
outdoor PCB
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Haier MRV II AV26NMVERA Startup Manual

Category
Split-system air conditioners
Type
Startup Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI