Introduction i
INTRODUCTION
This manual provides information concerning the operation and installation of BE3-GPR
Generator Protective Relays. To accomplish this, the following is provided.
•
Specifications
•
Functional Description
•
Mounting Information
•
Communications
•
Testing Procedures
WARNING
TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY
QUALIFIED PERSONNEL SHOULD PERFORM THE PROCEDURES
PRESENTED IN THIS MANUAL.
ii Introduction
First Printing: October 1996
Printed in USA
© 1997, 1998, 2000 Basler Electric Co., Highland, IL 62249
January 2000
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER
DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
It is not the intention of this manual to cover all details and variations in
equipment, nor does this manual provide data for every possible contingency
regarding installation or operation. The availability and design of all features and
options are subject to modification without notice. Should further information be
required, contact Basler Electric Company, Highland, Illinois.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, [email protected]
PHONE 618-654-2341 FAX 618-654-2351
Introduction iii
CONTENTS
SECTION 1 GENERAL INFORMATION..........................................................................1-1
Description....................................................................................................1-1
Capabilities...................................................................................................1-1
Basic Stand-Alone Generator Version...................................................1-1
Basic Paralleled Generator Version.......................................................1-1
Optional Protective Functions................................................................1-1
Control Enables......................................................................................1-1
Watchdog Timer.....................................................................................1-1
Indicators ...............................................................................................1-2
Communications ....................................................................................1-2
Outputs.........................................................................................................1-2
Contact Ratings .....................................................................................1-2
Specifications ...............................................................................................1-2
Style Chart....................................................................................................1-6
Timing Overcurrent Characteristic Curves...................................................1-7
SECTION 2 HUMAN-MACHINE INTERFACE (CONTROLS AND INDICATORS)..........2-1
Front Panel Display......................................................................................2-1
Panel Connections .......................................................................................2-2
SECTION 3 FUNCTIONAL DESCRIPTION.....................................................................3-1
General ........................................................................................................3-1
Functional Description..................................................................................3-1
Switching Power Supply.........................................................................3-1
Voltage Sensing And Conditioning.........................................................3-2
Frequency Sensing................................................................................3-2
Current Sensing And Conditioning.........................................................3-2
Control (Pushbutton) Inputs...................................................................3-2
Hardware (Jumper) Inputs.....................................................................3-2
Analog To Digital Converter...................................................................3-2
Microprocessor ......................................................................................3-2
Output Relays ........................................................................................3-4
RS-232 Channel.....................................................................................3-4
LCD Display...........................................................................................3-4
Timing Functions....................................................................................3-4
Software .......................................................................................................3-4
Power-Up Initialization ...........................................................................3-4
Relay Setup And Configuration..............................................................3-5
Remote RS232 Communications And Support ..........................................3-13
Logon...................................................................................................3-13
Logoff...................................................................................................3-13
Programming........................................................................................3-13
Default Settings....................................................................................3-16
Optional Communications Software.....................................................3-16
Hardware Jumper Inputs............................................................................3-17
Program Enable...................................................................................3-17
Fail-Safe Enable...................................................................................3-17
Output Disable .....................................................................................3-17
Trip Reset ............................................................................................3-17
iv Introduction
CONTENTS - Continued
SECTION 4 INSTALLATION...................................................................................................4-1
General................................................................................................................4-1
Mounting..............................................................................................................4-1
Overall Dimensions and Hole Locations (Surface Mounting)..............................4-1
Overall Dimensions and Hole Locations (Semi-Flush Mounting)........................4-2
Connections.........................................................................................................4-3
General .........................................................................................................4-3
Communications Link....................................................................................4-3
RS-232 Serial Communications Cable Connections.....................................4-3
System..........................................................................................................4-4
Connections For Three-Phase Rotations......................................................4-4
BE3-GPR, NGF, Inputs And Outputs ..................................................................4-5
BE3-GPR, TOC, Inputs And Outputs ..................................................................4-6
BE3-GPR Typical DC Control Circuit ..................................................................4-6
BE3-GPR (NGF) S-2 With Single-Phase, Line-To-Line Sensing and Conditioning,
and 5A CT.....................................................................................................4-7
BE3-GPR (NGF) S-2 With Three-Phase, Line-To-Line Sensing and 1A CT.......4-8
BE3-GPR (NGF) P-2 With Single-Phase, Line-To-Line Sensing and Conditioning,
and 5A CTs...................................................................................................4-9
BE3-GPR (NGF) P-2 With Three-Phase, Three Wire, Line-To-Line Sensing and
5A CTs........................................................................................................4-10
BE3-GPR (NGF) P-2 With Three-Phase, Four Wire, Line-To-Neutral Sensing and
Conditioning, and 5A CTs...........................................................................4-11
BE3-GPR (TOC) S-1 With Single-Phase, Line-To-Line Sensing and Conditioning,
and 5A CT...................................................................................................4-12
BE3-GPR (TOC) S-1 With Three-Phase, Line-To-Line Sensing and 1A CT.....4-13
BE3-GPR (TOC) P-1 With Single-Phase, Line-To-Line Sensing and Conditioning,
and 5A CTs.................................................................................................4-14
BE3-GPR (TOC) P-1 With Three-Phase, Three Wire, Line-To-Line Sensing and
5A CTs........................................................................................................4-15
BE3-GPR (TOC) P-1 With Three-Phase, Four Wire, Line-To-Neutral Sensing and
Conditioning, and 5A CTs...........................................................................4-16
SECTION 5 NGF COMMUNICATIONS ..................................................................................5-1
Introduction..........................................................................................................5-1
Installation............................................................................................................5-1
Operating Requirements...............................................................................5-1
Installing the Program on Your PC Using Windowsï›› 3.1 ............................5-1
Installing the Program on Your PC Using Windows95...............................5-1
Configuring the System.................................................................................5-1
Initializing Communications with the BE3-GPR...................................................5-2
Initialize Communications .............................................................................5-2
Change Settings..................................................................................................5-4
Sending, Getting, and Displaying Data................................................................5-4
Send To Relay ..............................................................................................5-4
Get From Relay.............................................................................................5-4
Display Data..................................................................................................5-4
Saving, Printing, and Opening Files ....................................................................5-5
File Save.......................................................................................................5-5
File Print........................................................................................................5-5
File Open.......................................................................................................5-6
Introduction v
CONTENTS - Continued
SECTION 5 NGF COMMUNICATIONS - Continued
Metering...............................................................................................................5-6
Enable Metering............................................................................................5-6
Metering Screen............................................................................................5-7
Terminating Communications with the BE3-GPR................................................5-8
SECTION 6 TOC COMMUNICATIONS ..................................................................................6-1
Introduction..........................................................................................................6-1
Installation ...........................................................................................................6-1
Operating Requirements...............................................................................6-1
Installing the Program on Your PC Using Windowsï›› 3.1 ............................6-1
Installing the Program on Your PC Using Windows95...............................6-1
Configuring the System.................................................................................6-1
Initializing Communications with the BE3-GPR...................................................6-2
Initialize Communications .............................................................................6-2
Change Settings..................................................................................................6-4
Sending, Getting, and Displaying Data................................................................6-4
Send To Relay ..............................................................................................6-4
Get From Relay.............................................................................................6-4
Display Data..................................................................................................6-4
Saving, Printing, and Opening Files ....................................................................6-5
File Save.......................................................................................................6-5
File Print........................................................................................................6-5
File Open.......................................................................................................6-6
Metering...............................................................................................................6-6
Enable Metering............................................................................................6-6
Metering Screen............................................................................................6-7
Terminating Communications with the BE3-GPR................................................6-7
SECTION 7 TESTING.............................................................................................................7-1
General................................................................................................................7-1
Equipment Required............................................................................................7-1
Test Setup...........................................................................................................7-1
Protective Functions............................................................................................7-1
Overvoltage Trip (Line-To-Neutral Voltage Sensing)....................................7-1
Undervoltage Trip .........................................................................................7-2
Overfrequency Trip (Line-To-Neutral Frequency Sensing)...........................7-2
Underfrequency 1 And Underfrequency 2 Trips ...........................................7-2
Phase Balance Trip.......................................................................................7-2
Overvoltage Trip (Line-To-Line Voltage Sensing).........................................7-2
Overfrequency Trip (Line-To-Line Frequency Sensing) ...............................7-3
Neutral Ground Fault Trip (5A NGF CT Current Sensing)............................7-3
Overcurrent Trip (5A, A, B, or C CT Current Sensing) .................................7-3
Reactive Current Trip (5A CT B Current Sensing)........................................7-3
Reverse Power Trip (5A CT B Current Sensing)..........................................7-3
Reverse Power Trip (1A CT B Current Sensing)..........................................7-4
Neutral Ground Fault Trip (1A NGF CT Current Sensing)............................7-4
Overcurrent Trip (1A, A, B, or C CT Current Sensing) .................................7-4
Sync-Check Functions ........................................................................................7-4
vi Introduction
CONTENTS - Continued
SECTION 7 TESTING - Continued
Sync-Check...................................................................................................7-4
Dead Bus ......................................................................................................7-5
Contact Sensing ..................................................................................................7-5
Trip Reset......................................................................................................7-5
Failsafe Enable .............................................................................................7-6
Output Disable ..............................................................................................7-6
Program Enable............................................................................................7-6
SECTION 8 MAINTENANCE ..................................................................................................8-1
General................................................................................................................8-1
Troubleshooting...................................................................................................8-1
SECTION 9 MANUAL CHANGE INFORMATION...................................................................9-1
Changes..............................................................................................................9-1
Summary of Changes..........................................................................................9-1
General Information 1-1
SECTION 1
•
••
•
GENERAL INFORMATION
DESCRIPTION
BE3-GPRs (Generator Protective Relays) use microprocessor based technology to provide total generator
protection in a single package. This microprocessor design allows for exact setpoint adjustment and
precise generator system protection. BE3-GPRs allow for quick and simple setup via a personal computer
or front panel human machine interface. Because the BE3-GPRs have low sensing burdens, no
dedicated PTs and CTs are required. Optional protective features allow for customizing the BE3-GPRs to
meet your system requirements. The BE3-GPR provides multiple functions in a single case -- a
combination that yields significant savings in installation and setup.
CAPABILITIES
BE3-GPRs are packaged in metal cases for improved electromagnetic compatibility. They are moisture
and dust resistant. Each device provides protection for stand-alone, isolated generating systems or
paralleled generating systems. Models with the following protective functions are available.
Basic Stand-Alone Generator Version
•
27/59 Under/Over voltage protection
•
81O/U Under/Over frequency protection
•
81U Underfrequency
Basic Paralleled Generator Version:
•
27/59 Under/Over voltage protection
•
81O/U Under/Over frequency protection
•
81U Underfrequency
•
32R Reverse power protection
Optional Protective Functions
•
51V Time Overcurrent
•
51N Neutral fault current protection
•
40 Reactive current (loss of excitation) protection (Paralleled Version Only)
•
47 Phase balance protection
•
25 Sync-check/dead bus closing (Paralleled Version Only)
Model combinations depend on the selected style.
Control Enables
Four hardware jumpers enable the following special protective features. Each feature is continuously
monitored by software within the microprocessor. They are:
•
Trip reset
•
Program enable
•
Failsafe enable
•
Output enable
Watchdog Timer
The watchdog timer monitors the microprocessor for proper software and microprocessor operation. If
there is an occurrence that inhibits proper operation, the watchdog timer de-energizes the watchdog timer
output contacts to annunciate the problem to the system.
General Information
1-2
Indicators
There are two indicators mounted on the front panel of the relay. The SYNC LED (present only in the
BE3-GPR P units with the sync-check option) indicates that the generator and bus inputs are within the
synchronization window set by the user. The liquid crystal display (LCD) is the main human-machine
interface and has capabilities to show any and all information necessary for programming and interpreting
relay actions.
Communications
Communication capability provides a remote serial interface between the relay and a computer. Basler
Electric offers a software package that enhances communications to BE3-GPRs. This software package
also provides a real time metering capability for monitoring generator voltage, frequency, current, watts,
power factor, and volt-amperes.
OUTPUTS
There are eleven isolated form C output contact arrangements. One for each of the nine protective
functions, the sync-check/dead bus function, and the watchdog timer.
SPECIFICATIONS
Timing Accuracy:
(All Functions Except 51V)
Accuracy is ±1% or ±50 milliseconds, whichever is greater.
27
Undervoltage
Trip point and reset set points are settable from 70 to 600 Vac in one volt
steps, and trip timing is adjustable from 0 to 20 seconds in one second
steps. Accuracy is ±2%. Repeatability is ±1.0 %.
59
Overvoltage
Trip point and reset set points are settable from 70 to 600 Vac in one volt
steps, and trip timing is adjustable from 0 to 20 seconds in one second
steps. Accuracy is ±2%. Repeatability is ±1.0 %.
81O
Overfrequency
Trip point and reset points are settable from 35 to 75 hertz in 0.1 hertz
steps. Trip timing is adjustable from 0 to 20 seconds in steps of one
second. Accuracy is ±0.025 Hz. Repeatability is ±0.01 Hz.
81U
Underfrequency
Trip point and reset points are settable from 35 to 75 hertz in 0.1 hertz
steps. Trip timing is adjustable from 0 to 20 seconds in one second
steps. Accuracy is ±0.025 Hz. There are two independent 81U functions
available. Repeatability is ±0.01 Hz.
32R
Reverse Power
Measures three-phase reverse power. Trip point and reset points are
settable from 50 to 999 watts in one watt steps. Trip timing is adjustable
from 0 to 20 seconds in one second steps. At power factors equal to or
greater than the absolute value of 0.5, and at 25
°
C, accuracy is ±2% or
±10W whichever is greater. At temperatures from -25 to 60
°
C, accuracy
is ±5% or ±10W whichever is greater. This function is available only in
the paralleled generator version. Repeatability is ±1.0 %.
General Information 1-3
25
Sync-Check With Dead Bus
Phase angle is settable from 2 to 20 degrees in one degree steps, and
voltage difference is adjustable from 1 to 100 Vac in one volt steps. Both
the time delay (which is variable from 0.2 to 2 seconds in 0.1 second
steps), and the slip frequency (which is variable from 0.1 hertz to 1.0
hertz in 0.1 hertz steps) qualify the in-sync condition. Dead Bus is
settable from 10 to 50 volts in increments of one volt. Accuracy is: Delta
Voltage — ±2% or ±1 V, whichever is greater throughout operating range
of 5 to 100 volts; Delta (slip) Frequency — ±0.02 Hz throughout operating
range of 0.1 to 0.5 Hz, Delta phase angle — ±0.5 degrees. This function
is an option available only on the paralleled generator version of the
relay. Repeatability is ±1.5 %.
47
Phase Balance
Phase balance measures the maximum voltage difference between any
two line-to-line phases. Trip point and reset points are settable from 5 to
100 volts in 1 volt steps. The timing is settable from 0 to 20 seconds in
one second steps. Accuracy is ±3% or ±2 V, whichever is greater
throughout operating range of 5 to 100 volts. Repeatability is ±1.0 %.
40
Loss of Excitation
Measures the reactive current into the generator. In the five ampere CT
setting, trip point and reset points are settable from 0.15 to 2.5 amperes
in 0.01 ampere steps. In the one ampere CT setting, trip point and reset
points are settable from 0.03 to 0.5 amperes in 0.01 ampere steps. Trip
timing is adjustable from 0 to 20 seconds in one second increments.
Accuracy is ±3.5% or ±0.05 ampere, whichever is greater throughout
operating range of 0.15 to 2.5 amperes. This is an option available only
in the paralleled version. Repeatability is ±1.0 %.
51N
Neutral Ground Fault (NGF)
Provides protection from ground fault occurrence by measuring RMS
neutral currents. In the five ampere CT configuration, trip point and reset
points are settable from 0.2 to 3 amperes in 0.01 ampere steps. Trip
point and reset points are settable from 0.04 to 0.6 amperes in 0.01
amperes increments, in the one ampere CT configuration. Trip timing is
adjustable from 0 to 2 seconds in 0.1 second steps. Accuracy is ±2% or
±0.01A whichever is greater throughout operating range of 0.2 to 3.0
amperes.
51V
Time Overcurrent (TOC) with
Voltage Restraint
Provides protection from overcurrent occurrence by measuring RMS line
currents. In the five ampere CT configuration, trip point and reset points
are settable from 0.1 to 9.99 amperes in 0.01 ampere steps. Trip point
and reset points are settable from 0.10 to 2.00 amperes in 0.01 amperes
increments, in the one ampere CT configuration. Accuracy is ±2.5% or
±0.05A whichever is greater throughout operating range of 0.1 to 5.0
amperes.
Time-Current Characteristic
Curves
Sixteen inverse time functions and one fixed time function can be selected.
Characteristic curves for the inverse and definite time functions are defined
by the following equation.
T
AD
MC
BD K
T
N
=
â‹…
−
+â‹…+
T
T
= Time to trip when M
≥
1
D = TIME DIAL setting (0.0 to 9.9)
M = Multiple of PICKUP setting (0 to 40)
A, B, C, N, K = Constants for the particular curve
See Table 1-1 for the time characteristic curve constants.
General Information
1-4
Timing Accuracy
(51V Functions)
Within ±5% or 50 mSec, whichever is greater for time dial settings of D
greater than 0.1 and multiples of 2 to 40* times the pickup setting but not
over 30 A for 5 A CT units or 6 A for 1 A CT units.
* 3-40 times pickup for the A-curve.
Voltage Restraint: Voltage restraint compares the sensed voltage with the nominal voltage
level. A decrease of the sensed voltage (between 100% and 25% of
nominal) results in a proportional decrease of the time overcurrent pickup
point. When the sensed voltage falls below 25% of nominal, the time
overcurrent pickup point will be 25% of the actual time overcurrent setting
(see Figure 1).
25%
0%
50%
100%
75%
25% 100%50% 75%
Sensed Voltage
Percent of Pickup Setting
D2224-21.vsd
01-31-00
Figure 1-1. Voltage Restraint
Power Supply: Power input (battery)
12 Vdc nominal systems (8 to 16 Vdc)
24 Vdc nominal systems (16 to 32 Vdc)
Power dissipated is 6.5 watts
Inputs: Voltage Sensing Inputs
100 to 480 Vac nominal, 50 to 60 hertz, @ less than 1 VA per phase
1.2 times nominal continuously
1.5 times nominal for 10 seconds
May be: single-phase; three-phase, three wire; or three-phase, four
wire
Current Sensing Inputs
1 or 5 ampere input @ 1 VA per phase
2 times nominal continuously
10 times nominal for 1 second
General Information 1-5
Outputs:
Resistive:
120/240 Vac
125/250 Vdc
30 Vdc
Inductive:
120/240 Vac, 125 Vdc
30 Vdc
Contact Ratings
Make 30 A for 0.2 seconds, carry 7 A continuously, break 7 A.
Make and carry 30 A for 0.2 seconds, carry 7 A continuously, break,
0.3 A
10 A
Make and carry 30 A for 0.2 seconds, carry 7A continuously, break, 0.3 A
(L/R=0.04)
5 A
UL Recognized/CSA Certified UL Recognized per Standard 508, UL File No. E97033. CSA Certified
per Standard CAN/CSA-C22.2 No. 14-M91, CSA File No. LR 23131.
Patent
Patented in U.S., 1997, U.S. Patent No. 5,309,312.
Isolation 2000 Vac for one minute between ground and voltage sensing inputs.
500 Vac for one minute between ground and any of the following groups
or between any of the following groups. Surge suppression components
are used on all case output terminals. Nominal leakage currents as
shown in the following paragraph will result.
Group Nominal Leakage Current
Voltage sensing inputs 63 mAac or 30 mAdc
Battery and contact sensing inputs 20 mAac or 7 mAdc
Current transformer inputs 5 mAac or 1 mAdc
RS-232 terminals 6 mAac or 1 mAdc
Contact outputs 31 mAac or 1 mAdc
Table 1-1. 51V Time Characteristic Curve Constants
BE3-GPR
Curve Curve BE Curve Name Trip Characteristic Constants
Number Selection A B C N K
1 S1 S1, Short Inverse 0.2663 0.03393 1.000 1.2969 0.028
2 S2 S2, Short Inverse 0.0286 0.0280 1.000 0.9844 0.028
3 L1 L1, Long Inverse 5.6143 2.18592 1.000 1.000 0.028
4 L2 L2, Long Inverse 2.3955 0.00000 1.000 0.3125 0.028
5 D D, Definite Time 0.4797 0.21359 1.000 1.5625 0.028
6 M M, Moderately Inverse 0.3022 0.12840 1.000 0.5000 0.028
7 I1 I1, Inverse Time 8.9341 0.17966 1.000 2.0938 0.028
8 I2 I2, Inverse Time 0.2747 0.10426 1.000 0.4375 0.028
9 V1 V1, Very Inverse 5.4678 0.10814 1.000 2.0469 0.028
10 V2 V2, Very Inverse 4.4309 0.09910 1.000 1.9531 0.028
11 E1 E1, Extremely Inverse 7.7624 0.02758 1.000 2.0938 0.028
12 E2 E2, Extremely Inverse 4.9883 0.01290 1.000 2.0469 0.028
13 A Standard Inverse 0.01414 0.00000 1.000 0.0200 0.028
14 B B, Very Inverse (It) 1.4636 0.00000 1.000 1.0469 0.028
15 C Extremely Inverse (I
2
t) 8.2506 0.00000 1.000 2.0469 0.028
16 G Long Time Inverse 12.1212 0.00000 1.000 1.0000 0.028
General Information
1-6
BE3-GPR
Curve Curve BE Curve Name Trip Characteristic Constants
Number Selection A B C N K
17 F Fixed Time 0.0000 1.00000 0.000 0.0000 0.028
Impulse
Qualified to IEC 255-5
Radio Frequency Interference
(RFI)
Field tested using a 5 watt, hand held transceiver operating at random
frequencies centered around 144 Mhz and 440 Mhz, with the antenna
located 6 inches from the relay in both horizontal and vertical planes.
Surge Withstand Capability:
Oscillatory
Fast transient
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems
Vibration: 10 to 500 Hz at 2 Gs in three mutually perpendicular planes.
Shock: 15 Gs in each of three mutually perpendicular axes.
Temperature:
Operating Range:
Storage Range:
-25
°
C (-13
°
F) to +60
°
C (+140
°
F)
-40
°
C (-40
°
F) to +85
°
C (+185
°
F)
Weight: 4 lb.
STYLE CHART
BE3-GPR relays are identified by a combination of letters and numbers that make up the style number
and define the electrical characteristics and operational features. The model number, together with the
style number, describe the options included in a specific device and appear on a relay side panel.
Upon receipt of a relay, be sure to check the style number against the requisition and the packing list to
ensure that they agree.
Figure 1-2 is the style number identification chart and defines the electrical characteristics and operational
features included in BE3-GPR relays. In this example, a BE3-GPR P2BVSF is specified and has the
following features:
P - Paralleled generator protection
2 - Neutral ground fault protection
B- Phase balance
V - Reactive current
S - Sync check function
F - Semi-flush mounting
General Information 1-7
BE3-GPR
S - STAND ALONE
P - PARALLELED GEN
1 - 3-PHASE OVERCURRENT
2 - NEUTRAL GROUND FAULT
N - NO PHASE BALANCE
B - PHASE BALANCE
V - REACTIVE CURRENT
S - SYNC-CHECK
MODEL TYPE
OPTION 1
OPTION 2
OPTION 4
OPTION 3
0 - NO REACTIVE CURRENT
N - NO SYNC-CHECK
*
*
P2B VS
PHASE BALANCE
REACTIVE CURRENT
SYNC-CHECK
NOTE: * Paralleled models only.
D2224-13
08-04-98
OVERCURRENT TYPE
F
CONFIGURATION
F - SEMI-FLUSH
B - BEHIND-THE-PANEL
MOUNTING
Figure 1-2. BE3-GPR Style Chart
TIME OVERCURRENT CHARACTERISTIC CURVES
Figures 1-2 through 1-17 illustrate the characteristic curves that are programmed into the nonvolatile
memory of this relay. A drawing number is given under each caption and listed in Table 1-2. Table 1-2
also cross references the BE3-GPR curves to existing electromechanical relay characteristics. Contact
Customer Service Department of the Power Systems Group, Basler Electric, and request the drawing
number to order a full-size (10 inch x 12 inch) Characteristic Curve graph on transparent paper (vellum).
Table 1-2. Characteristic Curve Cross Reference
Curve
Number
BE3-GPR
Curve
Curve Name Drawing NO. Similar To
1 S1 S1, Short Inverse 99-1369 ABB CO-2
2 S2 S2, Short Inverse 99-1595 GE IAC-55
3 L1 L1, Long Inverse 99-1370 ABB CO-5
4 L2 L2, Long Inverse 99-1594 GE IAC-66
5 D D, Definite Time 99-1371 ABB CO-6
6 M M, Moderately Inverse 99-1372 ABB CO-7
7 I1 I1, Inverse Time 99-1373 ABB CO-8
8 I2 I2, Inverse Time 99-1597 GE IAC-51
9 V1 V1, Very Inverse 99-1374 ABB CO-9
10 V2 V2, Very Inverse 99-1596 GE IAC-53
11 E1 E1, Extremely Inverse 99-1375 ABB CO-11
12 E2 E2, Extremely Inverse 99-1598 GE IAC-77
13 A Standard Inverse 99-1621 BS, IEC Standard Inverse
14 B B, Very Inverse (It) 99-1376 BS, IEC Very Inverse (It)
15 C Extremely Inverse (I
2
t) 99-1377 BS, IEC Extremely Inverse (I
2
t)
16 G Long Time Inverse 99-1622 BS, IEC Long Time Inverse
17 F Fixed Time
General Information
1-8
General Information 1-9
Figure 1-2. Time Characteristic Curve S1, Short Inverse, 99-1369, (Similar to ABB CO-2)
General Information
1-10
Figure 1-3. Time Characteristic Curve S2, Short Inverse, 99-1595 (Similar To GE IAC-55)
General Information 1-11
Figure 1-4. Time Characteristic Curve L1, Long Inverse, 99-1369, (Similar to ABB CO-5)
General Information
1-12
General Information 1-13
Figure 1-5. Time Characteristic Curve L2, Long Inverse, 99-1594, (Similar To GE IAC-66)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91