Mitsubishi MXZ-32SV User manual

Category
Split-system air conditioners
Type
User manual
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. INDOOR/OUTDOOR
CORRESPONDENCE TABLE···························3
4. INDOOR UNITS COMBINATION·······················4
5. SPECIFICATION·················································8
6. NOISE CRITERIA CURVES······························ 9
7. OUTLINES AND DIMENSIONS ······················ 10
8. WIRING DIAGRAM···········································11
9. REFRIGERANT SYSTEM DIAGRAM··············12
10. PERFORMANCE CURVES······························13
11. MICROPROCESSOR CONTROL·····················19
12. TROUBLESHOOTING······································25
13. DISASSEMBLY INSTRUCTIONS·····················37
14. PARTS LIST······················································40
15. OPTIONAL PARTS···········································43
Inverter-controlled multi system
Model
MXZ-32SV -
MXZ-32SV - E2
E1
No. OB254
REVISED EDITION-A
This manual describes technical data of outdoor unit.
For indoor unit refer to the service manuals No. OB229, OB227 REVISED EDITION-B, OB252, OB212, OB239
and OC165 of corresponding models.
Model indication
Revision:
MXZ-32SV - has been added.
• Please void OB254.
E2
SPLIT-TYPE, HEAT PUMP AIR CONDITIONER
OB254-1.qxp 03.1.16 4:33 PM Page 1
PART NAMES AND FUNCTIONS
2
OUTDOOR UNIT Air inlet
Air outlet
(back and side)
Model indication
MXZ-32SV-
MXZ-32SV- E2
E1
2
TECHNICAL CHANGES
1
MXZ-32RV - MXZ-32SV -
1. The combination pattern of the indoor unit has increased.
2. Crankcase heater has disused.
3. Refrigerant circuit has changed.
• Disuse of 2-way valve.
• Disuse of capillary tube [3 o[2 o500.
• Disuse of low pressure switch.
• Disuse of suction pipe temperature thermistor.
MXZ-32SV - MXZ-32SV -
1. Combinations of the connectable indoor units have increased.
2. Noise filter P.C. board has changed to improve the capacity for protecting the inverter-controlled circuit when the
voltage higher than the rated one is aupplied with the inverter-controlled circuit.
3. Noise filter P.C. board for “E1” and “E2” are not interchangeable.
4. Service parts have been changed as follows according to above change;
•The value of R(resistor)has changed. 1020
•TB6(terminal block) has been removed.
E2E1
E1E1
OB254-1.qxp 03.1.16 4:33 PM Page 2
3
3INDOOR / OUTDOOR CORRESPONDENCE TABLE
There is no combination other than this table.
MXZ-32SV- E1 , MXZ-32SV- E2
OUTDOOR UNIT
Combination of the connectable indoor units
07+07
07+09
07+12
07+18
09+09
09+12
09+18
12+12
12+18
18+18
07+07+07
07+07+09
07+07+12
07+07+18
07+09+09
07+09+12
07+09+18
07+12+12
07+12+18
07+18+18
09+09+09
09+09+12
09+09+18
09+12+12
09+12+18
09+18+18
12+12+12
12+12+18
07+07+07+07
07+07+07+09
07+07+07+12
07+07+07+18
07+07+09+09
07+07+09+12
07+07+09+18
07+07+12+12
07+07+12+18
07+09+09+09
07+09+09+12
07+09+09+18
07+09+12+12
09+09+09+09
09+09+09+12
09+09+09+18
09+09+12+12
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU).
MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
OB254-1.qxp 03.1.16 4:33 PM Page 3
4
07
09
12
18
07+07
07+09
07+12
07+18
09+09
09+12
09+18
12+12
12+18
18+18
07+07+07
07+07+09
07+07+12
07+07+18
07+09+09
07+09+12
07+09+18
07+12+12
07+12+18
07+18+18
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
3.47
4.17
6.67
10.65
7.13
7.50
10.56
14.31
8.80
12.64
17.31
18.33
18.33
18.33
10.19
11.25
13.80
13.80
12.96
13.80
13.80
13.80
13.80
13.80
3.79
4.55
7.27
11.62
7.78
8.18
11.52
15.61
9.60
13.79
18.89
20.00
20.00
20.00
11.11
12.27
15.05
15.05
14.14
15.05
15.05
15.05
15.05
15.05
2.2
(0.9-2.7)
2.8
(0.9-3.2)
4.0
(0.9-4.5)
5.0
(0.9-5.4)
4.4
(1.8-5.4)
5.0
(1.8-5.8)
6.2
(1.8-6.6)
7.2
(1.8-7.7)
5.6
(1.8-6.2)
6.8
(1.8-7.3)
7.8
(1.8-8.5)
8.0
(1.8-8.8)
8.0
(1.8-8.8)
8.0
(1.8-8.8)
6.6
(2.4-8.1)
7.2
(2.4-8.6)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
7.8
(2.4-8.9)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
0.75
(0.26-0.93)
0.90
(0.26-1.04)
1.44
(0.26-1.70)
2.30
(0.26-2.98)
1.54
(0.58-1.96)
1.62
(0.58-2.05)
2.28
(0.58-2.51)
3.09
(0.58-3.65)
1.90
(0.58-2.18)
2.73
(0.58-3.22)
3.74
(0.58-4.56)
3.96
(0.58-4.90)
3.96
(0.58-4.90)
3.96
(0.58-4.90)
2.20
(0.70-3.65)
2.43
(0.70-4.11)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.80
(0.70-4.23)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.2
2.8
3.8
4.2
2.8
3.6
4.0
3.1
3.6
3.25
-
-
-
-
2.2
2.8
4.0
5.0
2.8
4.0
5.0
4.0
4.5
4.0
2.2
2.2
2.1
1.9
2.8
2.5
2.3
3.1
2.8
3.25
2.2
2.8
4.0
5.0
2.2
2.2
2.2
2.2
2.8
2.8
2.8
4.0
3.5
4.0
2.2
2.2
2.1
1.9
2.2
1.9
1.7
1.8
1.6
1.5
Indoor units
combination Unit A Unit B Unit C Unit D
Cooling capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A) Power
factor
(%)
220V 240V
NOTE: Electrical data is for outdoor unit only.
MXZ-32SV - E1 , MXZ-32SV - E2
INDOOR UNITS COMBINATION
4
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU).
MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
OB254-1.qxp 03.1.16 4:33 PM Page 4
5
Indoor units
combination Unit A Unit B Unit C Unit D
Cooling capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A) Power
factor
(%)
220V 240V
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.80
13.08
13.08
13.08
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
15.05
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
-
-
-
-
-
-
-
-
2.0
2.4
2.9
3.5
2.2
2.8
3.2
2.6
3.0
2.1
2.7
3.1
2.45
2.0
2.6
3.0
2.35
2.67
3.4
3.8
3.0
3.4
3.1
2.67
3.1
2.0
1.87
1.7
1.5
2.2
2.0
1.8
2.6
2.4
2.1
1.9
1.75
2.45
2.0
1.8
1.67
2.35
2.67
2.3
2.1
2.0
1.9
1.8
2.67
2.45
2.0
1.87
1.7
1.5
1.8
1.6
1.5
1.4
1.3
1.7
1.5
1.4
1.35
2.0
1.8
1.67
1.65
2.67
2.3
2.1
3.0
2.7
3.1
2.67
2.45
2.0
1.87
1.7
1.5
1.8
1.6
1.5
1.4
1.3
2.1
1.9
1.75
1.75
2.0
1.8
1.67
1.65
09+09+09
09+09+12
09+09+18
09+12+12
09+12+18
09+18+18
12+12+12
12+12+18
07+07+07+07
07+07+07+09
07+07+07+12
07+07+07+18
07+07+09+09
07+07+09+12
07+07+09+18
07+07+12+12
07+07+12+18
07+09+09+09
07+09+09+12
07+09+09+18
07+09+12+12
09+09+09+09
09+09+09+12
09+09+09+18
09+09+12+12
NOTE: Electrical data is for outdoor unit only.
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU).
MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
OB254-1.qxp 03.1.16 4:33 PM Page 5
6
NOTE: Electrical data is for outdoor unit only.
07
09
12
18
07+07
07+09
07+12
07+18
09+09
09+12
09+18
12+12
12+18
18+18
07+07+07
07+07+09
07+07+12
07+07+18
07+09+09
07+09+12
07+09+18
07+12+12
07+12+18
07+18+18
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
5.23
6.11
8.84
10.65
8.94
9.49
11.81
12.41
10.88
12.13
12.87
12.87
12.87
12.87
11.20
11.57
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
5.71
6.67
9.65
11.62
9.75
10.35
12.88
13.54
11.87
13.23
14.04
14.04
14.04
14.04
12.22
12.63
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
3.2
(0.9-4.1)
4.0
(0.9-4.8)
6.0
(0.9-7.2)
7.1
(0.9-7.8)
6.4
(1.8-7.2)
7.2
(1.8-8.7)
8.6
(1.8-10.6)
9.0
(1.8-10.9)
8.0
(1.8-10.1)
8.8
(1.8-10.8)
9.3
(1.8-11.2)
9.3
(1.8-11.2)
9.3
(1.8-11.2)
9.3
(1.8-11.2)
8.6
(2.1-10.6)
9.0
(2.1-11.1)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
1.13
(0.27-1.60)
1.32
(0.27-1.70)
1.91
(0.27-2.57)
2.30
(0.27-2.83)
1.93
(0.48-2.30)
2.05
(0.48-2.68)
2.55
(0.48-3.80)
2.68
(0.48-3.89)
2.35
(0.48-3.56)
2.62
(0.48-3.86)
2.78
(0.48-3.98)
2.78
(0.48-3.98)
2.78
(0.48-3.98)
2.78
(0.48-3.98)
2.42
(0.52-3.00)
2.50
(0.52-3.30)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.87
3.5
4.5
4.9
3.3
4.25
4.6
3.65
4.05
3.8
-
-
-
-
3.2
4.0
5.4
6.2
4.0
5.3
5.95
4.65
5.0
4.65
2.87
2.75
2.4
2.2
3.3
2.8
2.6
3.65
3.4
3.8
3.2
4.0
6.0
7.1
3.2
3.2
3.2
2.8
4.0
3.5
3.35
4.65
4.3
4.65
2.87
2.75
2.4
2.2
2.7
2.25
2.1
2.0
1.85
1.7
Indoor units
combination Unit A Unit B Unit C Unit D
Heating capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A) Power
factor
(%)
220V 240V
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU).
MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
OB254-1.qxp 03.1.16 4:33 PM Page 6
7
Indoor units
combination Unit A Unit B Unit C Unit D
Heating capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A) Power
factor
(%)
220V 240V
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
-
-
-
-
-
-
-
-
2.32
2.7
3.6
3.9
2.55
3.4
3.75
3.05
3.3
2.45
3.25
3.65
2.9
2.32
3.15
3.45
2.8
3.1
4.0
4.4
3.5
3.8
3.65
3.1
3.5
2.32
2.2
1.9
1.8
2.55
2.3
2.15
3.05
2.8
2.45
2.15
2.0
2.9
2.32
2.05
1.95
2.8
3.1
2.65
2.45
3.5
3.3
3.65
3.1
2.9
2.32
2.2
1.9
1.8
2.1
1.8
1.7
1.6
1.6
2.45
2.15
2.0
1.95
2.32
2.05
1.95
1.85
3.1
2.65
2.45
2.3
2.2
2.0
3.1
2.9
2.32
2.2
1.9
1.8
2.1
1.8
1.7
1.6
1.6
1.95
1.75
1.65
1.55
2.32
2.05
1.95
1.85
09+09+09
09+09+12
09+09+18
09+12+12
09+12+18
09+18+18
12+12+12
12+12+18
07+07+07+07
07+07+07+09
07+07+07+12
07+07+07+18
07+07+09+09
07+07+09+12
07+07+09+18
07+07+12+12
07+07+12+18
07+09+09+09
07+09+09+12
07+09+09+18
07+09+12+12
09+09+09+09
09+09+09+12
09+09+09+18
09+09+12+12
NOTE: Electrical data is for outdoor unit only.
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU).
MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
OB254-1.qxp 03.1.16 4:33 PM Page 7
8
5SPECIFICATION
Outdoor model
Indoor units number
Indoor units total capacity (Connectable)
indoor units total capacity (Simultaneous operation)
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Crankcase heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level (Hi)
Fan speed (Hi)
Fan speed regulator
Refrigerant filling
capacity(R-22)
Refrigerating oil (Model)
Thermistor RT61
Thermistor RT62
Thermistor RT63
Thermistor RT65
Thermistor RT66,67
Thermistor RT68,69
kW
R/h
K /h
A
A
W
A(kW)
W
%
A
A
A
W
"
"
mm
kg
dB
rpm
kg
cc
k"
k"
k"
k"
k"
k"
Compressor Electrical
data
Fan
motor
Special
remarks
Capacity System
Coefficient of performance(C.O.P)
Outdoor unit power supply
MXZ-32SV - E1 , MXZ-32SV - E2
Single phase
220-240V,50Hz
2 to 4
Total model name 42
Total model name 42
Max. 60
Max. 25
10
10
2400-2640
25
90.0
15.05-13.80
0.6
THV-247FBA (ROTARY)
2100
U-V 0.61
V-W 0.61 W-U 0.61
RA6V60-BA
WHT-BLK 78.7 BLK-YLW 26.9
YLW-BLU 11.7 BLU-RED 83.6
900o900o320 (+35)
79
630-675
3
3.9
870 (MS-56)
13.4 (at 100:)
10.0 (at 25:)
17.0 (at 50:)
10.0 (at 25:)
10.0 (at 25:)
10.0 (at 25:)
Cooling
8.0 (0.9~9.0)
15.05-13.80
2980(260~4270)
15.71-14.35
2.68
45-47
Heating
9.3 (0.9~11.6)
14.04-12.87
2780(270~3500)
13.44-12.27
3.35
46-48
TEST CONDITIONS COOLING INDOOR DB27.0°C WB19.0°C
OUTDOOR DB35.0°C WB24.0°C
HEATING INDOOR DB20.0°C
OUTDOOR DB 7.0°C WB 6.0°C
1 Electrical data is for only outdoor unit.
OB254-1.qxp 03.1.16 4:33 PM Page 8
9
NOISE CRITERIA CURVES6
90
80
70
60
50
40
30
20
10 63 125 250 500 1000 2000 4000 8000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35: WB24:
Heating :DB 7:WB 6:
COOL(220V)
NOTCH
COOL(240V)
HEAT(220V)
HEAT(240V)
45
SPL(dB(A))
47
46
48
LINE
MXZ-32SV - E1
MXZ-32SV - E2
OB254-1.qxp 03.1.16 4:33 PM Page 9
10
OUTLINES AND DIMENSIONS
7
MXZ-32SV -
MXZ-32SV -E2
E1
Unit: mm
OUTDOOR UNIT
23
10 35320 900
88
460
50
900
350.0
480.8
531.3
317 23
33
Handle for
moving Air in
Indoor and
outdoor
connect wiring
2345 hole
Air in
D unit connection
C unit connection
B unit connection
A unit connection
6.35 (flared) 1/4
Liquid pipe
12.7 (flared) 1/2 (A , B unit)
9.52 (flared) 3/8 (C , D unit)
[
[
[
1.Installation space
2.Service space
More than
100
More than
200
More than
100
More than
500
More than
500
More than
100 More than
100
More than
350
Base bollt length
Less than
25
More than
350
More than
350
Service space
Air in
2-U-shape notched holes
(Base bolt M10)
(Base bolt M10)
Air in
Air out
200 200
387
355
27 40
(16) (16)
500
Veranda Base
Rubber cushion
More than
500
Note : Leave front and both sides
clearance fully. Note : Obsacle on front and rear sid only.
The unit can be used by attaching an optional
outdoor outlet guide (MAC-855SG)
(but both sides and the top are opend.)
Note : Leave front and overhead
clearance fully.
Note : Leave front, overhead and
both clearance fully.
2-12 36 Oval hole
OB254-1.qxp 03.1.16 4:33 PM Page 10
11
WIRING DIAGRAM
8
POWER SUPPLY
~/N 220-240V
50Hz
INDOOR
UNIT (A)
CIRCUIT BRAKER
TB2
TB3 BLU
RED
TB4
X64
GRN/YLW
GRN
CN720
CN601
0
4
X64
LD62
CN913
CN791
CN901
64
2
CN902
CN851 CN852
MF61
21S4
12
21
21
12
12
34
123456
1234567
123456
C65
LD63
LD64
LDB
LDB
LD61
LDE
L61
F911
SSR61
X63
X62
X61
1
6
L
N
3
N
INDOOR
UNIT (B) BLU
ORN
CN602
12
3
3
3
N
INDOOR
UNIT (C) BLU
YLW
CN603
12
N
INDOOR
UNIT (D) BLU
BRN
CN604
12
N
BLK
BRN
GRY
BLK
BLK WHT
YLW
RED
RED
RED
BRN
BLU
ORN
YLW
WHT
ORN
WHT
BLK
BLU
YLW
RED
ORN ORN RED RED
YLW
YLW
BLK
BLK
ORN
ORN
BRN
GRY
X65
X66
X67
63H2
CN552
CN553
BLK
RELAY
P.C. BOARD
WHT
WHT
RED
WHT
V
UW
AKL
WHT
NOISE FILTER
P.C.BOARD
RED DS61 DS62
C61
CT
61
C63 C62
++
-
+
-
+
-
-
BLKREDR
BLU
LEV A
CN792
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV B
CN793
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV C
CN794 CN722 CN663
63H1 RT63
123456 CN662
1234567812 1234
RED
RED
RED
BLK
BLK
RT66 RT68
RT67 RT69
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
CN661
CN705
7654321
CN515
1234
4321
CN801
CN501
TAB62
TAB63
T801
CT62
TAB66
TAB65
TAB64
I.P.M P.C. BOARD
F801
(1A)
CN704
CN514
CN554CN551
12345678
RT62
RT61
RT65
GRY
GRY
BLK
BLK
GRY
GRY
BRN
BLU
ORN
YLW
WHT
LEV D
ELECTRONIC CONTROL P.C. BOARD
MC
PE
(1A)
FROM INDOOR UNIT
CONNECTING 12V
SYMBOL
C61
C62,63
C65
CT61,62
DS61
DS62
F801
F911
L
L61
SYMBOL
LEV A~D
MC
MF61
R
RT61
RT62
RT63
RT65
RT66,67
RT68,69
NAME
POWER FACTOR CAPACITOR
SMOOTHING CAPACITOR
OUTDOOR FAN CAPACITOR
CURRENT TRANSFORMER
DIODE MODULE
DIODE STACK
FUSE (1A)
FUSE (1A)
REACTOR
COMMON MODE CHOKE COIL
NAME
EXPANSION VALVE
COMPRESSOR
OUTDOOR FAN MOTOR (INNER FUSE)
RESISTOR
DISCHARGE TEMPERATURE THERMISTOR
DEFROST TEMPERATURE THERMISTOR
EVAPORATION TEMPERATURE THERMISTOR
FIN TEMPERATURE THERMISTOR
GAS PIPE TEMPERATURE THERMISTOR
GAS PIPE TEMPERATURE THERMISTOR
SYMBOL
SSR61
T801
TB2,3,4
X61,62,63
X64,65
X66,67
21S4
63H1
63H2
NAME
SOLENOID COIL RELAY
TRANSFORMER
TERMINAL BLOCK
FAN MOTOR RELAY
RELAY
RELAY
R.V. COIL
HIGH PRESSURE SWITCH
HIGH PRESSURE SWITCH
NOTE: 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symboles below indicate. : Terminal block : Connector
POWER SUPPLY
~/N 220-240V
50Hz
INDOOR
UNIT (A)
CIRCUIT BRAKER
TB1
TB2 BLU
RED
X64
GRN/YLW
GRN
CN720
CN601
0
4
X64
LD62
CN913
CN791
CN901
64
2
CN902
CN851 CN852
MF61
21S4
12
21
21
12
12
34
123456
1234567
123456
C65
LD63
LD64
LDB
LDB
LD61
LDE
L61
F911
SSR61
X63
X62
X61
1
6
L
N
3
N
INDOOR
UNIT (B) BLU
ORN
CN602
12
3
3
3
N
INDOOR
UNIT (C) BLU
YLW
CN603
12
N
INDOOR
UNIT (D) BLU
BRN
CN604
12
N
BLK
BRN
GRY
BLK
BLK WHT
YLW
RED
RED
RED
BRN
BLU
ORN
YLW
WHT
ORN
WHT
BLK
BLU
YLW
RED
ORN ORN RED RED
YLW
YLW
BLK
BLK
ORN
ORN
BRN
GRY
X65
X66
X67
63H2
CN552
CN553
BLK
RELAY
P.C. BOARD
WHT
WHT
RED
WHT
V
UW
AKL
WHT
NOISE FILTER
P.C.BOARD
RED DS61 DS62
C61
CT
61
C63 C62
++
-
+
-
+
-
-
BLK
REDR
BLU
LEV A
CN792
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV B
CN793
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV C
CN794 CN722 CN663
63H1 RT63
123456 CN662
1234567812 1234
RED
RED
RED
BLK
BLK
RT66 RT68
RT67 RT69
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
CN661
CN705
7654321
CN515
1234
4321
CN801
CN501
TAB62
TAB63
T801
CT62
TAB66
TAB65
TAB64
I.P.M P.C. BOARD
F801
(1A)
CN704
CN514
CN554CN551
12345678
RT62
RT61
RT65
GRY
GRY
BLK
BLK
GRY
GRY
BRN
BLU
ORN
YLW
WHT
LEV D
ELECTRONIC CONTROL P.C. BOARD
MC
PE
(1A)
FROM INDOOR UNIT
CONNECTING 12V
SYMBOL
C61
C62,63
C65
CT61,62
DS61
DS62
F801
F911
L
L61
LEV A~D
SYMBOL
MC
MF61
R
RT61
RT62
RT63
RT65
RT66,67
RT68,69
SSR61
T801
NAME
POWER FACTOR CAPACITOR
SMOOTHING CAPACITOR
OUTDOOR FAN CAPACITOR
CURRENT TRANSFORMER
DIODE MODULE
DIODE STACK
FUSE (1A)
FUSE (1A)
REACTOR
COMMON MODE CHOKE COIL
EXPANSION VALVE
NAME
COMPRESSOR
OUTDOOR FAN MOTOR (INNER FUSE)
RESISTOR
DISCHARGE TEMPERATURE THERMISTOR
DEFROST TEMPERATURE THERMISTOR
EVAPORATION TEMPERATURE THERMISTOR
FIN TEMPERATURE THERMISTOR
GAS PIPE TEMPERATURE THERMISTOR
GAS PIPE TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
TRANSFORMER
SYMBOL
TB1,2,3,4,5
X61,62,63
X64,65
X66,67
21S4
63H1
63H2
F912
NR63
NAME
TERMINAL BLOCK
FAN MOTOR RELAY
RELAY
RELAY
R.V. COIL
HIGH PRESSURE SWITCH
HIGH PRESSURE SWITCH
FUSE(3.15A)
VARISTOR
NOTE: 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symboles below indicate. : Terminal block : Connector
TB3
TB4
TB5
(3.15A)
NLD65
F912
NR63
SG79Y085H01
MODELS MXZ-32SV- E1
OUTDOOR UNIT
MODELS MXZ-32SV- E2
OB254-1.qxp 03.1.16 4:33 PM Page 11
12
REFRIGERANT SYSTEM DIAGRAM
9
Unit:mm
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe,see page BACK COVER.
Indoor unit
Extension pipe diameter
class Pipe diameter
Liquid 6.35(1/4) Liquid 6.35(1/4)
07/09 Gas 9.52(3/8) Gas 9.52(3/8)
Liquid 6.35(1/4) Liquid 6.35(1/4)
12(13) Gas 12.7(1/2) Gas 12.7(1/2)
Liquid 6.35(1/4) Liquid 6.35(1/4)
18 Gas 15.88(5/8) Gas 15.88(5/8)
Outdoor unit union diameter
For Liquid 6.35(1/4)
Indoor unit A Gas 12.7(1/2)
Liquid 6.35(1/4)
Indoor unit B Gas 12.7(1/2)
Liquid 6.35(1/4)
Indoor unit C Gas 9.52(3/8)
Liquid 6.35(1/4)
Indoor unit D Gas 9.52(3/8)
Unit : mm (inch)
Piping length each indoor unit (a, b, c, d) 25m
Total piping length (a+b+c+d) 60m
Height difference between units (H) 10m
Bending point for each unit 25
Total bending point 60
It does not matter which unit is higher.
a
b
c
d
Outdoor
unit
Indoor
units
H
H
H
Indoor unit
DBall valve with
service port
Ball valve with
service port
Distributor
Strainer
Strainer
LEV
Oil
separator
Compressor
High pressure
switch 1
Accumulator
Capillary tube
Reversing valve
Discharge
temperature
thermistor
Evaporation
temperature
thermistor
(RT67)
Defrost
thermistor
Strainer Distributor
Outdoor
heat
exchanger
High pressure
switch 2
Unit D gas pipe temperature thermistor
[9.52
Indoor unit
C
Unit C gas pipe temperature thermistor
[9.52
[6
Indoor unit
B
Unit B gas pipe temperature
thermistor [12
Indoor unit
A
Indoor unit
A
Strainer LEV [6
Indoor unit
B
Strainer LEV [6
Indoor unit
C
Strainer LEV [6
Indoor unit
D
Unit A gas pipe
temperature thermistor
[12
[16 [16
[9.52
[16
Capillary tube
[2.5[0.6 750
[2.5 [0.61000
Capillary tube
[4.0[2.4 400
Capillary tube
Capillary tube
Capillary tube
Capillary tube
[3.0[2.0 200
[3.0[2.0 200
[3.0[2.0 200
[3.0[2.0 200
Refrigerant flow in cooling
Refrigerant flow in heating
Reversing valve coil
heating ON
cooling OFF
MXZ-32SV -
MXZ-32SV -E2
E1
OB254-1.qxp 03.1.16 4:33 PM Page 12
13
10
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB
(2) Indoor outlet air wet-bulb temperature : °CWB
(3) Outdoor intake air dry-bulb temperature : °CDB
(4) Total input: W
(5) Indoor intake air dry-bulb temperature : °CDB
(6) Outdoor intake air wet-bulb temperature : °CWB
(7) Total input : W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 14 and 15 shows the difference
between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your refer-
ence at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT OUTDOOR UNIT
}
}
Cooling
Heating
PERFORMANCE CURVES
Wet-and dry-bulb
thermometers
Wet-and dry-bulb
thermometers
10-1-1.CAPACITY AND THE INPUT CURVES
32.3
29.8
27.3
24.9
22.4
19.9
17.4
14.9
38.2
35.3
32.4
29.4
26.5
23.5
20.6
17.6
25.9
23.9
21.9
19.9
17.9
15.9
13.9
11.9
27.7
25.6
23.4
21.3
19.2
17.0
14.9
12.8
07 class
09 class
12 class
18 class
OB254-1.qxp 03.1.16 4:33 PM Page 13
14
10-3-.2.Capacity and input correction by inverter output frequency
(OUTDOOR UNIT:MXZ-32SV)
The dotted line on graphs connects the frequency range in normal operation shown by the full line and the frequency
in test run shown by the point.
0 50 100 150
0.5
1.0
1.5 <COOL>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz 0 50 100 150
0.5
1.0
1.5 <HEAT>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
0 50 100 150
0.5
1.0
1.5 <COOL>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz 0 50 100 150
0.5
1.0
1.5 <HEAT>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
0 50 100 150
0.5
1.0
1.5 <COOL>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz 0 50 100 150
0.5
1.0
1.5 <HEAT>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
0 50 100 150
0.5
1.0
1.5 <COOL>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz 0 50 100 150
0.5
1.0
1.5 <HEAT>Capacity
Frequency Hz 0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
1. 07-class unit in single operation
2. 09-class unit in single operation
3. 12-class unit in single operation
4. 18-class unit in single operation
OB254-1.qxp 03.1.16 4:33 PM Page 14
0 5 10 15 20 25
4
5
6
7
8
9
10
Ambient temperature(:)
45Hz
Outdoor unit current (A)
Ambient temperature(:)/ Ambient humidity(%) Ambient temperature(:)/ Ambient humidity(%)
Outdoor low pressure
(MPa•Gauge)
(kgf/F•Gauge)
Outdoor unit current (A)
15 20 25 30 35
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(;)
(%)
33Hz
15 20 25 30 35
3
4
5
6
7
8
9
(;)
(%)
33Hz
8
7
6
5
4
3
2
15
10-3-4.Outdoor low pressure and outdoor unit current
1. 07-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50
25 60
30 70
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat-
ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
(2) HEAT operation
DB(°C) 20.0
WB(°C) 14.5 DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
2Air flow speed : HI
3Inverter output frequency : 33Hz
OB254-1.qxp 03.1.16 4:33 PM Page 15
16
2. 09-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50
25 60
30 70
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat-
ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
2Air flow speed : HI
3Inverter output frequency : 33Hz
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
(2) HEAT operation
DB(°C) 20.0
WB(°C) 14.5 DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
0 5 10 15 20 25
4
5
6
7
8
9
10
Ambient temperature(:)
45Hz
Outdoor unit current (A)
Ambient temperature(:)/ Ambient humidity(%) Ambient temperature(:)/ Ambient humidity(%)
Outdoor low pressure
(MPa•Gauge)
(kgf/F•Gauge)
Outdoor unit current (A)
15 20 25 30 35
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(;)
(%)
33Hz
15 20 25 30 35
3
4
5
6
7
8
9
(;)
(%)
33Hz
8
7
6
5
4
3
2
OB254-1.qxp 03.1.16 4:33 PM Page 16
17
3. 12-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50
25 60
30 70
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat-
ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
2Air flow speed : HI
3Inverter output frequency : 33Hz
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
(2) HEAT operation
DB(°C) 20.0
WB(°C) 14.5 DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
Ambient temperature(:)/ Ambient humidity(%)
(%) Ambient temperature(:)/ Ambient humidity(%)
0 5 10 15 20 25
4
5
6
7
8
9
10
Ambient temperature(:)
45Hz
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
(MPa•Gauge)
(kgf/F•Gauge)
15 20 25 30 35
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(;)
33Hz
15 20 25 30 35
3
4
5
6
7
8
9
(;)
(%)
33Hz
8
7
6
5
4
3
2
OB254-1.qxp 03.1.16 4:33 PM Page 17
18
4. 18-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50
25 60
30 70
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat-
ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
Air flow speed : HI
Inverter output frequency : 33Hz
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
(2) HEAT operation
DB(°C) 20.0
WB(°C) 14.5 DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
Ambient temperature(:)/ Ambient humidity(%)
0 5 10 15 20 25
4
5
6
7
8
9
10
Ambient temperature(:)
45Hz
Ambient temperature(:)/ Ambient humidity(%)
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
(MPa•Gauge)
(kgf/F•Gauge)
15 20 25 30 35
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(;)
(%)
33Hz
15 20 25 30 35
3
4
5
6
7
8
9
(;)
(%)
33Hz
8
7
6
5
4
3
2
OB254-1.qxp 03.1.16 4:33 PM Page 18
19
MICROPROCESSOR CONTROL
11
Compressor
power
factor
Indoor unit
microprocessor
SSR61 Drive
circuit
Transistor
module
Indoor Unit
A
Indoor Unit
D
Indoor Unit
C
Indoor Unit
BGas pipe
temperature
thermistor
RT66, 67, 68, 69
Accumulator
Comp.
H.P.S 63H2 Discharge
temperature
thermistor
RT61
Indoor Unit
AEvaporation
temperature
thermistor
RT63 Outdoor
fan motor
MF61
x 61
x 62
x 63
Defrost
thermistor
RT62
LEV1
LEV2
LEV3
LEV4
Indoor Unit
B
Indoor Unit
C
Indoor Unit
D
Outdoor unit control microprocessor
Compressor
primary
current
Compressor
secondary
current
Fin temperature
thermistor RT65
R. V. coil
21S4
H.P.S 63H1
Input signal
Output signal
MXZ-32SV -
MXZ-32SV -E2
E1
INVERTER MULTI SYSTEM CONTROL
OB254-1.qxp 03.1.16 4:33 PM Page 19
20
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
The standard opening is on the straight line, which connects an each standard point in the section where divided
into seven according to the operation frequency of compressor as shown in the figure below.
(LEV opening is controlled in proportion to the operation frequency.)
Note: Opening is adjusted at the standard opening according to the indoor unit conditions.
However, inclination of standard opening in each point of opening does not change with the original curve.
Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8,
when capacity of the indoor unit is excluding code 1.
Add opening provided in Difference in Operation number in the table below to determined LEV opening for
each indoor unit, when 2, 3 or 4 indoor units are operated at the same time.
Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual
driving output opening is in a range from 59 to 500 pulse.
< Calculation example of LEV opening >
Cool operation: Compressor frequency 70Hz: 2 unit ON: 18class
(170-150)p(80-60)o(70-60)+150+75-30=205 pulse
Determination of LEV standard opening in each indoor unit
W
hen outdoor unit is operating,
s
ome indoor unit stops and
s
ome operates.
LEV opening for each indoor unit is determined by adding adjustment in accordance
with the number of operating unit and the capacity class to standard opening, based
on the operation frequency:
Ex.) Opening 130 pulse in standard opening 1 Minimum 80 pulse, Maximum 205
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
After starting operation, adjustment in accordance with intake super heat, discharge
temperature is included in standard opening. w1
Note: LEV opening in each frequency at DRY operation and COOL operation is the
same. However, velocity and compressor operation frequency controls are
different. See 11-2 Operational frequency range
(As far as the indoor unit velocity control goes, refer to DRY operation in
MICROPROCESSOR CONTROL in the indoor unit service manual.)
LEV opening for each indoor unit is determined by adding adjustment in accordance
with the number of operating unit and the capacity class to standard opening, based
on the operation frequency:
Ex.) Opening 120 pulse in standard opening 1 Minimum 70 pulse, Maximum 165
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
After starting operation, opening becomes the one that adjustment in accordance
with discharge temperature was added to basic opening. w1
Thermostat ON in HEAT mode
LEV opening
Thermostat OFF in
COOL or DRY mode
T
hermostat OFF in HEAT mode
Stop of all indoor unit
Indoor unit status
COOL : 5 pulse (full closed)
HEAT : 59 pulse (slightly opened)
Thermostat ON in
COOL or DRY mode
Opening before stop 500 pulse in 15 minutes
When the outdoor unit operation (When the other indoor unit operate): 5 pulse.
When outdoor unit stops. (When the other indoor unit stops or thermo off):
Maintain LEV opening before stop 500 pulse in 15 minutes
When the outdoor unit operates. (When the other indoor unit operates): 59 pulse
When the outdoor unit stops. (When the other indoor unit stops or thermo off):
Maintain LEV opening before stop 500 pulse in 15 minutes.
w1 LEV opening when the outdoor unit operating: Upper limit 500, Lower limit 59
7 20 40 60 80 100 120 140
Operation frequency of compressor (Hz) : F
120
130
140
150
160
170
180
190
200
210
220
LEV opening (Pulse)
Standard opening
12345678
COOL
HEAT
11-1.LEV control
OB254-1.qxp 03.1.16 4:33 PM Page 20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44